Seite 1/5
10/17 Page Model 8300.158 1 of 5
No. 2080167(15)
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359 Fax (775) 359-4712 -7424
E-mail: haws@hawsco.com website: www.hawsco.com
Model 8300.158 Combination
Shower Eye/Face Wash
INSTALLATION, OPERATION
&
MAINTENANCE INSTRUCTIONS
LIMITED WARRANTY
HAWS warrants that this specific product is guaranteed against defective material or poor
workmanship for a period of one year from date of shipment. HAWS liability under this
warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any goods,
or part thereof, which shall appear to the Company upon inspection to be of defective
material or not of first class workmanship, provided that claim is made in writing to Haws
within a reasonable period after receipt of the product. Where claims for defects are made,
the defective part or parts shall be delivered to the Company, prepaid, for inspection. HAWS
w
ill not be liable for the cost of repairs, alterations or replacements, or for any expense
connected therewith made by the owner or his agents, except upon written authority from
HAWS, Sparks, Nevada. HAWS will not be liable for any damages caused by defective
materials or poor workmanship, except for replacements, as provided above. Buyer agrees
that Haws has made no other warranties either expressed or implied in addition to those
above stated, except that of title with respect to any of the products or equipment sold
hereunder and that HAWS shall not be liable for general, special, or consequential
damages claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation
and maintenance instructions provided are adhered to. The units also must be used for the
purpose for which they were intended. This product is intended to supplement first-aid
treatment. Due to widely varying conditions, Haws cannot guarantee that the use of this
emergency
equipment will prevent serious injury or the aggravation of existing or prior
injuries.
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED
OR GIVEN BY HAWS.
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS
MODEL PLEASE CALL:
TECHNICAL SUPPORT: 1- - - 800 766 5612
FOR CUSTOMER SERVICE: 1- - - 888 640 4297
10/17 Model 8300.158 Page 2 of 5
LOCATION OF UNIT: The Model 8300.158 Emergency Shower should be installed in
close proximity to potential accident areas. It should be clearly identified, free from
obstructions and easy to access.
SUPPLY LINE: The minimum recommended line size is 1 1/4” IPS with 30- -90 psi (2 6
ATM) flowing pressure. Where sediment or mineral content is a problem, an inlet filter
is recommended.
PLUMBING CONNECTIONS: Inlet supply is female 1 1/4” IPS. Waste outlet is female
1 1/4” NPT.
MAINTENANCE: In freezing conditions, wipe eye/face wash head and dust cover dry
after each use to prevent unwanted ice build up.
NOTE: To minimize excessive spillage from air gap when testing, unit must be opened
and closed completely with one continuous motion. swift
INSTALLATION PROCEDURE
Refer to Installation Drawing for clarification. Check parts list to insure all required parts are
included. Use pipe joint sealant PST #565 (Loctite) on all connections.
STEP 1: Prepare the emergency shower foundation by using the floor flange assembly as
a template. Loc 16 UNC x 6” anchor bolts (not ate the three holes for the 3/8
supplied). They should extend 1” above the floor level.
STEP 2: Once the concrete foundation is ready (dry), assemble the floor flange assembly
to the anchor bolts 16 UNC Hex nuts and 3/8” ; then securely fasten with 3/8
washers (not supplied). Seal and tighten floor flange and tee making certain the
waste tee is facing the proper location (as shown in installation drawing) and the
foot control holes are facing side to side.
STEP 3: Assemble nipple (1 1/4” x 21 1/2”) to the floor flange assembly and tighten with a
pipe wrench.
STEP 4: Assemble the eye/face wash loop assembly to the 21 1/2” nipple from step three.
Connect the pipe wrench to the galvanized nipple between the two tees to avoid
damage.
STEP 5: Assemble in the following order:
Attach nipple (1 ” 1/4 x 24”) to loop assembly.
Attach coupling 1/4(1 ”) to nipple.
Attach nipple (1 1/4” x 24) to coupling.
Attach tee (1 1/4” ” x 1 1/4 x 1”) to nipple.
Attach nipple (1” x Close) to tee.
Attach ball valve/handle assembly to nipple. Note: Refer to installation
Drawing (Sheet 5 of O&M) for correct orientation of ball valve.
Attach nipple (1” x 19 ”) to ball valve/handle assembly.1/2
Attach elbow (1”) to nipple and attach showerhead to elbow.
STEP 6: Assemble the (1”) elbow onto the horizontal nipple (1” x 19 ½”), and attach the
showerhead onto the elbow.
10/17 Page Model 8300.158 3 of 5
STEP 7: Assemble the sign onto the unit. Use the strap, screws, washers and nuts
provided to mount the sign onto the upright. The sign should be positioned for
maximum visibility.
STEP 8: Air Gap Assembly: The 7” hose is connected to the SP158B valve, the 8” hose is
connected to the 3 way valve, and tube at bottom (8”) is connected to barb fitting
on elbow at the bottom of shower.
STEP 9: Before connecting the supply water line to the emergency shower, FLUSH THE
LINE THOROUGHLY.
TROUBLESHOOTING
PROBLEM
REPAIR CHECKLIST
1.
No flow.
1.
Check the main shut- off valve.
2.
Insufficient water flow
2.
Verify minimum 30 psi (2 ATM) flowing
supply line pressure.
3.
Insufficient water flow on eye/face
wash, however, shower is sufficient.
3
Probable clogging of flow control due to
inadequate line flushing. Unscrew
eye/face wash head and adapter.
Disassemble adap to gain access and ter
clean rubber flow control.
4.
Eye/face wash stream do not meet s
at desired eye level.
4.
Possible blocked flow control, see above
solution. Possible non leveled eye- /face
wash assembly.
5.
Insufficient water flow at the
showerhead wash , however, eye/face
is sufficient.
5.
Probable clogging of flow control inside
showerhead. Unscrew showerhead off
of elbow and clean rubber flow control.
6.
Water does not drain properly
6.
Check your drain system for debris.
Check the main waste line of your
building to see if it does handle the
capacity required for the entire drainage
system.
7.
Water leaks between joints or fittings
7.
Tighten loose connections. If leak
persists, the application of hot water will
sometimes reseat improperly applied
joint compound. After 30 minutes wait
and retest. A persistent leak will
necessitate reassembly and additional
sealant.
8.
Water flows from 3-way bleed valve
when in closed position.
8.
Remove nut and flag. Rotate stem 180
◦
and reassemble flag and nut.
9.
Continuous water flow from SP158B
when in closed position.
9.
Replace thermostat sub assembly.
For more information about Haws products, see our website: www.hawsco.com
© 20 Haws® Corporation ts Reserved17 – All Righ
HAWS® and other trademarks used in these materials are the exclusive property of Haws
Corporation.
Produktspezifikationen
Marke: | Haws |
Kategorie: | Duschsystem |
Modell: | 8300.158 |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Haws 8300.158 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Duschsystem Haws
24 August 2024
24 August 2024
24 August 2024
24 August 2024
24 August 2024
22 Februar 2024
8 Januar 2024
Bedienungsanleitung Duschsystem
- Duschsystem Panasonic
- Duschsystem IKEA
- Duschsystem Juno
- Duschsystem Fieldmann
- Duschsystem Miomare
- Duschsystem Delta
- Duschsystem Dimplex
- Duschsystem Gre
- Duschsystem Hansgrohe
- Duschsystem Schütte
- Duschsystem Hozelock
- Duschsystem Sani-Lav
- Duschsystem Fala
- Duschsystem Pulse ShowerSpas
- Duschsystem Omnires
- Duschsystem ECOstyle
- Duschsystem CurAqua
- Duschsystem Thermomate
- Duschsystem BMI
- Duschsystem Belanger
Neueste Bedienungsanleitung für -Kategorien-
8 September 2024
6 September 2024
6 September 2024
5 September 2024
5 September 2024
5 September 2024
5 September 2024
5 September 2024
5 September 2024
5 September 2024