JUNG 2336 REG HZR HE Bedienungsanleitung

JUNG Smarth-Startseite 2336 REG HZR HE

Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für JUNG 2336 REG HZR HE (8 Seiten) in der Kategorie Smarth-Startseite. Dieser Bedienungsanleitung war für 11 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/8
Heating actuator 6-gang, Heating actuator 6-gang with controller
Heating actuator 6-gang
Art. No. : 2336REGHZHE
Heating actuator 6-gang with controller
Art. No. : 2336REGHZRHE
Operating instructions
1 Safety instructions
Electrical equipment may only be installed and fitted by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. Always disconnect before carrying out work on the devise or
load. In so doing, take all the circuit breakers into account, which support dangerous
voltages to the device and or load.
Danger of electric shock. Device is not suitable for disconnection from supply voltage.
The load is not electrically isolated from the mains even when the device is switched off.
These instructions are an integral part of the product, and must remain with the end
customer.
2 Device components
Figure 1: Front view
(1) Supply of electrothermal valve drives
(2) Button field for manual operation
(3) Programming button and LEDs
(4) KNX connection
(5) Connection for mains supply
(6) Status LEDs for outputs
(7) Connection of electrothermal actuators
3 Function
System information
This device is a product of the KNX system and complies with the KNX directives. Detailed
technical knowledge obtained in KNX training courses is a prerequisite to proper understanding.
1/8
82590313
j0082590313 20.12.2016
The function of this device depends upon the software. Detailed information on loadable
software and attainable functionality as well as the software itself can be obtained from the
manufacturer´s product database. Planning, installation and commissioning of the device are
carried out with the aid of KNX-certified software. The latest versions of product database and
the technical descriptions are available on our website.
Intended use
- Switching of electrothermal actuators for heaters or cooling ceilings
- Installation in distribution boxes on DIN rail according to EN 60715
Product characteristics
- Switching operation or PWM operation
- Actuators with characteristics opened or closed without power controllable
- Valve drives 230 V or 24 V controllable
- Outputs can be operated manually, construction site mode
- Feedback in manual mode and in bus mode
- Disabling of individual outputs manually or by bus
- Overload-protected, short circuit-protected, error message with LED
- Protection against jamming valves
- Forced position
- Various setpoints for forced position or emergency operation in case of bus failure for
summer or winter
- Cyclical monitoring of the input signals can be parameterized
- Feedback via bus, e.g. in case of mains failure, overload or sensor failure
- Bus connection with standard bus connecting terminal
iPWM operation: electrothermal actuators only have the positions "open" and "closed". In
PWM operation, switch-on and switch-off during the drive's cycle time achieves an almost
constant behaviour.
Only heating actuators with controllers:
- Integrated room temperature control with setpoint value specification
- Six independent controllers to control up to six independent rooms
- Controller function for heating and cooling operation
Overload protection
In order to protect the device and connected actuators, in case of overload the device
determines which output is involved and switches it off. Non-overloaded outputs continue to
work, which means that the rooms in question are still heated.
- In case of major overloads the actuator initially switches all off the outputs off.A1...A6
- In the case of more minor overloads the actuators switches output groups and/orA1...A3
A4...A6 off.
- The actuator determines the overloaded output in up to 4 test cycles.
- If in the event of only a minor overload it is not possible to unambiguously identify any
output as overloaded, then the actuator switches individual outputs off one after the other.
- The overload can be reported to the bus for each output.
LED display:
- Overload LED flashes slowly: Test cycle active.
- Overload LED flashes quickly: Test cycle completed.
2/8
82590313
j0082590313 20.12.2016
Heating actuator 6-gang, Heating actuator 6-gang with controller
4 Operation
Operating elements
Figure 2: Operating elements – Overview
(6) : Status LEDs for outputsA1...A6
Å‹ Å‹1-3, 4-6: Display "Overload/short-circuit" for output group
(8) Button – Manual operationc
(9) LED – On: Continuous manual mode activec
(10) button – Open valveOPEN
(11) LED – On: Valve opened, manual operationOPEN
(12) button – Close valveCLOSE
(13) LED – On: Valve closed, manual operationCLOSE
(14) button – Central operating function for all outputs: Open and close all valveALL OP / CL
alternatively
Status display and output behaviour
The Status LEDs (6) show whether the current flow is switched on or switched off at theA1...A6
appropriate output. The connected heating or cooling valves open and close according to their
characteristics.
Valve drive LED on LED off
Deenergised closed Heating/cooling
Valve opened
Off
Valve closed
Deenergised opened Off
Valve closed
Heating/cooling
Valve opened
- LED flashes slowly: Output in manual mode
- LED flashes quickly: Output disabled via continuous manual mode
Operating modes
- Bus operation: Operation via push-button sensors or other bus devices
- Short-term manual operation: Manual operation locally with button field, automatic return to
bus operation.
- Continuous manual mode: Exclusively manual operation on the device
iNo bus operation is possible in manual mode.
iNo manual mode is possible in case of bus failure.
iThe behaviour after bus failure and return can be set.
3/8
82590313
j0082590313 20.12.2016
Heating actuator 6-gang, Heating actuator 6-gang with controller


Produktspezifikationen

Marke: JUNG
Kategorie: Smarth-Startseite
Modell: 2336 REG HZR HE

Brauchst du Hilfe?

Wenn Sie Hilfe mit JUNG 2336 REG HZR HE benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Smarth-Startseite JUNG

Bedienungsanleitung Smarth-Startseite

Neueste Bedienungsanleitung für -Kategorien-