Plugwise Stealth M Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Plugwise Stealth M (3 Seiten) in der Kategorie Messempfänger. Dieser Bedienungsanleitung war für 20 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/3
Be wise, plug in.
Stealth installaon
Stealth installaon guide
Also applicable to: Stealth+, Stealth M, Stealth M+
Be aware:
The Stealth is speciî„®cally designed
to be built in to an appliance/lighng
î„®xture or as a permanently connected
device in the electrical installaon of
a building. Installaon should always
be executed by a registered installer
in compliance with the local electrical
code (e.g. BS 7671 or NEC).
It is required to include an overcurrent protecve device (circuit breaker),
that support a maximum rang of 16A (depending on your localisaon). Be
sure to switch oî„« the circuit before installing the Stealth!
The product should be installed in a closed î…‡ame retardant casing with a
proper strain-relief mechanism.
Use the L↑ labelled clamp to connect the phase wire to the appliance and
connect the neutral wire to one of the ‘N’ labelled clamps. Then connect
the incoming phase wire to the clamp labelled ‘L’ and the neutral wire to
the free ‘N’ connecon.
For double phase 230V networks the second phase can be connected to the ‘N’ poles
(it will not be switched).
Informaon for the installer
Technical details
Voltage: 100-240 V~ Frequency: 50 / 60 Hz Total max. current: 16 A*
If a normal Stealth with relay is used, these addional maximum rangs apply:
• Inducve load: 4A
• Capacive load: 1A
Exceeding these rangs will adversely aect the service life of the relay!
Dimensions:
57.1 x 39 x 21 mm
ZigBee Dynamic MESH
2.4 GHz
E: helpdesk@plugwise.com T: +31(0) 252 43 30 70 W: www.plugwise.com
* Total max. current Stealth M and M+ : 20A.
All specicaons without prejudice.
See www.plugwise.com for detailed informaon.
Be wise, plug in.
Stealth installaon
Stealth installaon guide
1. Insert screwdriver and move in the direcon of the arrow (up)
2. Insert wire
L L N
Appliance/ circuit
Inverter
N
L
Be aware:
Connect the L↑ (black line) to the appliance to be measured (in this
example the inverter of the solar panel).
Be wise, plug in.
Stealth installaon
Verify the installaon
You can verify the installaon without the need of WiFi/ LAN:
Make sure you have installed the Stealth and Stretch 2.0.
Remember, the Stretch 2.0 must not be connected to LAN!
1. Connect the adapter with the Stretch 2.0 and the wall socket. The Stretch
2.0 will start in WiFi access point mode.
2. Connect your smartphone (installer) with the network of the Stretch via
the WiFi access point.
Password: The Stretch ID (see scker)
3. Go to : hp://192.168.40.40 via the mobile browser on your smartphone.
The Stretch 2.0 web interface starts loading and connues generang a
new appliance for the installed module.
Username: stretch
Password: The Stretch ID (see scker)
4. In case of energy producon (solar panel):
You will noce below the image of the Stealth in the green eld (and
the MAC adress) a negave sign (-) in front of the solar producon if
the installaon has been executed correctly (and if the solar panels
are producing energy). This may take some me. If the installaon is
connected incorrectly there will be no negave sign (-) in front of the
power output.
In case of energy consumpon (appliance):
If the installaon has been executed correctly there will be no negave
sign (-) in front of the power output.


Produktspezifikationen

Marke: Plugwise
Kategorie: Messempfänger
Modell: Stealth M
Breite: 39 mm
Tiefe: 21 mm
Produktfarbe: Black, White
Höhe: 57.1 mm
AC Eingangsfrequenz: 50 - 60 Hz
Nennstrom: 16 A
Eingangsspannung: 100 - 240 V
Funkfrequenz: 2400 MHz

Brauchst du Hilfe?

Wenn Sie Hilfe mit Plugwise Stealth M benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten