Eastron SDM72D-M Bedienungsanleitung

Eastron Messgeräte SDM72D-M

Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Eastron SDM72D-M (12 Seiten) in der Kategorie Messgeräte. Dieser Bedienungsanleitung war für 5 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/12
Eastron SDM72D-M User Manual V1.5
Zhejiang Eastron Electronic Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn Email: sales@eastrongroup.com
- 1 -
Measures active kWh & W.
Resettable partial energy
Bi-directional measurement IMP & EXP
Pulse Output
RS485 Modbus
Din rail mounting 35mm
Direct connection, up to 100A
Better than Class 1/ B accuracy
SDM72D-M
Three Phase Four Wire Energy Meter
User Manual V1.3
2017
Eastron SDM72D-M User Manual V1.5
Zhejiang Eastron Electronic Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn Email: sales@eastrongroup.com
- 2 -
Introduction
The SDM72D-M is digital three phase 4 wire energy meter with a white back-lighted LCD screen for perfect
reading. The unit measures and displays active energy (kWh) and power ( W), imported and exported. A resettable
partial energy is provided, so the user can easily check the energy imported and energy exported during a certain
period. SDM72D-M supports max.100A direct connection, saves the cost and avoid the trouble to connect
external CTs, giving the unit a cost-effective and east operation. Built-in interfaces provides pulse and RS485
Modbus RTU outputs. Configuration is password protected.
PART 1 Specification
General Specifications
Voltage AC (Un) 3x230(400)V
Voltage Range 80~120% Un
Base Current (Ib) 10A AC
Max. Current (Imax) 100A AC
Mini Current (Imin) 5% of Ib AC
Starting current 0.4% of Ib
Power consumption <2W/10VA
Frequency 50/60Hz
AC voltage withstand 4KV for 1 minute
Impulse voltage withstand 6KV-1.2uS wavform
Overcurrent withstand 30max 0I for 0.01s
Pulse output rate 1000imp/kWh (Pulse 2)
Display LCD with backlit
Max. Reading 999999.9kWh
Active energy Class 1 IEC62053-21
Class B EN50470-3
Unit Characteristics
The Unit can measure and display:
Power
Active energy imported and exported
Pulse output indicates real-time energy measurement. An RS485 output allows remote monitoring from another
display or a computer.
RS485 Serial Modbus RTU
This unit uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely monitoring and
controlling the Unit
Set-up screens are provided for setting up the RS485 port.
Eastron SDM72D-M User Manual V1.5
Zhejiang Eastron Electronic Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn Email: sales@eastrongroup.com
- 3 -
Pulse output
The unit provides pulse output for active kWh. The Pulse output is passive type.
The pulse out is fixed up with total kWh. The constant is 1000imp/kWh.
RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication parameters can be configured from the Set-up menu:
Baud rate 1200,2400, 4800, 9600
Parity none (default)/odd/even
Stop bits 1 or 2
RS485 network address nnn – 3-digit number, 001 to 247
Modbus™ Word order Hi/Lo byte order is set automatically to normal or reverse. It cannot be configured
from the set-up menu.
Environment
Operating temperature -25 to +55℃ ℃
Storage and transportation temperature -40 to +70℃ ℃
Reference temperature 23 2℃± ℃
Relative humidity 0 to 95%, non-condensing
Altitude up to 3000m
Warm up time 10s
Installation category CAT III
Mechanical Environment M1
Electromagnetic environment E2
Degree of pollution 2
Mechanics
Din rail dimensions 72x100x66 (WxHxD) DIN 43880
Mounting DIN rail 35mm
Sealing IP51 (indoor)
Material self-extinguishing UL94V-0
PART 2 Operation
Initialization Display
When it is powered on, the meter will initialize and do self-checking.


Produktspezifikationen

Marke: Eastron
Kategorie: Messgeräte
Modell: SDM72D-M

Brauchst du Hilfe?

Wenn Sie Hilfe mit Eastron SDM72D-M benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Messgeräte Eastron

Bedienungsanleitung Messgeräte

Neueste Bedienungsanleitung für -Kategorien-