INTELLIGENT UPS SERIES
OR500LCDRM1U / OR700LCDRM1U
USER MANUAL
YOUR ULTIMATE ALLY IN POWER
Cyber Power Systems (USA), Inc.
4241 12th Avenue East, Suite 400 | Shakopee, MN 55379 | CyberPowerSystems.com
FEATURES
1. LCD Module Display
2. Power On Indicator
3. Power Switch
4. LCD Function Selected Switch
5. Battery and Surge Protected Outlets
6. Full-Time Surge Protection Outlets
7. SNMP / HTTP Network Slot
8. Communication Protection Ports RJ45
9. USB Port to PC
10. Dry Contact
11. Circuit Breaker
12. AC Input
13. Electrical Wiring Fault Indicator (Red)
Thank you for purchasing a CyberPower product. This UPS is designed to provide unsurpassed
power protection, operation, and performance during the lifetime of the product. Please take a
few minutes to register your product at: www.CyberPowerSystems.com/registration.
Registration certiïŹes your productâs warranty, conïŹrms your ownership in the event of a
product loss or theft, and entitles you to free technical support. Register your product now to
receive the beneïŹts of CyberPower ownership.
CAUTION! To prevent the risk of ïŹre or
electric shock, install in a temperature and
humidity controlled indoor area free of
conductive contaminants. (Please see
speciïŹcations for acceptable temperature
and humidity range).
CAUTION! To reduce the risk of electric shock,
do not remove the cover except to service the
battery. Turn oî and unplug the unit before
servicing the batteries. There are no user
serviceable parts inside except for the battery.
CAUTION! Hazardous live parts inside can be
energized by the battery even when the AC
input power is disconnected.
CAUTION! The UPS must be connected to an
AC power outlet with fuse or circuit breaker
protection. Do not plug into an outlet that is
not grounded. If you need to de-energize this
equipment, turn oî and unplug the unit.
CAUTION! To avoid electric shock, turn oî the
unit and unplug it from the AC power source
before installing a computer component.
CAUTION! To reduce the risk of ïŹre, connect
only to a circuit provided with 20 amperes
maximum branch circuit over current
protection in accordance with the National
Electric Code, ANSI/NFPA 70.
CAUTION! Not for use in a computer room
as deïŹned in the Standard for the Protection
of Electronic Computer/Data Processing
Equipment, ANSI/NFPA 75.
CAUTION! Do not dispose of batteries in a
ïŹre. The batteries may explode.
CAUTION! Do not open or mutilate batteries.
Released electrolyte is harmful to the skin and
eyes. It may be toxic.
DO NOT USE FOR MEDICAL
OR LIFE SUPPORT EQUIPMENT!
CyberPower Systems does not sell products
for life support or medical applications. DO
NOT use in any circumstance that would
aîect operation and safety of life support
equipment, any medical applications or
patient care.
DO NOT USE WITH OR NEAR AQUARIUMS!
To reduce the risk of ïŹre or electric shock,
do not use with or near an aquarium.
Condensation from the aquarium can cause
the unit to short out.
DO NOT USE THE UPS
ON ANY TRANSPORTATION!
To reduce the risk of ïŹre or electric shock, do
not use the unit on any transportation such
as airplanes or ships. The eîect of shock or
vibration caused during transit and the damp
environment can cause the unit to short out.
PRODUCT REGISTRATION
IMPORTANT SAFETY WARNINGS (SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all instructions carefully
during installation and operation of the unit. Read this manual thoroughly before attempting to
unpack, install, or operate your UPS.
INSTALLING YOUR UPS SYSTEM
UNPACKING
Inspect the UPS upon receipt.
The box should contain the following:
(a) UPS unit
(b) Userâs manual
(c) Rack mount brackets
(d) USB A+B type cable
PowerPanelÂź Personal software is available
on our website. Please visit www.
cyberpowersystems.com and go to the
Software Section for a free download.
OVERVIEW
The OR500LCDRM1U/OR700LCDRM1U
provides automatic voltage regulation
for inconsistent utility power. The
OR500LCDRM1U / OR700LCDRM1U features
1030 Joules of surge protection, and provides
battery backup during power outages.
The OR500LCDRM1U / OR700LCDRM1U
ensures consistent power to your computer
system and its included software will
automatically save your open ïŹles and
shutdown your computer system during a
utility power loss.
AUTOMATIC VOLTAGE REGULATOR
The OR500LCDRM1U/OR700LCDRM1U stabilizes
inconsistent utility power. The incoming utility
power may be damaging to important data
ïŹles, but with Automatic Voltage Regulation,
the computer will not experience damaging
voltage levels. An Automatic Voltage Regulator
automatically increases low voltage to a
consistent, computer
safe 110v/120v. The unitâs
powerful sealed lead-acid
batteries will provide
power only if the incoming
voltage drops below 90v
or increases above 140v.
DETERMINE THE POWER
REQUIREMENTS OF YOUR EQUIPMENT
1. Ensure that the equipment plugged into
the UPS does not exceed the UPS unitâs
rated capacity. If the rated capacities of the
unit are exceeded, an overload condition
may occur and cause the UPS unit to shut
down or the circuit breaker to trip.
2. There are many factors that can aîect
the amount of power that your electronic
equipment will require. For optimal system
performance keep the load below 80% of
the unitâs rated capacity.
HARDWARE INSTALLATION GUIDE
1. Your new UPS may be used immediately
upon receipt. However, after receiving a
new UPS, to ensure the batteryâs maximum
charge capacity, it is recommended that
you charge the battery for at least 8 hours.
Your UPS is equipped with an auto-charge
feature. When the UPS is plugged into an
AC outlet, the battery will automatically
charge whether the UPS is turned on or
turned oî.
2. If you will use the software, connect the
USB cable to the USB port on the UPS.
3. With the UPS unit turned oî and
unplugged, connect your computer,
monitor, and any other peripherals
requiring battery backup into the battery
power supplied outlets. Plug the other
peripheral equipment (e.g. printer, scanner,
speakers, etc.) into the full-time surge
protection outlets. DO NOT plug a laser
printer, paper shredder, copier, space
heater, vacuum cleaner, sump pump, or
other large electrical device into the
âBattery and Surge Protected Outletsâ.
The power demands of these devices will
overload and possibly damage the unit.
4. Plug the UPS into a 2-
pole, 3-wire grounded
receptacle (wall
outlet). Make sure the
wall branch outlet is
protected by a fuse or circuit breaker and
does not service equipment with large
electrical demands (e.g. air conditioner,
refrigerator, copier, etc.). The warranty
prohibits the use of extension cords, outlet
strips, and surge strips in conjunction with
the UPS unit.
5. Press the power switch to turn the unit on.
The Power On indicator light will illuminate
green and the unit will âbeepâ twice.
â continued
Produktspezifikationen
Marke: | CyberPower |
Kategorie: | Unterbrechungsfreies Stromversorgungssystem |
Modell: | OR700LCDRM1U |
Akustische Signale: | Ja |
Gewicht: | 8391 g |
Akkuladezeit: | 8 h |
Akku-/Batterietechnologie: | Plombierte BleisÀure (VRLA) |
Anzahl USB 2.0 AnschlĂŒsse: | 1 |
Betriebstemperatur: | 0 - 40 °C |
Relative Luftfeuchtigkeit in Betrieb: | 0 - 95 % |
Zertifizierung: | UL1778, cUL 107.1, FCC DOC Class B |
Anzahl Ethernet-LAN-AnschlĂŒsse (RJ-45): | 1 |
Reaktionszeit: | 4 ms |
Abmessungen (BxTxH): | 438 x 235 x 44.45 mm |
Ausgangsleistung: | 400 W |
Eingangsfrequenz: | 60 Hz |
Anzahl serielle AnschlĂŒsse: | 1 |
Abmessungen (B x T x H) (in Zoll): | 17.25 x 9.25 x 1.75 " |
Temperatur Betriebsumgebung: | 32 - 95 °F |
AusgangskapazitÀt: | 0.7 kVA |
Modem (RJ-11) Port: | 1 |
Typische Backup-Zeit bei halber Belastung: | 11 min |
Typische Backup-Zeit bei voller Belastung: | 3 min |
Ausgang AnschlĂŒsse: | NEMA 5-15R |
Eingang Verbindungstyp: | NEMA 5-15P |
Gewicht (imperial): | 18.5 Pfund |
Batteriepatrone Wechsel: | BB - HR9-6 |
Anstieg der Energiemenge: | 1030 J |
Brauchst du Hilfe?
Wenn Sie Hilfe mit CyberPower OR700LCDRM1U benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem CyberPower
22 Mai 2024
27 April 2024
14 April 2024
10 April 2024
7 April 2024
7 April 2024
2 April 2024
1 April 2024
20 MĂ€rz 2024
29 Februar 2024
Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem
- Unterbrechungsfreies Stromversorgungssystem Approx
- Unterbrechungsfreies Stromversorgungssystem HP
- Unterbrechungsfreies Stromversorgungssystem Voltcraft
- Unterbrechungsfreies Stromversorgungssystem Siemens
- Unterbrechungsfreies Stromversorgungssystem Schneider
- Unterbrechungsfreies Stromversorgungssystem Lenovo
- Unterbrechungsfreies Stromversorgungssystem Tripp Lite
- Unterbrechungsfreies Stromversorgungssystem Adj
- Unterbrechungsfreies Stromversorgungssystem JUNG
- Unterbrechungsfreies Stromversorgungssystem Block
- Unterbrechungsfreies Stromversorgungssystem Digitus
- Unterbrechungsfreies Stromversorgungssystem APC
- Unterbrechungsfreies Stromversorgungssystem Eaton
- Unterbrechungsfreies Stromversorgungssystem EnerGenie
- Unterbrechungsfreies Stromversorgungssystem Furman
- Unterbrechungsfreies Stromversorgungssystem Riello
- Unterbrechungsfreies Stromversorgungssystem Steren
- Unterbrechungsfreies Stromversorgungssystem Puls Dimension
- Unterbrechungsfreies Stromversorgungssystem Atlantis Land
- Unterbrechungsfreies Stromversorgungssystem Phoenix Contact
- Unterbrechungsfreies Stromversorgungssystem Middle Atlantic
- Unterbrechungsfreies Stromversorgungssystem Minuteman
- Unterbrechungsfreies Stromversorgungssystem Salicru
- Unterbrechungsfreies Stromversorgungssystem Maruson
- Unterbrechungsfreies Stromversorgungssystem Minute Man
- Unterbrechungsfreies Stromversorgungssystem DEXP
- Unterbrechungsfreies Stromversorgungssystem Bxterra
- Unterbrechungsfreies Stromversorgungssystem Altronix
- Unterbrechungsfreies Stromversorgungssystem FSP
- Unterbrechungsfreies Stromversorgungssystem PowerWalker
- Unterbrechungsfreies Stromversorgungssystem FSP/Fortron
Neueste Bedienungsanleitung fĂŒr -Kategorien-
22 Juni 2024
22 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024