Senseair eSENSE Slim Bedienungsanleitung

Senseair CO2-Sensor eSENSE Slim

Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Senseair eSENSE Slim (4 Seiten) in der Kategorie CO2-Sensor. Dieser Bedienungsanleitung war für 10 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/4
Document
IMA0274
Rev
5
Page
1 (4)
CO2 transmitter
eSENSEâ„¢ Slim
General
The IAQ-sensor product eSENSE Slim (sensor in industrial housing) is used to
measure indoor air carbon dioxide concentration. The 300 mm long cable connected
to the PCB makes it possible to place the sensor where the mounting is difficult.
The unit is designed for connecting to Direct Digital Control (DDC) with 0-5V signal
inputs.
Gas and Air Sensors
eSENSE Slim 0-5V
Installation Manual
Document
IMA0274
Rev
5
Page
2 (4)
The eSENSE Slim has a permanently connected cable to the PCB.
Figure 1. The eSENSE-Slim with the cable.
Figure 2. The eSENSE PCB. The brown cable is connected to OUT1 voltage output 0-5VDC
Shrinking tubing
Brown, 0-5V
Red, +24V
Black, GND
Brown, 0-5V
Red, +24V
Black, GND
300(11,8)
Document
IMA0274
Rev
5
Page
3 (4)
Electrical connections
The power supply has to be connected to +~ and . is considered as
system ground. The same ground reference has to be used for the eSENSE unit and
for the DDC/signal receiver.
PLEASE NOTE!
The same ground reference has to be used for the eSENSE
unit and for the control system!
Connection
Terminal
Function
Electrical Data
Remarks
+~
Power (+)
Power ground (-)
24 VAC/DC+ (+-20%),
2W
24 VAC/DC-
Red
Black
OUT 1
OUT 2
Analogue Output 1 (+)
Analogue Output 2 (+)
0-5 VDC
2-10 VDC
Brown
0-2000 ppm CO2
Not connected
Table I. Electrical terminal connections for eSENSE
Output Configurations
The sensors/controllers are supplied from the factory with a 0.-.5VDC linear output
for OUT1 (see Table I).
Self diagnostics
The system contains complete self-diagnostic procedures. A full system test is
executed automatically every time the power is turned on. In addition, constantly
during operation, the sensor probe is checked against failure.
PLEASE NOTE!
The sensor accuracy is defined at continuous operation (at least 3 weeks after
installation)


Produktspezifikationen

Marke: Senseair
Kategorie: CO2-Sensor
Modell: eSENSE Slim

Brauchst du Hilfe?

Wenn Sie Hilfe mit Senseair eSENSE Slim benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung CO2-Sensor Senseair

Bedienungsanleitung CO2-Sensor

Neueste Bedienungsanleitung für -Kategorien-