CyberPower GX1500U Bedienungsanleitung
Lesen Sie kostenlos die đ deutsche Bedienungsanleitung fĂŒr CyberPower GX1500U (10 Seiten) in der Kategorie Unterbrechungsfreies Stromversorgungssystem. Dieser Bedienungsanleitung war fĂŒr 52 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet
Seite 1/10
YOUR ULTIMATE ALLY IN POWER
PFC SINEWAVE UPS SERIES
GX1500U
USER MANUAL
FEATURES
1. Power Switch 8. Battery and Surge Protected Outlets
2. Power On Indicator 9. Full-Time Surge Protection Outlets
3. LCD Module Display 10. Circuit Breaker
4. Down/Display Button 11. Serial / USB Ports to PC
5. Up/Mute Button 12. Wiring Fault Indicator (red)
6. Enter/Setup Button 13. Communication Protection Ports (RJ45)
7. USB Charge Ports 14. Widely-Spaced Outlets Designed
for AC Adapters
Cyber Power Systems (USA), Inc.
4241 12th Avenue East, Suite 400 | Shakopee, MN 55379 | CyberPowerSystems.com
PRODUCT REGISTRATION
Thank you for purchasing a CyberPower product. This UPS is designed to provide unsurpassed
power protection, operation, and performance during the lifetime of the product. Please take a
few minutes to register your product at: www.CyberPowerSystems.com/registration.
Registration certiïŹes your productâs warranty, conïŹrms your ownership in the event of a product
loss or theft, and entitles you to free technical support. Register your product now to receive the
beneïŹts of CyberPower ownership.
IMPORTANT SAFETY WARNINGS (SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all instructions carefully
during installation and operation of the unit. Read this manual thoroughly before attempting to
unpack, install, or operate your UPS.
CAUTION! To prevent the risk of ïŹre or
electric shock, install in a temperature and
humidity controlled indoor area free of
conductive contaminants. (Please see
speciïŹcations for acceptable temperature
and humidity range.)
CAUTION! To reduce the risk of electric shock,
do not remove the cover except to service the
battery. Turn oî and unplug the unit before
servicing the batteries. There are no user ser-
viceable parts inside except for the battery.
CAUTION! Hazardous live parts inside can be
energized by the battery even when the AC
input power is disconnected.
CAUTION! The UPS must be connected to an
AC power outlet with fuse or circuit breaker
protection. Do not plug into an outlet that is
not grounded. If you need to de-energize this
equipment, turn oî and unplug the unit.
CAUTION! To avoid electric shock, turn oî the
unit and unplug it from the AC power source
before connecting equipment to the unit.
CAUTION! To reduce the risk of ïŹre, connect
only to a circuit provided with 20 amperes
maximum branch circuit over current protec-
tion in accordance with the National Electric
Code, ANSI/NFPA 70.
CAUTION! Not for use in a computer room as
deïŹned in the Standard for the Protection of
Electronic Computer/Data Processing Equip-
ment, ANSI/NFPA 75.
CAUTION! Do not dispose of batteries in a ïŹre.
The batteries may explode.
CAUTION! Do not open or mutilate batteries.
Released electrolyte is harmful to the skin and
eyes. It may be toxic.
DO NOT USE FOR MEDICAL
OR LIFE SUPPORT EQUIPMENT!
CyberPower Systems does not sell products
for life support or medical applications. DO
NOT use in any circumstance that would aîect
operation and safety of life support equip-
ment, any medical applications or patient care.
DO NOT USE WITH OR NEAR AQUARIUMS!
To reduce the risk of ïŹre or electric shock, do
not use with or near an aquarium. Condensa-
tion from the aquarium can cause the unit to
short out.
DO NOT USE THE UPS
ON ANY TRANSPORTATION!
To reduce the risk of ïŹre or electric shock, do
not use the unit on any transportation such
as airplanes or ships. The eîect of shock or
vibration caused during transit and the damp
environment can cause the unit to short out.
INSTALLING YOUR UPS SYSTEM
UNPACKING
Inspect the UPS upon receipt.
The box should contain the following:
(a) UPS unit
(b) Userâs manual
(c) USB A+B Type cable
(d) Function Setup Guide
PowerPanelÂź software is available on our
website. Please visit www.cyberpowersystems.
com and go to the Software Section for a free
download.
SUPPORTS ACTIVE PFC POWER SUPPLIES
This CyberPower UPS system supports High
Eîciency power supplies with Active Power
Factor Correction (Active PFC). Active PFC is
used to improve the eîciency of power delivery.
The current US Energy StarÂź Program Require-
ments for Computers (version 7.1) mandates
Active PFC for all power supplies over 100
watts. Additionally, programs such as 80 PlusÂź
are often used to identify high eîciency power
supplies with Active PFC.
OVERVIEW
The GX1500U provides complete power protec-
tion from utility power that is not always consis-
tent and features 1445 Joules of surge protection.
All units provide long lasting battery backup
during power outages with maintenance free
batteries. The GX1500U ensures consistent power
to your computer system and includes software
that will automatically save your open ïŹles and
shutdown your computer system during a utility
power loss.
AUTOMATIC VOLTAGE REGULATOR
The GX1500U stabilizes inconsistent utility
power voltage to nominal levels that are safe
for equipment. Inconsistent incoming utility
power may be damaging to important data
ïŹles and hardware, but with Automatic Voltage
Regulation (AVR), damaging voltage levels are
corrected to safe levels.
AVR automatically increases low utility power
to a consistent and safe
110/120 volts. If incoming
utility voltage drops
below 90 volts, or exceeds
140 volts the units auto-
matically switch to battery
back-up power.
DETERMINE THE POWER REQUIREMENTS
OF YOUR EQUIPMENT
1. Ensure that the equipment plugged into
the UPS does not exceed the UPS unitâs
rated capacity. If the rated capacities of the
unit are exceeded, an overload condition
may occur and cause the UPS unit to shut
down or the circuit breaker to trip.
2. There are many factors that can aîect
the amount of power that your electronic
equipment will require. For optimal system
performance keep the load below 80% of
the unitâs rated capacity.
HARDWARE INSTALLATION GUIDE
1. Your new UPS may be used immediately
upon receipt. However, after receiving a
new UPS, to ensure the batteryâs maximum
charge capacity, it is recommended that
you charge the battery for at least 8 hours.
Your UPS is equipped with an auto-charge
feature. When the UPS is plugged into an
AC outlet, the battery will automatically
charge whether the UPS is turned on or
turned oî. Note: This UPS is designed with
a safety feature to keep the system from
being turned on during shipment. The ïŹrst
time you turn the UPS on, you will need to
have it connected to AC power or it will
not power up.
2. With the UPS unit turned oî and unplugged,
connect your computer, monitor, and any
other peripherals requiring battery backup
into the battery power supplied outlets.
Plug the other peripheral equipment (eg.
printer, scanner, speakers, etc.) into the
full time surge protection outlets. DO NOT
plug a laser printer, paper shredder, copier,
space heater, vacuum cleaner, sump pump
or other large electrical device into the
âBattery and Surge Protected Outletsâ.
The power demands of these devices will
overload and possibly damage the unit.
3. Plug the UPS into a 2-pole,
3- wire grounded receptacle
(wall outlet). Make sure the
wall branch outlet is protect-
ed by a fuse or circuit breaker and does
not service equipment with large electrical
demands (e.g. air conditioner, refrigerator,
copier, etc.). The warranty prohibits the use
of extension cords, outlet strips, and surge
strips in conjunction with the UPS unit.
-continued
Produktspezifikationen
Marke: | CyberPower |
Kategorie: | Unterbrechungsfreies Stromversorgungssystem |
Modell: | GX1500U |
Brauchst du Hilfe?
Wenn Sie Hilfe mit CyberPower GX1500U benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem CyberPower
22 Mai 2024
27 April 2024
14 April 2024
10 April 2024
7 April 2024
7 April 2024
2 April 2024
1 April 2024
20 MĂ€rz 2024
29 Februar 2024
Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem
- Unterbrechungsfreies Stromversorgungssystem Approx
- Unterbrechungsfreies Stromversorgungssystem HP
- Unterbrechungsfreies Stromversorgungssystem Voltcraft
- Unterbrechungsfreies Stromversorgungssystem Siemens
- Unterbrechungsfreies Stromversorgungssystem Schneider
- Unterbrechungsfreies Stromversorgungssystem Lenovo
- Unterbrechungsfreies Stromversorgungssystem Tripp Lite
- Unterbrechungsfreies Stromversorgungssystem Adj
- Unterbrechungsfreies Stromversorgungssystem JUNG
- Unterbrechungsfreies Stromversorgungssystem Block
- Unterbrechungsfreies Stromversorgungssystem Digitus
- Unterbrechungsfreies Stromversorgungssystem APC
- Unterbrechungsfreies Stromversorgungssystem Eaton
- Unterbrechungsfreies Stromversorgungssystem EnerGenie
- Unterbrechungsfreies Stromversorgungssystem Furman
- Unterbrechungsfreies Stromversorgungssystem Riello
- Unterbrechungsfreies Stromversorgungssystem Steren
- Unterbrechungsfreies Stromversorgungssystem Puls Dimension
- Unterbrechungsfreies Stromversorgungssystem Atlantis Land
- Unterbrechungsfreies Stromversorgungssystem Phoenix Contact
- Unterbrechungsfreies Stromversorgungssystem Middle Atlantic
- Unterbrechungsfreies Stromversorgungssystem Minuteman
- Unterbrechungsfreies Stromversorgungssystem Salicru
- Unterbrechungsfreies Stromversorgungssystem Maruson
- Unterbrechungsfreies Stromversorgungssystem Minute Man
- Unterbrechungsfreies Stromversorgungssystem DEXP
- Unterbrechungsfreies Stromversorgungssystem Bxterra
- Unterbrechungsfreies Stromversorgungssystem Altronix
- Unterbrechungsfreies Stromversorgungssystem FSP
- Unterbrechungsfreies Stromversorgungssystem PowerWalker
- Unterbrechungsfreies Stromversorgungssystem FSP/Fortron
Neueste Bedienungsanleitung fĂŒr -Kategorien-
22 Juni 2024
22 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024