CyberPower RB1270X2E Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für CyberPower RB1270X2E (2 Seiten) in der Kategorie Unterbrechungsfreies Stromversorgungssystem. Dieser Bedienungsanleitung war für 35 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/2
Copyright © 2019 Cyber Power Systems, Inc. All rights reserved.
Battery Replacement
Instructions
CyberPower encourages environmentally sound
methods for disposal and recycling of its UPS and
batteries. Please dispose of and/or recycle your
UPS and batteries in accordance to the local
regulations of your state.
1 2 3 4 5
7 8 9 10 116
IMPORTANT SAFETY INSTRUCTIONS
Read and follow the important safety instructions before
servicing the batteries. Visit CyberPower ocial website
www.cyberpower.com or contact your dealer for more
information on battery replacement.
CAUTION! Use only the specified CyberPower replacement
battery, or battery pack.
CAUTION! Do not dispose of batteries in a fire. The batteries
may explode.
CAUTION! Do not open or mutilate batteries. Released material
is harmful to the skin and eyes. It may be toxic.
Take the following precautions before replacing the battery:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of batteries.
5. Determine if battery is inadvertently grounded. If
inadvertently grounded, remove source from ground.
CONTACT WITH ANY PART OF A GROUNDED BATTERY
CAN RESULT IN ELECTRICAL SHOCK. The likelihood of
such shock can be reduced if such grounds are removed
during installation and maintenance (applicable to
equipment and remote battery supplies not having a
grounded supply circuit).
Intelligent LCD Series, AVR Series
MODEL: CP600LCD, CP825LCD, CP800AVR, CP685AVR-G,
CP825AVR-G, CP685AVRLCD-G, CP825AVRLCD-G,
AVRG750U, AVRG900U, AVRG750LCD, AVRG900LCD
1 2 3
1. Place the UPS on its top and remove the retaining screw (figure 1).
2. Slide the battery compartment cover completely o of the unit
(figure 2).
3. Remove the battery from the compartment and disconnect the
battery wires from the battery. Install the replacement battery by
connecting the red wire to the positive (+) terminal and the black
wire to the negative (-) terminal of the battery. (figure 3)
4. Slide the battery compartment cover over the battery and tighten
the retaining screw.
5. Charge the unit for 4–8 hours to ensure the UPS performs
expected runtimes.
MODEL: CP850AVRLCD, CP1000AVRLCD
132
1. Place the UPS on its side and locate the battery compartment
cover on the bottom of the UPS. Remove the four (4) retaining
screws and pull the battery compartment cover o the UPS
(figure 1 & 2).
2. Remove the battery from the compartment and disconnect the
battery wires from the batteries. Install the replacement batteries
by connecting the red wire and black wire to the same color wires
from the battery pack. Put the battery pack into the compartment
(figure 3).
3. Slide the battery compartment cover over the battery and tighten
the retaining screw. Charge the unit for 4–8 hours to ensure the
UPS performs expected runtimes.
Standby Series
MODEL: RT650, RT650EI
1. Place the UPS on its side and remove the retaining screw.
2. Slide the battery compartment cover completely o of the unit.
3. Remove the battery from the compartment and disconnect the
battery wires from the battery.
4. Install the replacement battery by connecting the red wire and
black wire to the positive (+) and negative (-) terminal of the
battery. Put the battery back into the compartment.
5. Slide back the battery compartment cover and tighten the
retaining screw.
6. Charge the unit for 8 hours to ensure the UPS performs
expected runtimes.
1 2
3 4
AVR Series
MODEL: BRG850AVRLCD, BRG1000AVRLCD, CP850AVRLCDa,
CP1000AVRLCDa
1. Place the UPS on its side.
2. Remove the front panel retaining screws located on the bottom
of the UPS.
3. Slide the battery compartment cover (front panel) completely
o of the unit.
4. Disconnect the battery wires from the battery and remove the
battery from the compartment.
5. Install the replacement battery by connecting the red wire (+) and
black wire (-) to the same color connectors from the battery pack.
Put the battery back into the compartment.
6. Slide back the battery compartment cover and tighten the
retaining screws.
7. Charge the UPS for 8-16 hours to ensure the UPS performs
expected runtimes.
1 2
3 4
MODEL: BRG1350AVRLCD, BRG1500AVRLCD, CP1500AVRLCDa
1. Place the UPS on its side.
2. Remove the front panel retaining screws located on the bottom
of the UPS.
3. Slide the battery compartment cover (front panel) completely
o of the unit.
4. Disconnect the battery wires from the batteries and remove the
batteries from the compartment.
5. Install the replacement batteries by connecting the red wire (+) and
black wire (-) to the same color connectors from both the upper and
lower battery pack. Put the batteries back into the compartment.
Note: Make sure both batteries are new and replaced at the
same time to ensure maximum battery lifespan.
6. Slide back the battery compartment cover and tighten the
retaining screws.
7. Charge the UPS for 8-16 hours to ensure the UPS performs
expected runtimes.
1 2
3 4
MODEL: CP900AVR, CP1200AVR, CP1500AVRT, CP1285AVRLCD,
CP1350AVRLCD, CP1500AVRLCD
1. Place the UPS on its side to locate and remove the front panel
retaining screw from the bottom of the UPS.
2. Slide the cover (front panel) towards the bottom of the UPS.
3. Detach the cover from the unit.
4. Disconnect the cable located at the top of the cover and remove
the cover from the unit.
5. Disconnect the battery wires from the batteries.
6. Remove the batteries from the compartment.
7. Install the replacement batteries by connecting the red and black
wires to the same color wires from the battery pack. Put the
battery pack back into the compartment.
8. Replace the battery compartment cover and tighten the retaining
screw.
9. Charge the unit for 4-8 hours to ensure the UPS performs
expected runtimes.
1
3
5
2
4
6
MODEL: CP900AVRa, CP1200AVRa, CP1350AVRLCDa,
CP1500AVRTa, LX1100G, LX1325GU, LX1500GU,
CST135XLU, CST150XLU
(+) Red
(-) Black
(+) Red
(-) Black
1
3
5
2
4
6
7 8
1. Place the UPS on its side and remove the two retaining screws
located on the bottom of the UPS.
2. Slide the battery compartment cover completely o the unit.
3. Remove the battery which is located on the right side from the
compartment and disconnect the battery wires from the right
side of the battery.
4. Slide the remaining battery from the left side to the right side of
the compartment.
5. Remove the remaining battery from the compartment and
disconnect the battery wires from it.
6. Install the "left side" replacement battery by connecting the
yellow wire (+) to the red connector from the battery and the
black wire (-) to the black connector from the battery. Place the
battery into the left side of the compartment.
7. Install the "right side" replacement battery by connecting the red
wire (+) to the red connector from the battery and yellow wire
(-) to the black connector from the battery. Place the battery into
the right side of the compartment.
Note: Make sure both batteries are new and replaced at the same
time to ensure maximum battery lifespan.
8. Slide back the battery compartment cover and tighten the
retaining screws.
9. Charge the UPS for 8-16 hours to ensure the UPS performs
expected runtimes.
Smart APP Intelligent LCD Series
MODEL: OR500LCDRM1U, OR700LCDRM1U, OR1000LCDRM1U,
OR1500LCDRM1U
1 2
4 5
3
MODEL: OR1500LCDRM2U, OR2200LCDRM2U
OR1500LCDRTXL2U, OR2200LCDRTXL2U
OR1500LCDRT2U, OR2200LCDRT2U
4
1 2 3
5 6
1. Remove the right side front panel.
2. Remove the three retaining screws for the cable protection cover
and remove the cover.
3. Disconnect the black and red cable.
4. Remove the one retaining screw holding the battery pack in place.
5. Remove the battery pack.
6. Install the new battery pack. Assemble the screws, cover, cable
and front panel in the reverse order of the previous steps. Charge
the unit for 4-8 hours to ensure the UPS performs expected
runtimes.
1. Remove the right side front panel.
2. Remove the three retaining screws for the cable protection cover
and remove the cover.
3. Remove the two retaining screws from the cable connectors.
4. Disconnect the black and red cable.
5. Remove the four retaining screws holding the battery pack in
place.
6. Remove the battery pack.
7. Install the new battery pack. Assemble the screws, cover, cable
and front panel in the reverse order of the previous steps. Charge
the unit for 4-8 hours to ensure the UPS performs expected
runtimes.
MODEL: CPS1500AVR
WARNING
BATT
BATTERYUSING
!
ONPOWER
LOAD
AVR
WARNING
LOAD
BATT
ONPOWER
AVR
BATTERYUSING
!
WARNING
LOAD
BATT
ONPOWER
AVR
BATTERYUSING
!
WARNING
BATT
USING
!
LOAD
ON
POWER
AVR
BATTERY
BATTERY
AVR
POWER
ON
LOAD
!
USING
BATT
WARNING
1 2
4 5
3
1. Remove the right side front panel.
2. Remove the two retaining screws for the cable protection cover
and remove the cover.
3. Disconnect the black and red cable.
4. Remove the four retaining screws holding the battery pack in
place.
5. Remove the battery pack.
6. Install the new battery pack. Assemble the screws, cover, cable
and front panel in the reverse order of the previous steps.
Charge the unit for 4-8 hours to ensure the UPS performs
expected runtimes.
Smart APP SINEWAVE Series
MODEL: PR750LCD, PR750 JP
R
R
750VA
1 2
43
R
MODEL: PR1000LCD, PR1000 JP
1 2
43
1. Remove the front panel of the UPS.
2. Pull out both round knobs and remove the battery compartment
cover completely o of the unit.
3. Remove the batteries from the compartment.
4. Disconnect the battery wires from the batteries.
5. Install the replacement batteries by connecting the wire bundle
(composed of one red wire and one black wire) to the connector
from the battery pack. Put the batteries back into the compartment.
6. Re-install the battery compartment cover and push both round
knobs back into place. Put the front panel back on the UPS.
7. Connect to AC power and charge the new batteries for up to 16
hours to insure a full charge.
1. Remove the front panel of the UPS.
2. Remove two screws from the battery compartment cover and
slide the cover completely o of the unit.
3. Remove the batteries from the compartment. Disconnect the
battery wires from the batteries.
4. Install the replacement batteries by connecting the wire bundle
(composed of one red wire and one black wire) to the
connector from the battery pack.
5. Put the batteries back into the compartment. Re-install the
battery compartment cover and tighten the retaining screws.
Put the front panel back on the UPS.
6. Connect to AC power and charge the new batteries for up to 16
hours to insure a full charge.
MODEL: PR1500LCD, PR1500 JP
1 3 42
MODEL: PR2000SL JP, PR3000SL JP, PR2200LCDSL,
PR3000LCDSL, PR2200ELCDSL, PR3000ELCDSL,
M550L, M750L, M1100XL
1 2
43
1. Remove the front panel of the UPS.
2. Remove two screws from the battery compartment cover and
slide the cover completely o of the unit.
3. Remove the batteries from the compartment. Disconnect the
battery wires from the batteries.
4. Install the replacement batteries by connecting the wire bundle
(composed of one red wire and one black wire) to the
connector from the battery pack.
5. Put the batteries back into the compartment. Re-install the
battery compartment cover and tighten the retaining screws.
Put the front panel back on the UPS.
6. Connect to AC power and charge the new batteries for up to 16
hours to insure a full charge.
1. Remove the front panel of the UPS.
2. Remove two screws from the battery compartment cover and
slide the cover completely o of the unit.
3. Remove the batteries from the compartment.
4. Disconnect the battery wires from the batteries.
5. Install the replace batteries by connecting the red wire (+) and
black wire (-) to the same color connectors from the battery pack.
6. Put the batteries back into the compartment.
7. Re-install the battery compartment cover and tighten the
retaining screws.
8. Put the front panel back on the UPS.
9. Connect to AC power and charge the new batteries for up to 16
hours to insure a full charge.
MODEL: PR2200LCD, PR3000LCD
1 2 3 4
1. Remove the front panel of the UPS and two screws from the
battery compartment cover and slide the cover completely o
of the unit.
2. Pull out the battery pack on the outside from the compartment.
Disconnect the battery connector from the batteries.
3. Before removing the battery pack on the inside, unlock the
cable tie and pull out the battery wires. Disconnect the battery
connector from the batteries.
4. Install the replacement battery pack on the inside by
connecting the wire bundle connector (composed of one red
wire and one black wire) to the connector from the battery
pack. Lock the battery wires back with the cable tie.
5. Install the replacement batteries on the outside by connecting
the wire bundle connector (composed of one red wire and one
black wire) to the connector from the battery pack. Put the
battery pack on the outside back into the compartment.
6. Re-install the battery compartment cover and tighten the
retaining screws and put the front panel back on the UPS.
7. Connect to AC power and charge the new batteries for up to 16
hours to insure a full charge.
Note: The battery pack on the outside has a fuse, while the
battery pack on the inside does not.
MODEL: PR750LCDRM1U, PR1000LCDRM1U
1 2
4 5
3
1. Remove the right side front panel.
2. Remove the two retaining screws for the cable protection cover
and remove the cover.
3. Disconnect the black and red cable.
4. Remove the one retaining screw holding the battery pack in place.
5. Remove the battery pack.
6. Install the new battery pack. Assemble the screws, cover, cable
and front panel in the reverse sequence of the above steps.
Charge the unit for 4-8 hours to ensure the UPS performs
expected runtimes.
K01-0000611-03
13 14 15 1612
Cyber Power Systems, Inc.
www.cyberpower.com
For USA and Canada:
4241 12th Ave East, Suite 400
Shakopee, MN 55379
Toll-free: (877) 297-6937
For all other regions:
Please visit our website for local contact information.
17
18 19 20 21 22
MODEL: PR1000LCDRT2U, PR1000LCDRTXL2U,
PR1500LCDRT2U, PR2200LCDRT2U, PR3000SWRM2U
21
!
3
45
1. Remove the right side front panel.
2. Remove the two screws for the cable protection cover.
3. Disconnect the red and black cables.
4. Remove the four retaining screws holding the battery pack in place.
5. Remove the battery pack.
6. Install the new battery pack. Assemble the screws, cover, cable
and front panel in the reverse order of the previous steps. Charge
the unit for 4-8 hours to ensure the UPS performs expected
runtimes.
MODEL: OR750PFCLCD, OR1000PFCLCD, OR1500PFCLCD
1 3 42
1. Remove the front panel of the UPS.
2. Remove two screws from the battery compartment cover and
slide the cover completely o of the unit.
3. Remove the batteries from the compartment.
4. Disconnect the battery wires from the batteries.
5. Install the replacement batteries by connecting the red wire (+) and
black wire (-) to the same color connectors from the battery pack.
6. Put the batteries back into the compartment.
7. Re-install the battery compartment cover and tighten the
retaining screws.
8. Put the front panel back on the UPS.
9. Connect to AC power and charge the new batteries for up to 16
hours to insure a full charge.
MODEL: PR1000LCDRTXL2Ua, PR1500LCDRTXL2U,
PR2200LCDRTXL2U, PR3000LCDRT2U,
PR3000LCDRTXL2U
1 2
65
43
1. Remove the six retaining screws, and remove the front panel from
the UPS.
2. Remove the two retaining screws for the cable protection cover
and remove the cover.
3. Remove the two retaining screws from the cable connectors.
4. Disconnect the black and red cable.
5. Remove the three retaining screws holding the battery pack in place.
6. Remove the battery pack.
7. Install the new battery pack. Assemble the screws, cover, cable
and front panel in the reverse order of the previous steps. Charge
the unit for 4-8 hours to ensure the UPS performs expected
runtimes.
MODEL: PR5000LCDRTXL5U, PR6000LCDRTXL5U
1 2
4 5
3
1. Remove the front panel.
2. Remove the two retaining screws of the cable protection cover
and remove the cover.
3. Pull the plastic sticker out slowly to remove the battery module.
4. Put the new battery modules back into the compartment.
5. Tighten the screws and replace the cable protection cover and
the front panel.
MODEL: PR500LCDRT1U, PR750LCDRT1U, PR1000LCDRT1U,
PR1000LCDRT1U JP
1. Remove the two screws and remove the right panel.
2. Disconnect the battery connector.
3. Remove the two retaining screws and remove the battery cover.
Install new battery pack. Assemble the screws, cover, connector
and front panel in the reverse order of previous steps. Charge the
unit for at least 12 hours to fully charge the battery.
1 2 3
3
1
MODEL: MODEL: PR750RT2U, PR1000RT2U, PR1500RT2U,
PR2000RT2U, PR2200RT2U, PR3000RT2U,
PR750RTXL2U, PR1000RTXL2U, PR1500RTXL2U,
PR2000RTXL2U, PR2200RTXL2U, PR3000RTXL2U,
PR2200RTXL2UA, PR3000RTXL2UA,
PR2200RTXL2UHVA, PR3000RTXL2UHVA,
PR750ERT2U, PR1000ERT2U, PR1500ERT2U,
PR2000ERT2U, PR2200ERT2U, PR3000ERT2U,
PR750ERTXL2U, PR1000ERTXL2U, PR1500ERTXL2U,
PR2000ERTXL2U, PR2200ERTXL2U,
PR3000ERTXL2U, PR2200ERTXL2UA,
PR3000ERTXL2UA
1. Remove the faceplate and unscrew the thumbscrews on toolless
battery access door and then open the door.
Note: The thumbscrews are designed to be fixed on the door, do
not remove them from the metal cover.
2. Disconnect the battery and battery management module
connector and remove the battery pack.
3. Insert the new battery pack. Assemble the connectors,
thumbscrews and faceplate. Recharge the unit for at least 12
hours to ensure the UPS performs expected runtime.
Reminder: Battery Change Date is optional setup information for
users to record the installation date of battery pack. It can be adjusted
through LCD module in Advanced Setup Menu or through software.
2
PFC SINEWAVE Series MODEL: CP850PFCLCD, CP1000PFCLCD
3 4
1 2
1. Turn the UPS on its side. Remove the retaining screw located on
the bottom of the UPS.
2. Slide the battery compartment cover completely o of the unit.
3. Remove the batteries from the compartment.
4. Disconnect the battery wires from the batteries.
5. Install the replacement batteries by connecting the red wire (+)
and black wire (-) to the same color connectors from the battery
pack. Put the batteries back into the compartment.
6. Slide back the battery compartment cover and tighten the
retaining screw. Recharge the UPS for 8-16 hours to fully charge
the battery.
MODEL: CP1350PFCLCD
1
3 4
2
1. Turn the UPS on its side. Remove the front panel retaining screws
located on the bottom of the UPS.
2. Slide the battery compartment cover (front panel) completely o
of the unit.
3. Remove the batteries from the compartment.
4. Disconnect the battery wires from the batteries.
5. Install the replacement batteries by connecting the red wire (+)
and black wire (-) to the same color connectors from the battery
pack. Put the batteries back into the compartment.
6. Slide back the battery compartment cover and tighten the
retaining screws. Recharge the UPS for 8-16 hours to fully charge
the battery.
MODEL: CP1500PFCLCD
1
3 4
2
1. Turn the UPS on its side. Remove the front panel retaining screws
located on the bottom of the UPS.
2. Slide the battery compartment cover (front panel) completely o
of the unit.
3. Remove the batteries from the compartment.
4. Disconnect the battery wires from the batteries.
5. Install the replacement batteries by connecting the wire bundle
(composed of one red wire and one black wire) to the connector
from the battery pack. Put the batteries back into the
compartment.
6. Slide back the battery compartment cover and tighten the
retaining screws. Recharge the UPS for 8-16 hours to fully charge
the battery.
MODEL: OR1000PFCRT2U, OR1500PFCRT2U,
OR2200PFCRT2U
4
1 2 3
5 6
1. Remove the right side front panel.
2. Remove the three retaining screws for the cable protection cover
and remove the cover.
3. Remove the two retaining screws from the cable connectors.
4. Disconnect the black and red cable.
5. Remove the four retaining screws holding the battery pack in
place.
6. Remove the battery pack.
7. Install the new battery pack. Assemble the screws, cover, cable
and front panel in the reverse order of the previous steps. Charge
the unit for 4-8 hours to ensure the UPS performs expected
runtimes.
FTTx Series
MODEL: CSN27U12V-NA2, CSN27U12V-NA3,
CSN27U12V-NA3-G, CSN27U12V-XL
1 2 3
1. Remove the battery cover.
2. Disconnect battery cable connector to remove battery.
3. Replace with new battery and re-connect the battery
connector.
4. Make sure battery is fixed properly in the compartment and
close the battery cover.
MODEL: DTC36U12V-NA3-G
1 2 3
1. Slide o the battery cover at the back of the DTC36U12V unit.
2. Remove the battery from the enclosure.
3. Disconnect both battery cable connectors.
4. Install the new battery by connecting the red lead to the positive
terminal and the black lead to the negative terminal.
5. Slide the battery back into the normal operation.
6. Replace battery cover to resume normal operation.
MODEL: CS24C12V2-E
1 2 3
1. Remove the case screw.
2. Open the battery cover.
3. Loosen the battery strap.
4. Disconnect battery cable connector to remove battery.
5. Replace with new battery and re-connect the battery connector.
6. Tighten the battery strip
7. Close the battery cover and tighten the case screw.
Extended Battery Modules
MODEL: BP48V45ART2U, BP48V75ART2U
2 31
4 5
1. Remove the front panel on the right side.
2. Remove the front panel on the left side.
3. Disconnect the black and red wire from the battery.
4. Remove the cover and then remove the eight retaining screws.
5. Pull out the old battery packs and replace them with the new
ones. Recharge the unit for at least 12 hours to ensure the
Extended Battery Module performs expected runtime and then
connect the Extended Battery Module to your UPS.
Reminder: Check and modify the Extended Battery Module Quantity
setting on your UPS through the LCD module, PowerPanel® Business
software or RMCARD interface (if installed) to ensure the UPS reports
an accurate runtime.
1
MODEL: BP48VP2U01, BP48VP2U02, BP48VP2U03,
BP48VP2U04
1. Disconnect the Extended Battery Module from your UPS, remove
the faceplate and unscrew the screws on battery cover and then
remove the battery cover.
2. Disconnect the battery and battery management module connector.
3. Insert the new battery pack. Assemble the connectors, screws,
battery cover and faceplate. Recharge the unit for at least 12 hours
to ensure the Extended Battery Module performs expected runtime
and then connect the Extended Battery Module to your UPS.
Reminder: Check and modify the Extended Battery Module Quantity
setting on your UPS through the LCD module, PowerPanel® Business
software or RMCARD interface (if installed) to ensure the UPS reports
an accurate runtime.
2 3


Produktspezifikationen

Marke: CyberPower
Kategorie: Unterbrechungsfreies Stromversorgungssystem
Modell: RB1270X2E
Breite: 151 mm
Tiefe: 132 mm
Gewicht: 4380 g
Akku-/Batterietechnologie: Plombierte Bleisäure (VRLA)
Höhe: 105 mm
Betriebstemperatur: 0 - 40 °C
Relative Luftfeuchtigkeit in Betrieb: 0 - 90 %
Verpackungsbreite: 190.5 mm
Verpackungstiefe: 203.2 mm
Verpackungshöhe: 146.05 mm
Paketgewicht: 3630 g
Akku-/Batteriespannung: 12 V
Batteriekapazität: 7 Ah
Kompatibilität: M550L
Anzahl enthaltener Akkus/Batterien: 2 Stück(e)

Brauchst du Hilfe?

Wenn Sie Hilfe mit CyberPower RB1270X2E benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem CyberPower

Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem

Neueste Bedienungsanleitung für -Kategorien-