Universal panel meter DA9602R
lUniversal panel meter in 96 x 48 mm DIN format
l Extremly short mounting depth of 32 mm
l Universal input for process signals, thermocouples and RTD
l16 mm high red LED display
l2 alarm outputs as relay
l Protection IP65 from the front
l Programming via buttons or software (USB-Port)
The DA9602 is a quite versatile process indicator with totalizing
function. With a wide list of input types - thermocouples, thermo-
resistance, voltage and current the is capable of measuring
the majority of the variables and sensors encountered in industrial
processes.
It contains two alarms (six functions), sensor offset, configuration of
parameters protected by password, USB communication, indication in
degrees Celsius (°C) or Fahrenheit (°F), among others.
Display: LED display, 5-digits, red with 16 mm high digits.
Display range input signal: -1.999 to 30.000
Display range totalizer: 0 to 999.999.999 (alternating display)
Indicators: Ten red indicators for alarm status, communication,
totalizer function, Min- and MAX-value.
°C,°F ON, depending on temperature range
TX, RX, USB ON, during communication via USB
A1, A2 ON, when alarm is active
TOT ON, when displaying totalizer value
HIGH ON, when most significat digit of totalizer is displayed
LOW ON, when last
Buttons: 4 buttons for programming and setup of set points.
Input range: Setup of input signal via buttons.
Thermocouples: Type J, K,T, N, R, S, B, E; internal cold junction
RTD: Pt100 in 3-wire connection (alpha = 0,00385)
Linear inputs: 0 V to 5/10 V, 0/4 mA to 20 mA, 0 mV to 50 mV
Sensor type Measurement range
TC type J -110 ºC to 950 ºC (-166 ºF to 1742 ºF)
K -150 ºC to 1370 ºC (-238 ºF to 2498 ºF)
T -160 ºC to 400 ºC (-256 ºF to 752 ºF)
N -270 ºC to 1300 ºC (-454 ºF to 2372 ºF)
R -50 ºC to 1760 ºC (-58 ºF to 3200 ºF)
S -50 ºC to 1760 ºC (-58 ºF to 3200 ºF)
B 400 ºC to 1800 ºC (752 ºF to 3272 ºF)
E -90 ºC to 730 ºC (-130 ºF to 1346 ºF)
RTD -200 ºC to 850 ºC (-328 ºF to 1562 ºF)
Accuracy:
Thermocouples type J, K, T, E: 0,25 % of the span +/-1 °C
N, R, S, B: 0,25 % +/-3 °C
RTD: 0,2 % of the span
Linear analogue input: 0,2 % of the span
Resolution: Internal resolution with 65.535 steps (16 bits),
Display resolution 32.000 steps.
Measurement rate: 55 Hz with programmable digital filter.
DA9602
significat digit of totalizer is displayed
TC type
TC type
TC type
TC type
TC type
TC type
TC type
Thermocouples type of the span
Wachendorff Prozesstechnik GmbH & Co. KG
Industriestrasse 7
D-65366 Geisenheim
Tel.: +49 (0) 67 22 / 99 65 - 20
Fax: +49 (0) 67 22 / 99 65 - 78
www.wachendorff.de
Input impedance: Thermocouples, RTD, 0 to 50 mV: >10 MOhm;
0 to 5/10 V: >500 kOhm; 0/4 to 20 mA: 100 Ohm
Excitation: 24 VDC +/-15 % @ 50 mA
Relay outputs: 2x Relay SPST, 1,5 A at 240 VAC / 30 VDC.
Serial communication: Mini-USB (virtual COM port).
Supply: 100 to 240 VAC +/-10 %, 50/60Hz, 6 VA
Connections:
Protection: IP65 from the front (with rubber sealing), back side IP20.
Housing: Plastic case Polycarbonat (PC) L94-V2. Back panel ABS +
PC Ul94 V-0.
Diemensions: W 96 mm x H 48 mm x D 35 mm. Panel cut out: 93,0 x
45,5 mm. Mounting with plastic clamps.
Connection: Plug-in terminal blocks, 5 mm pitch.
Environmental conditions: Operating temeprature: 0 °C to +50 °C;
relative humidity 80 % rF @ 30 °C, for temperature above 30 ºC,
reduction by 3 % rF for ºC.
Package content: Panel meter, mounting material, rubber sealing,
manual.
Copyright by Wachendorff Prozesstechnik GmbH & Co. KG, Industriestraße 7, D-65366 Geisenheim, Tel.: 06722/9965-20, Fax: -78, Stand: 20.08.2012.
Alle Angaben ohne Gewähr, Irrtümer und Änderungen vorbehalten.
DA9602R
7
8
3
4
11
10
9
12
6
513
INPUT
V
mA
24 VDC
OUT
+
+
+
+
+
+
+
+
+
+
ALM1
RELAIS
ALM2
RELAIS
SUPPLY
100-240 VAC/VDC
50/60 Hz - 9 VA
wp-direkt.de
P/N: XXXXXXXX
S/N: XXXXXXXXXXXX
Order details
Typ Order-No.
Universal panel meter, 2 relay, 240 VAC DA9602R0
Accessories
USB programming cable. KABUSB20
Softwaredownload under:
http://www.wachendorff.de/wp/dpc_dow_epg_sof.html
Produktspezifikationen
Marke: | Wachendorff |
Kategorie: | Temperaturregler |
Modell: | DA9602R0 |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Wachendorff DA9602R0 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Temperaturregler Wachendorff
28 August 2024
Bedienungsanleitung Temperaturregler
- Temperaturregler Voltcraft
- Temperaturregler Techno Line
- Temperaturregler Technoline
- Temperaturregler Ventus
- Temperaturregler Cocraft
- Temperaturregler Honeywell
- Temperaturregler Kathrein
- Temperaturregler Inkbird
- Temperaturregler Dimplex
- Temperaturregler JUNG
- Temperaturregler Davis
- Temperaturregler Bulex
- Temperaturregler Fluke
- Temperaturregler Opticlimate
- Temperaturregler ACV
- Temperaturregler Ygnis
- Temperaturregler AstralPool
- Temperaturregler Emko
- Temperaturregler Jumo
- Temperaturregler Ziehl
Neueste Bedienungsanleitung für -Kategorien-
2 Oktober 2024
30 September 2024
28 September 2024
21 September 2024
20 September 2024
19 September 2024
5 September 2024
31 August 2024
31 August 2024
31 August 2024