Eltako WSZ15D-65A Bedienungsanleitung

Eltako Messung WSZ15D-65A

Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Eltako WSZ15D-65A (2 Seiten) in der Kategorie Messung. Dieser Bedienungsanleitung war für 21 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/2
Maximum current 65A. Standby loss 0.4 watt only.
Modular device for DIN-EN 60715 TH35 rail mounting.
1 module = 18mm wide and 58 mm deep.
Accuracy class B (1%). With S0 interface as standard.
This single-phase energy meter measures active energy by means of the current
between input and output. The internal power consumption of 0.4 watt active
power is neither metered nor indicated.
1 phase conductor with a max. current up to 65A can be connected.
The start current is 4OmA.
If the anticipated load exceeds 50%, maintain an air gap of ½ pitch unit to
the devices mounted adjacently. If necessary, use spacer DS12.
Two N terminals for secure cross wiring of several counters.
Power consumption is shown by a bar flashing at a rate of 1000 times per kWh.
Error message
In case of a connection error, the background lighting of the display flashes.
When the display is running, it shows the total active energy and the display
bars are in the kWh position.
Press the button under the display to switch on the background lighting. Then
you can browse through the menu. The bar moves to the current display: the
cumulative power of the resettable memory RS (kWh), the current power P (kW),
the current voltage U (V) and the present current I (A) will be displayed
successively. In the end it will be browsed to the active energy display (kWh).
The program automatically returns back to normal display (kWh) 20 seconds
after pressing the button and the background lighting will be swiched off.
The memory RS is reset by pressing the button for longer than 3 seconds while
the memory is displayed. Then confirm the message 'reset' by pressing the
button again for 3 seconds.
The 7 segment LC display is also legible twice within a period of 2 weeks
without power supply. Press the button.
Typical connection
Single-phase energy meter WSZ15D-65A with display,
with MID approval
Only skilled electricians may install this electrical equipment
otherwise there is the risk of fire or electric shock!
Temperature at mounting location: -25°C up to +55°C.
Storage temperature: -25°C up to +70°C.
Relative humidity: annual average value <75%.
28 065 615 - 1
GB Menu guidance WSZ15D
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025
technical-support@eltako.de
eltako.com
23/2020 Subject to change without notice.
Must be kept for later use!
We recommend the housing for operating instructions GBA12.
Technical data
Rated voltage, extended range 230V, 50Hz, -20%/+15%
Reference current I
ref ((Limiting current Imax) 0.5 - 10(65)A
Internal consumption active power 0.4W
Display LC display 7 digits,
therefrom 1 or 2 digits after the decimal point
Accuracy class ±1% B
Inrush current according to accuracy class B 4OmA
Ambient temperature limits -25/+55°C
Interface potential free by opto-coupler,
max. 30V DC/2OmA and min. 5V DC.
S0: pulse output described in DIN EN 62053-31,
impedance 100 Ohm, pulse length 30ms, 2000 Imp./kWh
Protection degree lP50 for mounting in distribution cabines
with protection class IP51
Maximum conductor cross section
1) L terminals 16mm2
N and SO terminals 6mm2
Recommended torque
2)
L terminals 1,5 Nm (max. 2,0 Nm)
N and S0 terminals 0,8 Nm (max. 1,2 Nm)
EC type examination certificate 0120/SGS0272
The energy meter is used indoors.
Mechanical environmental conditions class M1
Electromagnetic environmental conditions class class E2
1) The carrying capacity of cables and wires is defined in DIN VDE 0298-4.
2) The torques for screw terminals are mentioned in DIN EN 60999-1.
To avoid damages at the energy meter, the recommended torque values for each terminal
must not be exceeded!