FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2014 V00029FB
Wyr-Grid Cabinet Mount Bracket
Part Number(s): WGCMB1070**, WGCMB1200**,
WGCMK1070**, & WGCMK1200**
Page 1 of 6
WGCMK1070** OR WGCMK1200** (as shown)
Step 1: Attach Strut to top of cabinet
thru existing M10 tapped cabinet top
holes with provided M10 Bolts and
Lockwashers.
WGCMB1070** OR WGCMB1200** (as shown)
Adjustable legs
Strut
Center Support
2x M10 Bolt 2x M10 Lockwasher
Strut
4x M5 Button Head
Torx Screws
Center Support
Note: The cabinet Mounting Brackets in the depicted
configurations are capable of supporting Wyr-Grid Path-
ways at their safe working load unless otherwise
noted.
M10 Bolt
Torque both screws to a maximum of 7 Lb-ft
(9.5 N-m) with 8mm Hex key
For N-Type cabinets
Remove the 2 screws
prior to installing strut
(See page 5 & 6 for Pathway installation.)
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS V00029FB
Page 2 of 6
Step 1: Attach adjustable legs to top
of cabinet using (2) M5 Torx Screws.
(each leg) (Do not tighten M5 Torx
screws)
Step 2: Attach Strut to top of adjustable
legs using (1) M10 Bolt & (1) M10 lock-
washer per side. Square the adjustable
legs and tighten the M10 Bolts & M5
Torx Screws (1.6 Lb-ft / 2.1 N-m).
Adjustable legs
M5 Torx screws
M10 Bolt
Torque both screws to a
maximum of 7 Lb-ft (9.5 N-m)
with 8mm Hex key.
Strut Beam
M10 Lockwasher
Torque Screws to a min.
of 4 Lb-ft (5.4 N-m) per
screw.
Standard Elevated Installation WGCMK1070** or WGCMK1200** (as shown)
Step 3: Adjust the height of the Strut to
the desired height.
Height Adjusts from 11.00” (279.4mm) to
16.75” (425.5mm)
(See page 5 & 6 for Pathway installation.)
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS V00029FB
Page 3 of 6
Step 1: Remove Front & Rear Fascia. Cut out removable
tab of front & rear fascias using wire cutters. Refer to the
Standard Elevated Installation Instructions for Mounting.
Top Integral Cable Manager Installation
Front Fascia
Rear Fascia
Removable tab
Step 2: Adjust the height of the
Strut to the desired height.
Height Adjusts from 11.00”
(279.4mm) to 16.75” (425.5mm)
Adjustment Screws
Torque to a min. of 4 Lb-ft
(5.4 N-m) per screw
Step 3: Re-install Front and Rear Fascias
(See page 5 & 6 for Pathway installation.)


Produktspezifikationen

Marke: Panduit
Kategorie: Kabel für PCs und Peripheriegeräte
Modell: WGCMK1070BL

Brauchst du Hilfe?

Wenn Sie Hilfe mit Panduit WGCMK1070BL benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Kabel für PCs und Peripheriegeräte Panduit

Bedienungsanleitung Kabel für PCs und Peripheriegeräte

Neueste Bedienungsanleitung für -Kategorien-