MESSUREMENT
AND CONTROL
MEASUREMENT AND CONTROL
GENERAL CHARACTERISTICS
TECHNICAL INFORMATION
DIMENSIONS (mm) CONNECTION DIAGRAM
Code Model Description Dimensions
VE429700 Energy-230 Multi Active single-phase energy meter to multi-times pricing 2 DIN modules
DIRECT CONNECTION
SINGLE-PHASE METER
• Power supply 230 V AC (-15% Ă· +10%) 50 Hz
• Display for the view of the total consumed energy, of partials for each time band, date and
time and cost, for each time band, of consumed energy (if the unit value has been inserted)
• Total not resettable counter (full scale 99999.99)
• Total partial counter (resettable) more 3 partial counters for 3 time bands
• Direct connection max 40 A
• 2 DIN modules format
• Password protected lock keypad
• Precision: class B
• Sealable cover
• Sealable block cover (cover included in the package)
ENERGY-230 MULTI
1 Wide display for displaying of measured consumptions,
divided into time bands
2 Keyboard for parameters setting and to scroll
the various menu pages
3 Energy metering indication led (1 ash = 10 Wh)
or incorrect connection signalling
4 Terminal blocks for the connection of power supply and of load
Active energy meter for single-phase 230 Vac systems designed for displaying consumption divided into
time bands as required by the authority for electricity.
Energy meters
REFERENCE STANDARDS
Compliance with Community Directives: 2006/95/EC (Low voltage) and 2004/108/EC (E.M.C.)
is declared with reference to the following standards: • Safety: EN 61010-1 • E.M. Compatibility: EN 61000-6-2 / EN 61000-6-4 • Metrological requirements EN 50470-1 / EN 50470-3
Current circuit power consumption VA <4
Total energy resolution kWh 0.1
Partial energy resolution kWh 0.1
Operating temperature °C -10 ÷ +45
Storage temperature °C -25 ÷ +70
Humidity 10 Ă· 90% non condensing
Container 2 DIN modules
Protection degree IP20 / 51 Frontal
Power supply 230 (-15 Ă· +10%)V AC
Frequency 50Hz
Absorption VA 5
Starting current Ist mA 20
Minimum current Imin A 0.25
Nominal current Iref A 5
Maximum current Imax A 40
Signalling led Green = powered
Red = flashing
with frequency 10 Wh
Precision Class B
Front view Side view Diagram
Division of time bands as established by the authority for electricity
0:00 7:00 8:00 19:00 23:00 24:00
Mon-Fri
Saturday
Sunday
and holidays
Time band 1 Time band 2 Time band 3
Load
(max 40A)
Energy-230 Multi_201602
1
4
3 2


Produktspezifikationen

Marke: Vemer
Kategorie: Messgeräte
Modell: Energy-230 Multi

Brauchst du Hilfe?

Wenn Sie Hilfe mit Vemer Energy-230 Multi benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Messgeräte Vemer

Bedienungsanleitung Messgeräte

Neueste Bedienungsanleitung fĂ¼r -Kategorien-