User Manual for:
CPS320SL / CPS375SL / CPS500SL /
CPS575SL / CPS650SL
and PowerPanelâ„¢ Software
ADDITIONAL INSTALLATION TIPS CAN BE FOUND AT:
http://www.cyberpowersystems.com/faq_sl.htm
TABLE OF CONTENTS
Description……………………. ………1 LED Indicators……………………………..7
Determining Power Requirements…..1 Troubleshooting Guide……………………8
Hardware Installation Guide………….2 Specifications………………………………8
Software Installation Guide…………..3 Battery Replacement Instructions…….….9
Software User Manual………………..4 Warranty…………………………………...10
Thank you for purchasing a CyberPower Systems Product. To enjoy all the features and benefits of this Uninterruptible Power System
(UPS), please read and follow all installation and operation instructions completely. This UPS is designed to provide guaranteed power
protection for connected electronic equipment. The accompanying PowerPanelâ„¢ software saves data, closes open applications and
automatically shuts down your computer system in an intelligent and orderly manner.
IMPORTANT SAFETY INSTRUCTIONS
(SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all instructions carefully during installation and
operation of unit. Read this manual thoroughly before attempting to unpack, install, or operate.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of
conductive contaminants. (Please see specifications for acceptable temperature and humidity range).
CAUTION! To reduce the risk of electric shock, do not remove the cover except to service the battery. No user serviceable
parts inside except for battery.
CAUTION! Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected.
CAUTION! UPS must be connected to an AC power outlet with fuse or circuit breaker protection. Do not plug into an outlet
that is not grounded. If you need to de-energize this equipment, turn off and unplug the unit.
CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the battery or
installing a computer component.
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not sell products for life
support or medical applications. DO NOT use in any circumstance that would affect operation or safety of any life support
equipment or with any medical applications or patient care.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use with or near an
aquarium. Condensation from the aquarium can cause the unit to short out.
CPS320SL / CPS375SL / CPS500SL / CPS575SL / CPS650SL
Guaranteed Uninterruptible Power System
DESCRIPTION
INSPECTION
The box should contain the following:
(1) PowerPanelâ„¢ software (floppy disk); (1) serial interface cable (DB-9);
(1) telephone communication cable; (1) user manual; (1) warranty registration card;
(1) UPS unit.
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
1. Make sure that the total Volt-Amp (VA) requirements of your computer, monitor and peripherals does not exceed 1440 VA.
2. Insure that the equipment plugged into the three battery power-supplied outlets does not exceed the UPS unit’s rated capacity
(320VA/185W for CPS320SL, 375VA/210W for CPS375SL, 500VA/275W for CPS500SL, 575VA/320W for CPS575SL and
650VA/350W for CPS650SL). If rated unit capacities are exceeded, an overload condition may occur and cause the UPS unit to
shut down and the circuit breaker to trip.
3. If the power requirements of your equipment are listed in units other than Volt-Amps (VA), convert Watts (W) or Amps (A) into VA
by doing the calculations below. Note: The below equation only calculates the maximum amount of VA that the equipment can
use, not what is typically used by the equipment at any one time. Users should expect usage requirements to be approximately
60% of below value.
TO ESTIMATE POWER REQUIREMENTS:
Watts (W) x 1.82 = VA or Amps (A) x 120 = VA
Add the totals up for all pieces of equipment and multiply this total by .6 to calculate actual requirements.
There are many factors that can effect the amount of power that your computer system will require. The total load that you will be
placing on the battery-powered outlets should not exceed 80% of the unit’s capacity.
1
X Battery/Surge Outlets
Provides three battery powered/surge outlets for connected
equipment and insures temporary uninterrupted operation
of your equipment during a power failure.
Y Full-Time Surge Protection Outlets
Provides three always on surge suppression outlets.
Z Power Switch
Can be used as a mater on/off switch for equipment
connected to the battery power supplied outlets.
[ Electrical Wiring Fault Indicator
This LED indicator will illuminate to warn the user that a
wiring problem exists, such as bad ground, miss ground or
reversed wiring. If this is illuminated, user is advised to
disconnect all electrical equipment from the outlet and have
an electrician check to ensure the outlet is properly wired.
\ Power On Indicator
This LED is illuminated when the utility condition is normal
and the UPS outlets are providing power, free of surges
and spikes.
] Circuit Breake
r
Located on the side of the UPS, the circuit breaker serves to
provide overload and fault protection. Under normal operating
conditions, the circuit breaker is depressed.
^ Serial Port to PC
This port allows connection and communication from the DB-9
serial port on the computer to the UPS unit. The UPS
communicates its status to the PowerPanelâ„¢ software. This
interface is also compatible with the UPS service provided by
Windows NT and Windows 2000.
_ Communication Protection Ports
Communication protection ports will protect any standard modem,
fax or telephone line.
` Outlets Designed for AC Adapters
Allows six AC power adapter blocks to be plugged into the UPS
without blocking adjacent outlets.
Produktspezifikationen
Marke: | CyberPower |
Kategorie: | Unterbrechungsfreies Stromversorgungssystem |
Modell: | CPS320SL |
Produktfarbe: | Schwarz |
Akku-/Batterietechnologie: | Plombierte Bleisäure (VRLA) |
Energieschutzeigenschaften: | Ãœberlastschutz |
Betriebstemperatur: | 0 - 35 °C |
Relative Luftfeuchtigkeit in Betrieb: | 0 - 95 % |
Zertifizierung: | UL1778, cUL, FCC DOC Class B |
Kabellänge: | 1.8 m |
Reaktionszeit: | 4 ms |
LED-Anzeigen: | Ja |
Formfaktor: | Kompakt |
Ausgangsleistung: | 185 W |
Nachhaltigkeitszertifikate: | RoHS |
Eingangsfrequenz: | 60 Hz |
Anzahl der AC-Ausgänge: | 6 AC-Ausgänge |
Eingangs-Betriebsspannung (min): | - V |
Eingangs-Betriebsspannung (max): | - V |
Ausgangskapazität: | 0.32 kVA |
Ausgangs-Betriebsspannung (min): | - V |
Ausgangs-Betriebsspannung (max): | - V |
Modem (RJ-11) Port: | 3 |
AC-Steckertypen: | NEMA 5–15R |
Typische Backup-Zeit bei halber Belastung: | 0 min |
Stromstärke (maximal): | 36 A |
Nominale Eingang Spannung: | 120 V |
Ausgang Anschlüsse: | NEMA 5-15R |
Eingang Verbindungstyp: | NEMA 5-15P |
Anstieg der Energiemenge: | 450 J |
Brauchst du Hilfe?
Wenn Sie Hilfe mit CyberPower CPS320SL benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem CyberPower
22 Mai 2024
27 April 2024
14 April 2024
10 April 2024
7 April 2024
7 April 2024
2 April 2024
1 April 2024
20 März 2024
29 Februar 2024
Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem
- Unterbrechungsfreies Stromversorgungssystem Approx
- Unterbrechungsfreies Stromversorgungssystem HP
- Unterbrechungsfreies Stromversorgungssystem Voltcraft
- Unterbrechungsfreies Stromversorgungssystem Siemens
- Unterbrechungsfreies Stromversorgungssystem Schneider
- Unterbrechungsfreies Stromversorgungssystem Lenovo
- Unterbrechungsfreies Stromversorgungssystem Tripp Lite
- Unterbrechungsfreies Stromversorgungssystem Adj
- Unterbrechungsfreies Stromversorgungssystem JUNG
- Unterbrechungsfreies Stromversorgungssystem Block
- Unterbrechungsfreies Stromversorgungssystem Digitus
- Unterbrechungsfreies Stromversorgungssystem APC
- Unterbrechungsfreies Stromversorgungssystem Eaton
- Unterbrechungsfreies Stromversorgungssystem EnerGenie
- Unterbrechungsfreies Stromversorgungssystem Furman
- Unterbrechungsfreies Stromversorgungssystem Riello
- Unterbrechungsfreies Stromversorgungssystem Steren
- Unterbrechungsfreies Stromversorgungssystem Puls Dimension
- Unterbrechungsfreies Stromversorgungssystem Atlantis Land
- Unterbrechungsfreies Stromversorgungssystem Phoenix Contact
- Unterbrechungsfreies Stromversorgungssystem Middle Atlantic
- Unterbrechungsfreies Stromversorgungssystem Minuteman
- Unterbrechungsfreies Stromversorgungssystem Salicru
- Unterbrechungsfreies Stromversorgungssystem Maruson
- Unterbrechungsfreies Stromversorgungssystem Minute Man
- Unterbrechungsfreies Stromversorgungssystem DEXP
- Unterbrechungsfreies Stromversorgungssystem Bxterra
- Unterbrechungsfreies Stromversorgungssystem Altronix
- Unterbrechungsfreies Stromversorgungssystem FSP
- Unterbrechungsfreies Stromversorgungssystem PowerWalker
- Unterbrechungsfreies Stromversorgungssystem FSP/Fortron
Neueste Bedienungsanleitung für -Kategorien-
22 Juni 2024
22 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024