Hager ECM310D Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Hager ECM310D (4 Seiten) in der Kategorie Messgeräte. Dieser Bedienungsanleitung war für 14 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/4
ECM310D
4
5
60
7
107
92
44
z i y
Technical data Technische data Dati tecnici
Data in compliance with EN 50470-1, EN 50470-3, IEC 62053-21 and
IEC62053-23
Gegevens conform EN 50470-1, EN 50470-3, IEC 62053-21 en
IEC62053-23
Dati conformi alle norme EN 50470-1, EN 50470-3, IEC 62053-21 e
IEC62053-23
General characteristics Algemene karakteristieken Caratteristiche generali
Housing DIN 43880 Behuizing DIN 43880 Involucro DIN 43880 DIN 6 0
Mounting EN 60715 Montage EN 60715 Montaggio EN 60715 DIN rail 35 mm
Depth Diepte ProfonditĂ  mm 60
Weight Gewicht Peso g700
Operating features Bedieningsfuncties FunzionalitĂ  operative
Connection to single-phase network - number of wires Verbinding naar eenfasig netwerk - aantal draden Connessione alla rete monofase - numero di îť°li -2 (L1)
to three-phase network - number of wires naar driefasen netwerk - aantal draden alla rete trifase - numero di îť°li -4
Storage of energy values and
conîť°guration
Internal îť±ash non volatile memory Opslag van energiewaarden en
conîť°g.
Intern îť±ash niet-vluchtig geheugen Memorizzazione dei valori di
energia e conîť°gurazione
Memoria interna non volatile -c
Tariff for active and reactive energy Tarief voor reële en reactieve energie Tariffa per energia attiva e reattiva T1 … T2 230V - T1 … T2 M-Bus-
Approval (according to EN 50470-1, EN 50470-3) Goedkeuring (volgens EN 50470-1, EN 50470-3) Omologazione (secondo EN 50470-1, EN 50470-3)
Reference Voltage (Un) (Un)phase / neutral Referentiespanning fase /nul Tensione di riferimento fase / neutro(Un) VAC 230
phase / phase fase / fase fase / fase VAC 400
Reference Current Referentie stroom Corrente di riferimento (Iref) (Iref) (Iref) A 5
Minimum Current Minimumstroom Corrente minima (Imin) (Imin) (Imin) A 0.25
Maximum Current Maximale stroom Corrente massima (Imax) (Imax) (Imax) A 125
Starting Current Startstroom Corrente di avviamento (Ist) (Ist) (Ist) A 0.020
Reference Frequency Referentie frequentie Frequenza di riferimento (fn) (fn) (fn) Hz 50
Number of phases / number of wires Aantal fasen / aantal draden Numero di fasi / numero di îť°li -3 / 4
Certiîť°ed Measures Gecertiîť°ceerde maatregelen Misure certiîť°cate kWh kWh kWh
Accuracy Nauwkeurigheid Precisione
- Active Energies (accord. to EN 50470-3) - Reële energie (conform EN 50470-3) - Energia attiva (secondo EN 50470-3) classe B / 1
- Active Powers (accord. to IEC 62053-21 and IEC 61557-12) - Reëel vermogen (conform IEC 62053-21 en IEC 61557-12) - Potenza attiva (secondo IEC 62053-21 e IEC 61557-12)
- Reactive Energies (accord. to IEC 62053-23) - Reactive Energieën (conform IEC 62053-23) - Energia reattiva (secondo IEC 62053-23) classe 2
- Reactive Power (accord. to IEC 62053-21) - Reactief vermogen (conform IEC 62053-21) - Energia reattiva (secondo IEC 62053-21)
Supply Voltage and Power Consumption Voedingsspanning en Energieverbruik Tensione di alimentazione e potenza assorbita
Operating Supply Voltage range Intervallo tensione di alimentazioneBedrfsspanningbereik V92 … 276 / 160 … 480
Maximum Power Consumption (Voltage circuit) Maximaal energieverbruik (Spanningscircuit) Potenza massima assorbita (circuito voltmetrico) VA / W ≤2 / 0.6
Maximum VA burden (Current circuit) @ Maximale VA last (stroom circuit) @ Massimo assorbimento VA (circuito amperometrico) @ Imax Imax Imax VA ≤0.7
Voltage Input Waveform Meetspanningsvorm Forma d'onda tensione di ingresso -AC
Voltage impedance Impedantie spanningsingang Impedenza circuito voltmetrico MΩ 1
Current impedance Impedantie stroomingang Impedenza circuito amperometrico mΩ ≤20
Overload capability Overbelastingscapaciteit CapacitĂ  di sovraccarico
Voltage continuous phase / neutral Spanning doorlopend fase /nul Tensione continuo fase / neutro VAC 276
temporary (1 s) phase / neutral fase /nul temporaneo (1 s) fase / neutrotdelk (1 s) VAC 300
continuous phase / phase doorlopend fase / fase continuo fase / fase VAC 480
temporary (1 s) phase / phase fase / fase temporaneo (1 s) fase / fasetdelk (1 s) VAC 800
Current continuous Stroom doorlopend Corrente continuo A125
temporary (10 ms) temporaneo (10 ms)tdelk (10 ms) A3750
Measuring Features Meetfuncties Funzioni di misura
Voltage range phase / neutral Spanningsbereik fase /nul Intervallo di tensione fase / neutro VAC 92 … 276
phase / phase fase / fase fase / fase VAC 160 … 480
Current range Stroombereik Intervallo di corrente A0.020 … 125
Frequency range Frequentiebereik Intervallo di frequenza Hz 45 … 65
Measured Quantities Gemeten hoeveelheden QuantitĂ  misurate -V, A, kWh, kvarh, PF, Hz, kW, kvar
Display features Display functies Caratteristiche del display
Display type LCD with backlight Display type LCD met achtergrondverlichting Tipo di
visualizzazione
LCD retroilluminato -7.2 +3.2
Active Energy Reële Energie Energia attiva7 digits + 2 decimal digits 7 cfers + 2 decimalen 7 cifre + 2 cifre decimali kWh 0.01 … 9999999.99
Reactive Energy Reactieve energie Energia reattiva7 digits + 2 decimal digits 7 cfers + 2 decimalen 7 cifre + 2 cifre decimali kvarh 0.01 … 9999999.99
Voltage Spanning Tensione3 digits + 1 decimal digit 3 cfers + 1 decimaal 3 cifre + 1 cifra decimale V92.0 … 276.0
Current Stroom Corrente2 digits + 2 decimal digits / 3+1 / 4+0 2 cfers + 2 decimalen / 3+1 / 4+0 2 cifre + 2 cifre decimali / 3+1 / 4+0 A0.00 … 125.00
Power factor Powerfactor Fattore di potenza1 digit + 3 decimal digits with sign + capac./induc. indic. 1 cfer + 3 decimalen + capaciteit./induc. indic. 1 cifra + 3 cifre decimali con segno + indic. capac. /
indutt. --1.000 … 1.000
Frequency Frequentie Frequenza2 digits + 2 decimal digits 2 cfers + 2 decimalen 2 cifre + 2 cifre decimali Hz 45.00 … 65.00
Active Power Reëel vermogen Potenza attiva2 digits + 2 decimal digits 2 cfers + 2 decimalen 2 cifre + 2 cifre decimali kW 0.00 … 34.50
Reactive Power Reactief vermogen Potenza reattiva2 digits + 2 decimal digits 2 cfers + 2 decimalen 2 cifre + 2 cifre decimali kvar 0.00 … 34.50
Apparent Power 2 digits + 2 decimal digits Schnbaar
vermogen
2 cfers + 2 decimalen 2 cifre + 2 cifre decimaliPotenza Apparente kVA 0.00 … 34.50
Running Tariff 1 digit Actueel tarief Tariffa in funzione 1 cifra1 cfer -T1 … T2 230V - T1 … T2 M-Bus
Display refresh period Toon verversingsperiode Frequenza di aggiornamento del display s1
Optical metrological LED Optische metrologische LED LED metrologico ottico
Front mounted red LED (meter constant) proportional to active imp/
exp Energy
Aan voorzde gemonteerde rode LED (meter
constant)
evenredig met actieve imp /
exp Energie
LED rosso frontale (costante del contatore) proporzionale all'energia imp /
exp. Attiva
p/kWh 1000
Safety Veiligheid Sicurezza
Overvoltage category Overspanningscategorie Categoria di sovratensione -3
Protective class Beschermingsklasse Classe di protezione classe II
AC voltage test (EN 50470-3, 7.2) AC spanningstest (EN 50470-3, 7.2) Test di tensione AC (EN 50470-3, 7.2) kV 4
Degree of pollution Vervuilingsgraad Grado di inquinamento -2
Operational voltage Nominale spanning Tensione di funzionamento V300
Impulse voltage test Impulsspanningstest Test di tensione ad impulso (Uimp) (Uimp) (Uimp) 1.2/50 ÎĽs-kV 6
Housing material îť±ame resistance Resistenza alla îť°amma del materiale dell'involucroUL 94 Behuizing materiaal vlamwerendheid UL 94 UL 94 classe V0
Safety-sealing between upper and lower housing part Veiligheidsafdichting tussen bovenste en onderste behuizing Sigillo di sicurezza tra la parte superiore e quella inferiore dell'involucro -c
IR Connectable Communication Modules IR-koppelbare communicatiemodules Moduli di comunicazione IR collegabili
For communication modules Voor communicatiemodules Per moduli di comunicazione -c
Embedded M-Bus communication GeĂŻntegreerde communicatie M-Bus Comunicazione incorporata M-Bus
Baud rate adjustable Baudrate Instelbaar Velocità Baud regolabile bps 300 … 9600
Address adjustable Adres Instelbaar Indirizzo regolabile -0 … 250
Isolation class SELV Isolatieklasse SELV Classe di isolamento SELV -c
Tariff Tarief Tariffa
Tariff 1 Tarief 1 Tariffa 1 -c
Tariff 2 Tarief 2 Tariffa 2 VAC 230 ±20%
Input impedance Ingangsimpedantie Impedenza di ingresso kΩ 224
Environmental conditions Milieuomstandigheden Condizioni ambientali
Storage temperature range Opslagtemperatuur Temperatura di stoccaggio °C -25 … +70
Operating temperature range Temperatura di funzionamentoBedrfstemperatuur °C -25 … +55
Mechanical environment Mechanische omgeving Ambiente meccanico -M1
Electromagnetic environment Elektromagnetische omgeving Ambiente elettromagnetico -E2
Installation indoor only Installatie alleen binnen Installazione solo all'interno -c
Altitude (max.) Hoogte (max.) Altitudine (max.) m≤2000
Humidity yearly average, without condensation Vochtigheid Umidità media annuale, senza condensajaarlks gemiddelde, zonder condensatie -≤75%
on 30 days per year, without condensation op 30 dagen per jaar, zonder condensatie su 30 giorni all'anno, senza condensa -≤95%
IP rating in built-in condition (front part) IP rating in ingebouwde conditie (voorkant) Grado di protezione IP in condizione di incasso (parte frontale) -IP51(*)
terminal block klemblok morsettiera -IP20
(*) For use in accordance with the MID Directive, the energy meter must be installed in a
distribution board/enclosure for modular products with a minimum protection rating IP30
The IP51 ratings apply to the meter parts exposed in front of (outside of) the cover of the
enclosure.
(*) Voor gebruik in overeenstemming met de MID-richtlîśťn moet de energiemeter
worden gemonteerd in een verdeelkast voor modulaire producten met een minimale
beschermingsklasse IP30. De IP51 is van toepassing op het gedeelte van de behuizing van
de energiemeter dat door de afdekplaat heen naar buiten steekt..
(*) Per l'utilizzo in conformitĂ  alla direttiva MID, il contatore di energia deve essere installato
in un quadro di distribuzione per apparecchi modulari con grado di protezione minimo
IP30. Il grado di protezione IP51 è relativo a parti del contatore esterne al quadro (frontale
dell'apparecchio).
z
i
y
Sealable terminal cover Dimension
Verzegelbare
schroefklemafdekkap Afmetingen
Coprimorsetto sigillabile Dimensione
Wiring diagram
Cable stripping length and terminal screw torque
Aansluitschema
Kabelstriplengte en aandraaimomenten van de
aansluitklemmen
Schema di collegamento
Lunghezza di sguainatura del cavo e coppia della
vite del morsetto
MID certified
MID gecertiîśźceerd
Certiîśźcato MID
MID safety sealing
MID-verzegeling
Sigillo di sicurezza MID
6LE005398Ad
1 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 6LE005398AdOCOM 136679
ECM310D
OK
OK
OK
OK
OK
OK
1s
1s
OK
OK
OK
OK
By powering. Software
version and checksum
Active Energy Imported
Tariff 1 with Partial
register
Active Energy Exported
Tariff 1 with Partial
register
Active Energy Imported
Tariff 2 with Partial
register
Active Energy Exported
Tariff 2 with Partial
register
Reactive Energy
Imported Tariff 1
Reactive Energy
Exported Tariff 1
Reactive Energy
Imported Tariff 2
Reactive Energy
Exported Tariff 2
After 2 seconds it goes
back to the Main Page
Active Power
(L1, L2, L3)
Reactive Power
(L1, L2, L3)
Apparent Power
(L1, L2, L3)
Voltage
(L1-N, L2-N, L3-N)
Current
(L1, L2, L3)
Neutral current
Power factor
L1
Power factor
L2
Power factor
L3
Frequency
Meter type
Main page is depending on current power direction
indication with the corresponding global and
partial energy register display.
Active energy exported
Reactive energy
imported
Reactive energy
exported
Tariff related Energies
Partial Register Reset
Measures reading
Conîśźguration
Serial number
Software version and
checksum
Display test
Primary Address:
0 ... 250
Baud Rate:
300-600-1200-2400
4800-9600
Secondary Address not
modiîśźable
Unidirectional
Bidirectional
Tariffs conîśźguration:
1T
2T input 230 V
2T input M-Bus
The cabling sequence (L1-L2-L3) is wrong. L1, L2 and L3
icons blink. Invert the voltage wires of 2 phases (phase 1 <>
phase 2 or phase 2 <> phase 3). Otherwise, by pressing the
"OK" button for at least 5 seconds, the message disappears
until the next restart.
Diagnostic message
Active energy imported
Three phase energy meter,
direct connection 125 A
with MID declaration of conformity
and M-Bus communication
MID certiîť°cation concerns active energy only.
User instructions
EU declaration of conformity:
http://hgr.io/r/ecm310d
Power factor
Convention according to IEC 62053-23
Safety instructions
This device must be installed only by a professional electrician îť°tter
according to local applicable installation standards. Do not plug in
or unplug this product when the power supplying is ON. Its use is
only permitted within the limits shown and stated in the installation
instructions. The device and the equipement connected can be destroyed
by loads exceeding the values stated.
Operating principle
This 4 quadrants M-Bus meter measures the active and reactive energy
used in an electrical installation.
This device can manage 2 tariffs by 230 VAC digital input or 2 controlled
via communication. Only the total active energy register can be used for
billing purposes according to measuring instrument directive (MID).
- Active Energy Class B (according to EN 50470)
- Active Power Class 1 (according to IEC 62053-21 and IEC 61557-12)
- Reactive Energy Class 2 (according to IEC 60253-23)
- Reactive Power Class 2 (according to IEC 62053-21).
This device has a backlighted LCD and 3 push-button keys to read
Energies, V, I, PF, F, P, Q and to conîť°gure some parameters. The design
and manufacture of this meter comply with Standard EN 50470-3
requirements.
Product presentation
LCD display:
Energy for all tariffs
Tariff
Reactive power
inductive/capacitive
Phase indicator
Main Energy Register, not resettable
Partial Energy Register, resettable
Units
Energy import (consumption )
Energy export (production )
Communication activity status
Symbols
One phase
Three phases
Protected by double insulation (Class II)
Backstop: Reversal preventing device
Commands
OK button: is used to conîť°rm a modiîť°cation of a
parameter (or of a digit of a numerical parameter) or to
answer to a question
SCROLL button: is used to scroll Menu pages or to
modify the whole value or a digit of a parameter
ESCAPE button: is used to escape to main menu from
anywhere or to skip back to the previous digit of the
value under modiîť°cation
Optical metrological LED
Note:
If no button is pushed for at least 20 seconds the display goes back to the
Main Page and the backlight is switched off again.
Operating M-Bus Communication
M-Bus MEDIA:
In a standard conîť°guration, a M-Bus connection can be used to link up
to 250* products with a PC or PLC, over a range of 1000 meters**.
* depending on the M-Bus master.
** depending on the number of products and the communication speed.
Recommendations:
The use of a JYSTY Nx2x0.8 mm (0.5 mm²) unshielded twisted pair is
recommended. If the range of 1000 m and/or the limit of 250 products
are exceeded, a repeater will need to be connected.
If the 250 limit is exceeded: only use the secondary address.
M-Bus protocol:
The M-Bus protocol operates using a master/slave structure. ECM310D
(slave) units are compatible with both primary and secondary addressing
modes. Primary addressing can be conîť°gured via the product interface.
Secondary addressing uses a îť°xed, unique address shown on the
product. M-Bus ECM310D units also have the «Wildcard addressing»
function which allows products to be searched for on the M-Bus
network. Option to broadcast to addresses 254 and 255. In addition,
M-Bus product units are OMS compatible (Open Metering Systems).
M-Bus table:
Download from: http://hgr.io/r/ecm310d
Error condition:
When partial energy blinks, reset partial energy (maximum partial energy
register). When the display shows the message or ERROR N02 ERROR
N03, the meter has got a malfunction and must be replaced.
z
QS
P
- +
+
-
II I
III IV
kvar
kW
kvar
kW
PF PF ≤0 ≥0
6LE005398Ad
2 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 6LE005398AdOCOM 136679
ECM310D
OK
OK
OK
OK
OK
OK
1s
1s
OK
OK
OK
OK
Via voeding.
Softwareversie en check
som
Reële energie
geĂŻmporteerd Tarief 1
met gedeeltelk register
Reële energie
geëxporteerd Tarief 1
met gedeeltelk register
Reële energie
geĂŻmporteerd Tarief 2
met gedeeltelk register
Reële energie
geëxporteerd Tarief 2
met gedeeltelk register
Reactieve energie
geĂŻmporteerd Tarief 1
Reactieve energie
geëxporteerd Tarief 1
Reactieve energie
geĂŻmporteerd Tarief 2
Reactieve energie
geëxporteerd Tarief 2
Na 2 seconden gaat
het terug naar de
hoofdpagina
Reëel vermogen
(L1, L2, L3)
Reactief vermogen
(L1, L2, L3)
Schnbaar
vermogen
(L1, L2, L3)
Spanning
(L1-N, L2-N, L3-N)
Stroom
(L1, L2, L3)
Nulgeleider stroom
Powerfactor
L1
Powerfactor
L2
Powerfactor
L3
Frequentie
Meter type
Hoofdpagina is afhankelk van de huidige
aanduiding van de stroomrichting met
het bbehorende algemeen en gedeeltelke
energieregisterscherm.
Reële energie
geëxporteerd
Reactieve energie
geĂŻmporteerd
Reactieve energie
geëxporteerd
Tariefgerelateerde
energieën
Gedeeltelk register
resetten
Meetwaarden
Conîśźguratie
Serienummer
Softwareversie en
check som
Displaytest
Hoofdadres:
0 ... 250
Baudrate:
300-600-1200-2400
4800-9600
Secundair adres kan
niet worden gewzigd
Unidirectionele
Bidirectionele
Tarieven conîśźguratie:
1T
2T ingang 230 V
2T ingang M-Bus
De bekabelingsvolgorde (L1-L2-L3) is verkeerd.
Pictogrammen L1, L2 en L3 knipperen. Keer de
spanningsdraden van 2 fasen om (fase 1 <> fase 2 of fase
2 <> fase 3). Anders verdwnt het bericht door gedurende
ten minste 5 seconden op de knop "OK" te drukken tot de
volgende herstart.
Diagnostisch bericht
Reële energie
geĂŻmporteerd
Driefase energiemeter,
directe stroommeting 125 A
met MID-verklaring van overeenstemming
en M-Bus-communicatie
MID certicering heeft alleen betrekking op werkelke energie.
Gebruikersinstructies
EU-conformiteitsverklaring:
http://hgr.io/r/ecm310d
Powerfactor
Conventie volgens IEC 62053-23
Veiligheidsinstructies
Dit apparaat mag alleen worden geĂŻnstalleerd door een professionele
installateur in overeenstemming met de geldende installatienormen.
Sluit dit product niet aan of koppel het niet los b ingeschakelde
spanning. Het gebruik ervan is alleen toegestaan binnen de aangegeven
grenzen en vermeld in de installatie-instructies. Het apparaat en het
aangesloten apparaat kunnen worden beschadigd door belastingen die
de vermelde waarden overschrden.
Werkingsprincipe
Deze 4 kwadranten M-Bus-meter meet de reële en reactieve energie die
wordt gebruikt in een elektrische installatie.
Dit apparaat kan 2 tarieven beheren via de binaire 230 VAC tarief ingang
en 2 tarieven via de digitale communicatie interface. Alleen het totale
actieve energieregister kan voor factureringsdoeleinden worden gebruikt
volgens de meetinstrumentrichtln (MID).
- Reële energieklasse B (volgens EN 50470)
- Reële vermogensklasse 1 (volgens IEC 62053-21 en IEC 61557-12)
- Reactieve energieklasse 2 (volgens IEC 60253-23)
- Reactieve vermogensklasse 2 (volgens IEC 62053-21).
Dit apparaat heeft een LCD-achtergrondverlichting en 3 druktoetsen om
de meetwaarden, V, I, PF, F, P, Q te lezen en om enkele parameters te
conîť°gureren. Het ontwerp en de fabricage van deze meter voldoen aan
de vereisten van norm EN 50470-3.
Productpresentatie
LCD scherm:
Energie voor alle
tarieven
Tarief
Reactief vermogen
inductief/capacitief
Fase-indicator
Hoofdenergieregister, niet opnieuw
instelbaar
Gedeeltelk energieregister,
opnieuw instelbaar
Eenheden
Energie-import (consumptie )
Energie-export (productie )
Status van communicatieactiviteit
Symbolen
Een fase
Drie fasen
Beschermd door dubbele isolatie (klasse II)
Backstop: apparaat om achteruitrden te voorkomen
Commando's OK-knop: wordt gebruikt om een wziging van een
parameter (of een cfer van een numerieke parameter) te
bevestigen of om een vraag te beantwoorden
SCROLL-knop: wordt gebruikt om door menupagina's
te bladeren of om de hele waarde of een cfer van een
parameter te wzigen
ESCAPE-knop: wordt gebruikt om naar het hoofdmenu
terug te gaan of om naar het vorige cfer van de
gewzigde waarde terug te gaan
Optische metrologische LED
Opmerking:
Als er ten minste 20 seconden lang op geen enkele knop wordt
gedrukt, keert het display terug naar de hoofdpagina en wordt de
achtergrondverlichting weer uitgeschakeld.
Operationele M-Bus-communicatie
M-Bus MEDIA:
In een standaardconîť°guratie kan een M-Bus-verbinding worden gebruikt
om tot 250 * producten te verbinden met een pc of PLC, over een bereik
van 1000 meter **.
* afhankelk van de M-Bus-master.
** afhankelk van het aantal producten en de communicatiesnelheid.
Aanbevelingen:
Het gebruik van een niet-afgeschermd getwist aderpaar JYSTY Nx2x0,8
mm (0,5 mm²) wordt aanbevolen. Als het bereik van 1000 m en / of
de limiet van 250 producten wordt overschreden, moet een repeater
worden aangesloten.
Als de limiet van 250 wordt overschreden: gebruik alleen het secundaire
adres.
M-Bus-protocol:
Het M-Bus-protocol werkt met een master / slave-structuur. ECM310D
(slave) -eenheden zn compatibel met zowel primaire als secundaire
adresseringsmodi. Primaire adressering kan via de productinterface
worden gecongureerd. B secundaire adressering wordt een vast uniek
adres gebruikt dat op het product wordt vermeld. M-Bus ECM310D-
enheden hebben ook de functie "Wildcard-adressering" waarmee
producten op het M-Bus-netwerk kunnen worden opgezocht. Optie om
uit te zenden naar adressen 254 en 255. Bovendien zn de M-Bus-
producteenheden OMScompatibel (open meetsystemen).
M-Bus-tabel:
Downloaden van: http://hgr.io/r/ecm310d
Foutconditie:
In de situatie dat het woord Partial op het diplay knippert, dan heeft de
“partial” teller de maximale waarde overschreden. In dit geval moet je
de “partial” teller resetten.
In de situatie dat de foutmeldingen of op het ERROR N02 ERROR N03
display verschnen dan is er een defect in de meter. In deze situatie
moet de meter worden vervangen.
i
QS
P
- +
+
-
II I
III IV
kvar
kW
kvar
kW
PF PF ≤0 ≥0
6LE005398Ad
3 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 6LE005398AdOCOM 136679