ECO ECO1000LCD
Lesen Sie kostenlos die đ deutsche Bedienungsanleitung fĂźr Tripp Lite ECO ECO1000LCD (36 Seiten) in der Kategorie Unterbrechungsfreies Stromversorgungssystem. Dieser Bedienungsanleitung war fĂźr 13 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet
Seite 1/36
1
Digital ECO-UPS⢠Systems
Models:
ECO1000LCD, ECO1300LCD, ECO1500LCD
(Series Numbers: AG-87C1, AG-87C2, AG-87C3)
Important Safety Instructions 2 .................
Quick Installation 3
...................................
ECO Energy Saving Setup 4
.......................
Basic Operation 4
.....................................
UPS On/Off 4
..........................................
LCD Screen 5 .........................................
Display UPS/Power Conditions 6
...............
Enable/Disable Alarm 6
...........................
Self-Test
..............................................
6
Error Messages 7
....................................
Features 8
................................................
UPS Features 8
......................................
Battery Replacement 10
...........................
Storage and Service 11
............................
Product Registration and......................12
Regulatory Compliance
EspaĂąol................................................13
Français 25 ...............................................
Ownerâs Manual
1111 W. 35th Street, Chicago, IL 60609 USA ⢠www.tripplite.com/support
Copyright Š 2018 Tripp Lite. All rights reserved.
PROTECT YOUR INVESTMENT!
Register your product for quicker service and ultimate peace of mind.
You could also win an ISOBAR6ULTRA surge protectorâa $100 value!
www.tripplite.com/warranty
2
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the installation, operation and storage of this
product. Failure to heed these warnings may affect the warranty.
UPS Location Warnings
⢠Install your UPS indoors, away from excess moisture or heat, conductive contaminants, dust or direct sunlight.
⢠For best performance, keep the indoor temperature between 32º F and 104º F (0º C and 40º C).
⢠Leave adequate space around all sides of the UPS for proper ventilation.
⢠Only set the UPS upright on a sturdy ďŹat surface. Do not block fans or ventilation holes, as this will seriously inhibit the unit's internal cooling
and cause product damage not covered under warranty.
UPS Connection Warnings
⢠Connect your UPS directly to a properly grounded AC power outlet. Do not plug the UPS into itself; this will damage the UPS.
⢠Do not modify the UPS plug, and do not use an adapter that would eliminate the UPS ground connection.
⢠Do not use extension cords to connect the UPS to an AC outlet.
⢠If the UPS receives power from a motor-powered AC generator, the generator must provide clean, ďŹltered, computer-grade output.
⢠The mains socket outlet that supplies the UPS should be easily accessible and located near the UPS.
Equipment Connection Warnings
Install in accordance with National Electrical Code standards ANSI/NFPA 70 and Canadian Electrical Code, Part I, C22.1.
Short Circuit backup protection and overcurrent protection is provided by the building installation.
To reduce the risk of ďŹre, connect only to a circuit provided branch circuit overcurrent protection in accordance with the
National Electrical Code, ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1. The plug on the power supply
cord is intended to serve as the disconnect device. Be sure that the socket-outlet is installed near the equipment and is
made easily accessible.
⢠Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life
support equipment or to signiďŹcantly affect its safety or effectiveness is not recommended.
⢠Do not connect surge protectors or extension cords to the output of your UPS. This might damage the UPS and may affect the surge
protector and UPS warranties.
⢠Connect the UPS to an outlet that is adequately protected against excess currents, short circuits and earth faults as part of the building
installation.
Battery Warnings
⢠Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. There are no user-
serviceable parts inside the UPS. Do not open the UPS except to perform battery replacement. Do not open batteries. Do not short or
bridge the battery terminals with any object. Do not dispose of batteries in a ďŹre. The batteries may explode. Released material is harmful
to the skin and eyes. It may be toxic. Unplug and turn off the UPS before performing battery replacement. Use tools with insulated handles.
Battery replacement should be performed only by authorized service personnel using the same number and type of batteries (Sealed Lead-
Acid). Do not dispose of the batteries in a ďŹre. The batteries are recyclable. Refer to your local codes for disposal requirements or in the
USA only call 1-800-SAV-LEAD or 1-800-8-BATTERY (1-800-822-8837) or visit www.rbrc.com for recycling information. Tripp Lite offers a
complete line of UPS System Replacement Battery Cartridges (R.B.C.).Visit Tripp Lite on the Web at www.tripplite.com/products/battery-ďŹnder
to locate the speciďŹc replacement battery for your UPS.
Important Safety Instructions
3
STEP 1: Plug the UPS into
a properly grounded outlet.
After plugging the UPS into a wall outlet, press and hold the power button for one second
to turn on the UPS (See ).Basic Operation
Note: The UPS will not turn on automatically in the presence of live utility power.
STEP 2: Plug your equipment into the UPS.
There are two sets of outlets on the back of your UPS. Outlets marked SURGE PROTECTED do
not provide battery backup power during power outages. Connect common desktop items like
printers, scanners and other accessories not requiring battery support to these outlets. Outlets
marked BATTERY & SURGE offer UPS battery backup support during power failures. Connect
your vital computer equipment into these outlets.
Your UPS is designed to support electronic equipment only. You will overload the UPS if
the total volt-amp (VA) ratings for all the equipment connected to the BATTERY/SURGE
PROTECTED outlets exceed the UPS output capacity. To ďŹnd your equipmentâs VA ratings, look
on their nameplates. If the equipment is listed in amps (A), multiply the number of amps by
120 to determine VA. For example: 1A Ă 120 = 120VA. If you suspect you have overloaded
the outlets, check Load Meter screens (see Display UPS/Power Conditions Basic in
Operation).
Optional Installation
All models include USB communication ports and tel/DSL/Ethernet surge protection jacks
(not compatible with PoE applications). These connections are optional, as the UPS will work
properly without these connections.
If the on-line AC power icon does not illuminate when the UPS is turned ON, try the
following:
1. Make sure that the UPS is plugged into a live AC outlet.
2. Press and hold the power button for one second to turn on the UPS. A beep should
sound when the UPS starts.
3. If the UPS still does not start, contact Tripp Lite Tech Support for assistance.
Quick Installation
Produktspezifikationen
Marke: | Tripp Lite |
Kategorie: | Unterbrechungsfreies Stromversorgungssystem |
Modell: | ECO ECO1000LCD |
Display-Typ: | LCD |
Akustische Signale: | Ja |
USB Anschluss: | Ja |
Mitgelieferte Kabel: | USB-Kabel |
Produktfarbe: | Schwarz |
Stecker: | NEMA 5-15P |
Anzahl Ethernet-LAN-AnschlĂźsse (RJ-45): | 1 |
Ursprungsland: | China |
Kabellänge: | 1.8 m |
Betriebsanleitung: | Ja |
Gehäusematerial: | Acrylnitril-Butadien-Styrol (ABS) |
Reaktionszeit: | 0 ms |
Formfaktor: | Tower |
Ausgangsleistung: | 600 W |
Eingangsfrequenz: | 50/60 Hz |
KĂźhlung: | Passiv |
Anzahl der AC-Ausgänge: | 8 AC-Ausgänge |
USV-Topologie: | Line-Interaktiv |
Eingangs-Betriebsspannung (min): | 120 V |
Eingangs-Betriebsspannung (max): | 120 V |
Ausgangskapazität: | 1 kVA |
Ausgangs-Betriebsspannung (min): | 110 V |
Ausgangs-Betriebsspannung (max): | 120 V |
Modem (RJ-11) Port: | 1 |
AC-Steckertypen: | NEMA 5â15R |
Typische Backup-Zeit bei halber Belastung: | 7 min |
Typische Backup-Zeit bei voller Belastung: | 2 min |
Wellenform: | Sine |
Stromstärke (maximal): | 12 A |
EMI/RFI Lautstärkefilter: | Ja |
Akustische Alarm-Modi: | Fault, Low battery alarm, Overload alarm |
Anzahl der Eingangs-Phasen: | 1 |
Effizienz (Online-Modus): | 96 % |
Ăbertragungszeit (Line-Modus in Batterie-Modus): | 6 ms |
Anstieg der Energiemenge: | 316 J |
Buchsen Hauptschalter: | Ja |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Tripp Lite ECO ECO1000LCD benĂśtigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem Tripp Lite
28 April 2024
29 März 2024
27 März 2024
19 März 2024
6 März 2024
2 März 2024
29 Februar 2024
6 Februar 2024
5 Februar 2024
Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem
- Unterbrechungsfreies Stromversorgungssystem Approx
- Unterbrechungsfreies Stromversorgungssystem HP
- Unterbrechungsfreies Stromversorgungssystem Voltcraft
- Unterbrechungsfreies Stromversorgungssystem Siemens
- Unterbrechungsfreies Stromversorgungssystem Schneider
- Unterbrechungsfreies Stromversorgungssystem Lenovo
- Unterbrechungsfreies Stromversorgungssystem Adj
- Unterbrechungsfreies Stromversorgungssystem JUNG
- Unterbrechungsfreies Stromversorgungssystem Block
- Unterbrechungsfreies Stromversorgungssystem Digitus
- Unterbrechungsfreies Stromversorgungssystem APC
- Unterbrechungsfreies Stromversorgungssystem CyberPower
- Unterbrechungsfreies Stromversorgungssystem Eaton
- Unterbrechungsfreies Stromversorgungssystem EnerGenie
- Unterbrechungsfreies Stromversorgungssystem Furman
- Unterbrechungsfreies Stromversorgungssystem Riello
- Unterbrechungsfreies Stromversorgungssystem Steren
- Unterbrechungsfreies Stromversorgungssystem Puls Dimension
- Unterbrechungsfreies Stromversorgungssystem Atlantis Land
- Unterbrechungsfreies Stromversorgungssystem Phoenix Contact
- Unterbrechungsfreies Stromversorgungssystem Middle Atlantic
- Unterbrechungsfreies Stromversorgungssystem Minuteman
- Unterbrechungsfreies Stromversorgungssystem Salicru
- Unterbrechungsfreies Stromversorgungssystem Maruson
- Unterbrechungsfreies Stromversorgungssystem Minute Man
- Unterbrechungsfreies Stromversorgungssystem DEXP
- Unterbrechungsfreies Stromversorgungssystem Bxterra
- Unterbrechungsfreies Stromversorgungssystem Altronix
- Unterbrechungsfreies Stromversorgungssystem FSP
- Unterbrechungsfreies Stromversorgungssystem PowerWalker
- Unterbrechungsfreies Stromversorgungssystem FSP/Fortron
Neueste Bedienungsanleitung fĂźr -Kategorien-
22 Juni 2024
22 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024