Eastron SDM630-EV Bedienungsanleitung
Eastron
Messgeräte
SDM630-EV
Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Eastron SDM630-EV (2 Seiten) in der Kategorie Messgeräte. Dieser Bedienungsanleitung war für 9 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet
Seite 1/2
1. Introduction
The SDM630-EV V2 measures and displays the
characteristics of single phase two wires (1p2w),
three phase three wires (3p3w,) and three phase four
wires(3p4w) supplies, including voltage, frequency,
current, power ,active and reactive energy, imported or
exported. Energy is measured in terms of kWh, kVArh.
Maximum demand current can be measured over preset
periods of up to 60 minutes. In order to measure energy,
the unit requires voltage and current inputs in addition to
the supply required to power the product.
SDM630-EV V2 supports max. 100A direct connection,
saves the cost and avoid the trouble to connect external
CTs, giving the unit a cost-effective and easy operation.
Built-in interfaces provides pulse and RS485 Modbus RTU
outputs. Configuration is password protected.
1.2 Measured Parameters
The unit can monitor and display the following parameters
of a single phase two wire(1p2w), three
phase three wire(3p3w) or four phase four wire(3p4w)
supply.
1.3 Voltage and Current
Phase to neutral voltages 100 to 289V a.c.
(not for 3p3w supplies)
Voltages between phases 173 to 500V a.c.
(3p supplies only)
Percentage total voltage harmonic distortion (THD%) for
each phase to N ( not for 3p3w supplies)
Percentage voltage THD% between phases (three phase
supplies only)
Current THD% for each phase
1.4 Power Factor and
Frequency and Max. Demand
Frequency in Hz
Instantaneous power:
Power 0 to 99999 W
Reactive Power 0 to 99999 VAr
Volt-amps 0 to 99999 VA
Maximum demanded power since last Demand reset
Power factor
Maximum neutral demand current, since the last Demand
reset (for 3p4w supply only)
1.5 Energy Measurements
• Imported active energy 0 to 999999.99 kWh
• Exported active energy 0 to 999999.99 kWh
• Imported reactive energy 0 to 999999.99 kVArh
• Exported reactive energy 0 to 999999.99 kVArh
• Total active energy 0 to 999999.99 kWh
• Total reactive energy 0 to 999999.99 kVArh
1.6 Measured Inputs
Voltage inputs through 4-way fixed connector with 25mm²
stranded wire capacity. single phase two wire(1p2w), three
phase three wire(3p3w) or four phase four wire(3p4w)
unbalanced. Line frequency measured from L1 voltage or
L3 voltage.
1.7 Accuracy
• Voltage 0·5% of range maximum
• Current 0·5% of nominal
• Frequency 0·2% of mid-frequency
• Power factor 1% of unity (0.01)
• Active power (W) ±1% of range maximum
• Reactive power (VAr) ±1% of range maximum
• Apparent power (VA) ±1% of range maximum
• Active energy (Wh) Class 1 IEC 62053-21
Class B EN50470-1/3
• Reactive energy (VArh) Class 2 IEC 62053-23
• Response time to step input 1s, typical, to >99% of
final reading, at 50 Hz.
SDM630-EV
DIN Rail Smart Meter for Single and
Three Phase Electrical Systems
The interface performs a
self-test and indicates the
result if the test passes.
The second screen
indicates the firmware
installed in the unit and its
build number.
*The build number(41
01.00) is for reference only.
The actual build number
changes according to
product requirements.
Meter SN, Modbus ID and
baud rate setting
If you have any question, please feel free to contact our sales team. Tel: 0203 758 3494 Email: sales@eastroneurope.com www.eastrongroup.com
Warnings
Important Safety Information is contained in the
Maintenance section. Familiarize yourself with this
information before attempting installation or other
procedures. Symbols used in this document:
Risk of Danger: These instructions contain
important safety information. Read them before
starting installation or servicing of the equipment.
Caution: Risk of Electric Shock
• Measures kWh Kvarh, KW, Kvar, KVA, P, F,
PF, Hz, dmd, V, A, etc.
• Bi-directional measurement IMP & EXP
• Pulse output
• RS485 Modbus
• Din rail mounting 35mm
• 100A direct connection
• Better than Class 1 / B accuracy
1.8 Interfaces for External
Monitoring
Three interfaces are provided:
• 2 RS485 communication channels via protocol remotely.
• Pulse output indicating real-time measured energy.
1.9 Pulse Output
Pulse output is non-configurable. It is fixed up with active
kWh. The constant is 400imp/kWh.
1.10 RS485 Output for
Modbus RTU
There 2 two channels of RS485 Modbus RTU.
For Modbus RTU, the following RS485 communication
parameters can be configured from the
Set-up menu:
• 1st Modbus Output (configurable):
2400, 4800, 9600(default), 19200, 38400 Baud rate
none (default)/odd/even Parity
1 or 2 Stop bits
RS485 network address nnn – 3-digit number,
001 to 247
• 2nd Modbus Pitput (non-configurable):
9600 Baud rate
none Parity
1 Stop bits
Modbus™ Word order Hi/Lo byte order is set
automatically to normal or reverse. It cannot be
configured from the set-up menu.
1.11 Reference Conditions of
Influence Quantities
Influence Quantities are variables that affect measurement
errors to a minor degree. Accuracy is
verified under nominal value (within the specified tolerance)
of these conditions.
• Ambient temperature 23°C ±1°C
• Input frequency 50Hz(MID)
50 or 60Hz ±2%
(non- MID)
• Input waveform Sinusoidal (distortion
factor < 0·005)
• Magnetic field of external origin Terrestrial flux
1.12 Environment
• Operating temperature 3K6(-25°C to
+55°C*),Default
3K7(-40°C to +70°C*)
• Storage temperature -40°C to +70°C*
• Relative humidity 0 to 90%, non-
condensing
• Altitude Up to 2000m
• Warm up time 5S
• Vibration 10Hz to 50Hz,
IEC 60068-2-6, 2g
• Shock 30g in 3 planes
* Maximum operating and storage temperatures are in the context of
typical daily and seasonal variation.
1.13 Unit Characteristics
The Unit can measure and display:
• Line voltage and THD% (total harmonic distortion)
of all phases
• Line Frequency
• Currents, Current demands and current THD% of
all phases
• Power, maximum power demand and power factor
• Active energy imported and exported
• Reactive energy imported and exported
The unit has password-protected set-up screens for:
• Changing password
• Supply system selection 1p2w, 3p3w,3p4w
• Demand Interval Time(DIT)
• Reset for demand measurements
The pulse output indicates real-time energy measurement.
2 RS485 outputs allows remote monitoring from another
display or a computer.
2. Start-up Screens
Selects the Voltage and Current display screens
In Set-up Mode, this is the “Left” or “Back” button.
Select the Frequency and Power factor display
screens
In Set-up Mode, this is the “Up” button
Select the Power display screens
In Set-up Mode, this is the “Down” button
Select the Energy display screens
In Set-up mode, this is the “Enter” or “Right” button
After a short delay, the screen will display active energy
measurements.
2.1 Measurements
The buttons operate as follows:
2.2 Voltage and Current
Each successive pressing of the button selects
a new range:
Phase to neutral
voltages(3p4w)
Phase to neutral
voltages(3p3w)
Current on each phase
Neutral current
2.3 Frequency and Power
Factor and Demand
Each successive pressing of the button selects
a new range:
Power Factor
Maximum Current Demand
Maximum Power Demand
2.4 Power
Each successive pressing of the button selects
a new range:
Instantaneous Active
Power in W
Instantaneous Reactive
Power in VAr
Instantaneous Volt-amps
in VA
Total W, VArh, VA
2.5 Energy Measurements
Each successive pressing of the button selects
a new range:
Total kWh and time will be
showed when no charging
Total kWh and charged
kWh will be showed when
charging
CSID Numbers And current
time will be showed when
charging
Total active kWh, import
active kWh, export active
kWh
Total reactive kWh, import
reactive kWh, export
reactive kWh
2.6 Set-up
To enter set-up mode, pressing the button for 3
seconds, until the password screen appears.
Setting up is password-protected so you must enter the
correct password (default ‘1000’) before processing. If
an incorrect password is entered, the display will show:
PASS Err
To exit setting-up mode, press repeatedly until
the measurement screen is restored.
Setting - Button operation
3 Set-up Entry Methods
Some menu items, such as password, require a four-digit
number entry while others, such as supply system, require
selection from a number of menu options.
3.1 Menu Option Selection
1) Use the and buttons to select the
required item from the menu. Selection does not roll over
between bottom and top of list.
2) Press to confirm your selection.
3) If an item flashes, then it can be adjusted by the
and buttons. If not, there maybe a further layer.
4) Having selected an option from the current layer press
to confirm your selection. The SET indicator will appear.
5) Having completed a parameter setting, press to
return to a higher menu level. The SET indicator will be
removed and you will be able to use the and
buttons for further menu selection.
6) On completion of all set-up, press repeatedly
until the measurement screen is restored.
3.2 Number Entry Procedure
When setting up the unit, some screens require the
entering of a number. In particular, on entry to the setting
up section, a password must be entered. Digits are set
individually, from left to right.
The procedure is as follows:
1) The current digit to be set flashes and is set using
the and buttons.
2) Press to confirm each digit setting. The SET
indicator appears after the last digit has been set.
3) After setting the last digit, press to exit the
number setting routine.
3.3 Main set
System type From the Set-up menu, use and
buttons to select the System option. The screen
will show the currently selected system type.
Password Use the and to choose the change
password option.
Reset Press to enter the selection routine. If succeed,
the cursor will jump back to Reset.
Press to exit the number setting routine and return to the
Set-up menu. SET will be removed.
3.4 Communication set
Addr From the Set-up menu, use and
buttons to select the Address ID.
Baud From the Set-up menu, use and
buttons to select the Baud Rate option.
Parity From the Set-up menu, use
and
buttons to select the Parity option.
3.5 Time set
Data From the Set-up menu, use and
buttons to select the data.
Use to move cursor
Time From the Set-up menu, use
and
buttons to select the data.
Use to move cursor
DMD From the Set-up menu, use
and
buttons to select the dmd. Setting options: 0, 5,
8, 10, 15, 20, 30, 60
ZONE From the Set-up menu, use
and
buttons to select the ZONE. Setting range:-12~12
Backlight From the Set-up menu, use and
buttons to select the Backlight. Setting options:
on,10, 30, 60, 120, off
Use and buttons to select the time interval. Press
to confirm the set-up.
3.6 Record
Record From the Set-up menu, use and
buttons to select record data.
Max.: lastest 10 records
Use and buttons to select the time interval.
1.Main
1.1Sytem Type 3P4W
1.2Password 1000
1.3Reset DMD
2.Communication
2.1Addr 002
2.2Baud 9600
2.3Parity NONE
4.Time
4.1Data 14-01-30
4.2Time 08-15-14
4.3DMD 60
4.Time
4.4ZONE +08
4.5Backlight 060
5.Record
CSID:20140130000005
T: 00:00:03
C: 000006wh
PASSWORD :
0 0 0 0
User Manual
2022 V1.0
If you have any question, please feel free to contact our sales team. Tel: 0203 758 3494 Email: sales@eastroneurope.com www.eastrongroup.com
4. Wiring diagram
• Three Phase Three Wires
CONTACT US
If you have any question, please feel free to contact our
sales team.
Eastron Europe Limited; Suite 20 Cornwallis House, Howard Chase, Basildon,
Essex SS14 3BB.
Tel: 0203 758 3494
Email: sales@eastroneurope.com
www.eastrongroup.com
EU Declaration of Conformity
We, Zhejiang Eastron Electronic Co LTD
No.1369,Chengnan Rd. Jiaxing, Zhejiang, China 314001,
Ensure and declare that electricity meter types:
SDM630- EV
with the measurement range
1. 3 x 230/400V 50Hz, - 0.5 10(100)A 400imp/ kWh.
Are in conformity with the type as described the - examination in EU type certificate
0120/ SGS0151
The fulfillment the essential requirements Annex I the relevant of set out in and in
instrument specific Annexes has been demonstrated.
The electricity meter described conformity with the types above are in relevant Union
harmonization legislation and satisfy the appropriate requirements of the Directive
2014/32/EU with the following standards:
EN50470 1:2006,- Electricity equipment (AC) part metering 1: General requirements,
tests and test conditions. Metering equipment (class indexes A, B and C)
EN50470 3:2006,- Electricity equipment (AC) Part metering 3: Particular requirements-
Static meters for active energy (class indexes A, B and C)
This Declaration of issued the Conformity is under sole responsibility of the
manufacturer.
Signed behalf Zhejiang Eastron Electronic Co., on of LTD.
Signature:
Date: - - 2022 07 05
Position: General Manager
8. EU Declaration of Conformity
7. MID Certificate
• Three Phase Four Wires
• Single Phase Two Wires
5. Dimensions
6. Wiring Torque
Produktspezifikationen
Marke: | Eastron |
Kategorie: | Messgeräte |
Modell: | SDM630-EV |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Eastron SDM630-EV benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Messgeräte Eastron
16 September 2024
14 September 2024
2 August 2024
28 Juli 2024
27 Juli 2024
25 Juli 2024
23 Juli 2024
21 Juli 2024
17 Juli 2024
16 Juli 2024
Bedienungsanleitung Messgeräte
- Messgeräte Basetech
- Messgeräte Hama
- Messgeräte LogiLink
- Messgeräte Nedis
- Messgeräte Panasonic
- Messgeräte Voltcraft
- Messgeräte Bosch
- Messgeräte Flex
- Messgeräte Laserliner
- Messgeräte Vonroc
- Messgeräte Velleman
- Messgeräte Powerfix
- Messgeräte Alecto
- Messgeräte Bresser
- Messgeräte Techno Line
- Messgeräte Technoline
- Messgeräte TFA
- Messgeräte Cocraft
- Messgeräte Skil
- Messgeräte Trotec
- Messgeräte Hema
- Messgeräte Einhell
- Messgeräte Pyle
- Messgeräte Mitsubishi
- Messgeräte Topcom
- Messgeräte Pioneer
- Messgeräte Megasat
- Messgeräte Continental Edison
- Messgeräte Hazet
- Messgeräte Güde
- Messgeräte Perel
- Messgeräte Probuilder
- Messgeräte Wago
- Messgeräte Workzone
- Messgeräte ProfiCare
- Messgeräte Homedics
- Messgeräte Lanaform
- Messgeräte Soehnle
- Messgeräte Bushnell
- Messgeräte Fysic
- Messgeräte Laica
- Messgeräte Amprobe
- Messgeräte Metrix
- Messgeräte Goobay
- Messgeräte IHealth
- Messgeräte Ansmann
- Messgeräte Westfalia
- Messgeräte Honeywell
- Messgeräte Profitec
- Messgeräte Reely
- Messgeräte Holzmann
- Messgeräte MSW
- Messgeräte Midland
- Messgeräte Leica
- Messgeräte Brandson
- Messgeräte Toolland
- Messgeräte Grohe
- Messgeräte ABB
- Messgeräte AS Schwabe
- Messgeräte Kopp
- Messgeräte Hager
- Messgeräte Omnitronic
- Messgeräte Kyoritsu
- Messgeräte GW Instek
- Messgeräte Monacor
- Messgeräte KERN
- Messgeräte Brüder Mannesmann
- Messgeräte Milwaukee
- Messgeräte Aktobis
- Messgeräte Testo
- Messgeräte Elma
- Messgeräte Albrecht
- Messgeräte Kogan
- Messgeräte Peak
- Messgeräte IDEAL
- Messgeräte TrueLife
- Messgeräte Carrier
- Messgeräte VDO
- Messgeräte Digitus
- Messgeräte Eberle
- Messgeräte Testboy
- Messgeräte Fantini Cosmi
- Messgeräte Greenlee
- Messgeräte Multimetrix
- Messgeräte IFM
- Messgeräte Cablexpert
- Messgeräte Extech
- Messgeräte BENNING
- Messgeräte Metrel
- Messgeräte Fluke
- Messgeräte Soler & Palau
- Messgeräte FLIR
- Messgeräte Vemer
- Messgeräte Oregon Scientific
- Messgeräte Finder
- Messgeräte Shimano
- Messgeräte Stabila
- Messgeräte Elgato
- Messgeräte Hikmicro
- Messgeräte Duro Pro
- Messgeräte Enda
- Messgeräte Entes
- Messgeräte GMC Instruments
- Messgeräte Gossen Metrawatt
- Messgeräte Hameg
- Messgeräte Ideal Networks
- Messgeräte Joy-it
- Messgeräte LaCie
- Messgeräte Maximum
- Messgeräte Megger
- Messgeräte Mercury
- Messgeräte Myoton
- Messgeräte Nieaf-Smitt
- Messgeräte PCE Instruments
- Messgeräte PICO
- Messgeräte Psiber
- Messgeräte RK Technology
- Messgeräte Sanwa
- Messgeräte Sekonic
- Messgeräte Skandia
- Messgeräte Sonel
- Messgeräte Uni-T
- Messgeräte Uni-Trend
- Messgeräte Wachendorff
- Messgeräte TFA Dostmann
- Messgeräte Vimar
- Messgeräte Owon
- Messgeräte PeakTech
- Messgeräte Siig
- Messgeräte Comark
- Messgeräte Eltako
- Messgeräte H-Tronic
- Messgeräte Beha-Amprobe
- Messgeräte Chauvin Arnoux
- Messgeräte Electronics International
- Messgeräte Arya
- Messgeräte Emko
- Messgeräte Pancontrol
- Messgeräte Wentronic
- Messgeräte X-Rite
- Messgeräte CESYS
- Messgeräte Trumeter
- Messgeräte Etymotic
- Messgeräte ORNO
- Messgeräte Ebro
- Messgeräte TDE Instruments
- Messgeräte Zircon
- Messgeräte Apollo Ultrasonic
- Messgeräte BJZ
- Messgeräte Adwa
- Messgeräte Greisinger
- Messgeräte Clean Air Optima
- Messgeräte Motrona
- Messgeräte Atmel
- Messgeräte Tru Components
- Messgeräte Qubino
- Messgeräte Janitza
- Messgeräte CEM
- Messgeräte Klein Tools
- Messgeräte J.P. Instruments
- Messgeräte AREXX
- Messgeräte Tempo
- Messgeräte CIRCUTOR
- Messgeräte Camille Bauer
- Messgeräte Seaward
- Messgeräte Dostmann Electronic
- Messgeräte ClimeMET
- Messgeräte Cliff
- Messgeräte Water-i.d.
- Messgeräte Tektronix
- Messgeräte AkYtec
- Messgeräte Aeros
- Messgeräte Aqua Master Tools
- Messgeräte Hanna
- Messgeräte Qualita
- Messgeräte MGL Avionics
- Messgeräte Aerospace Logic
- Messgeräte Johnson Level
- Messgeräte GMW
- Messgeräte SOEKS
- Messgeräte Softing
- Messgeräte Weltron
- Messgeräte Oscium
- Messgeräte Lascar Electronics
- Messgeräte INFICON
- Messgeräte Blebox
- Messgeräte HOZO Design
- Messgeräte Corentium
- Messgeräte GQ
- Messgeräte Murideo
- Messgeräte SecuTech
- Messgeräte NetPeppers
- Messgeräte SensoProtect
- Messgeräte ZKETECH
- Messgeräte LabNation
- Messgeräte MASIMO
- Messgeräte Milesight
- Messgeräte Ermenrich
- Messgeräte Siglent
- Messgeräte Noyafa
- Messgeräte Stamos
Neueste Bedienungsanleitung für -Kategorien-
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024