Eltako DSZ14WDRS-3x5A Bedienungsanleitung
Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Eltako DSZ14WDRS-3x5A (2 Seiten) in der Kategorie Messung. Dieser Bedienungsanleitung war für 7 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet
Seite 1/2
CT operated three-phase energy meter with settable CT ratio and MID.
Maximum current 3x5A. Standby loss 0,8W at L1 and only 0,5 W at L2
and L3 each.
Modulair device for DIN-EN 60715 TH35 rail mounting in distribution cabinets
with IP51 protection class.
4 modules = 70 mm wide and 58 mm deep.
Accuracy class B (1%). With RS485 interface.
This three-phase energy meter measures active energy by means of the
current between input and output.
The internal power consumption of 0,8W or 0,5 W active power per path is
neither metered nor indicated.
1, 2 or 3 phase conductors with max. currents up to 5A can be connected.
The inrush current is 10 mA.
The terminals  L1 and N must always be connected.
Connection via a FBA14 to the Eltako RS485 bus with a 2-wire shielded
bus cable (telephone cable). The meter reading and the momentary capacity
are transferred to the bus – e.g. for transfer to an external computer of the
GFVS 3.0 Software – and is also transferred to the wireless network via the
FAM14. Display also using FEA65D.
The 7 segment LC display is also legible twice within a period of 2 weeks
without power supply.
The power consumption is displayed with a LED flashing 10 times per kWh
next to the display.
On the right next to the displa y are the keys MODE and SELECT. Press them
to scroll through the menu. First the background lighting switches on. The
display then shows the total active energy, the active energy of the resettable
memory as well as the instantaneous values of consumption, voltage and
current per phase
The CT ratio can also be set. It is set to 5:5 at the factory and blocked with a
bridge over the terminals which are marked with 'JUMPER'. To adjust the CT
ratio to the installed transformer remove the bridge and reset the energy meter
according to the operation manual. Then block it again with the bridge.
Adjustable current transformer ratios: 5:5, 50:5, 100:5, 150:5, 200:5, 250:5,
300:5, 400:5, 500:5, 600:5, 750:5, 1000:5, 1250:5 and 1500:5.
Error message (false)
When the phase conductor is missing or the current direction is wrong 'false'
and the corresponding phase conductor are indicated on the display.
Important ! Before working on the current transformers disconnect the voltage
paths of the energy meters.
A device address for the DSZ14 has to be assigned from the FAM14, to hand
the telegrams of the DSZ14 over to the bus.
Assign device address for the DSZ14:
Normal display: Briefly press the SELECT button, the backlight is switched on.
If the SELECT button is pressed longer than 3 seconds, the device address
appears in the display. Now turn the rotary switch on the FAM14 to position
1 within 60 seconds, its lower LED flashes red. Once the address is assig-
ned by the FAM14, its lower LED lights green for 5 seconds and the normal
display appears again on the DSZ14.
Delete device address of the DSZ14:
Normal display: Briefly press the SELECT button, the backlight is switched
on. If the SELECT button is pressed longer than 3 seconds, the device
address appears in the display. Now hold the SELECT button for 5 seconds,
the device address is set to zero.
Transmit teach-in telegram:
Normal display: Briefly press the SELECT button, the backlight is switched
on. If the SELECT button is pressed longer than 3 seconds, the device
address appears in the display.
By briefly pressing the MODE button, a teach-in telegram and a data tele-
gram is sent. The FAM14 has to be operated in position 2 or 5, to sent the
telegrams of the DSZ14 into the Eltako Wireless Building.
CT operated three-phase energy meter DSZ14WDRS-3x5A
with display and MID approval
GB
28 305 712 - 4
Only skilled electricians may install this electrical equipment
otherwise there is the risk of fire or electric shock!
Temperature at mounting location: -25°C up to +55°C.
Storage temperature: -25°C up to +70°C.
Relative humidity: annual average value <75%.
Technical data
Rated voltage, extended range 3x230/400 V, 50 Hz,
-2O%/+15%
Reference current Iref (Limiting current Imax ) 3x0.05 - 5 (6) A
Internal consumption active power 0,8 W at L1 and
only 0,5 W at L2 and L3
Display LC display 7 digits,
therefrom 1 digit after the decimal point
Accuracy class ±1% B
Inrush current according to accuracy class B 1OmA
Operating temperature - 25/ +55°C
Interface RS485 bus Series 14
Terminal cover sealable Terminal cover claps
Protection degree lP50 for mounting in distribution cabines
with protection class IP51
Maximum conductor cross section
1) N and L terminals 16 mm
2,
RSA/RSB terminals and jumper terminals 6 mm
2
Recommended torque2) L- and N terminals 1,5 Nm (max. 2,0 Nm)
RSA/RSB terminals and jumper terminals 0,8 Nm (max. 1,2Nm)
EC type examination certificate 0120/ SGS0314
The energy meter is used indoors.
Mechanical environmental conditions class M1
Electromagnetic environmental conditions class class E2
1) The carrying capacity of cables and wires is defined in DIN VDE 0298-4.
2) The torques for screw terminals are mentioned in DIN EN 60999-1.
To avoid damages at the energy meter, the recommended torque values for each terminal
must not be exceeded!
g g
A data telegram containing meter reading, power and serial number is auto-
matically sent and cyclically transmitted every 10 minutes after switching on
the supply voltage.
If you change the meter reading by 0.1 kWh, the meter reading telegram is
sent.
Within 20 seconds after a change in power of at least 10%, a power telegram
is sent.
The DSZ14 can be read-out with the PC tool PCT14.
The serial number, meter reading and resettable meter reading will be
displayed.
Typical connection:
4-wire-connection 3x230/400 V
Connect the current transformer terminals on the secondary part to the
phase cunductors which are metered. These connections for the voltage
supply of the energy meters must be secured according to the local
installation regulations.
Menu guidance
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025
technical-support@eltako.de
eltako.com
23/2020 Subject to change without notice.
Must be kept for later use!
We recommend the housing for operating instructions GBA14.
Produktspezifikationen
Marke: | Eltako |
Kategorie: | Messung |
Modell: | DSZ14WDRS-3x5A |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Eltako DSZ14WDRS-3x5A benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Messung Eltako
3 Mai 2024
12 November 2023
20 September 2023
Bedienungsanleitung Messung
- Messung Hama
- Messung REV
- Messung Voltcraft
- Messung Bosch
- Messung Laserliner
- Messung Velleman
- Messung Powerfix
- Messung Alecto
- Messung Beurer
- Messung Bresser
- Messung König
- Messung TFA
- Messung Black And Decker
- Messung Trotec
- Messung DeWalt
- Messung Pioneer
- Messung Megasat
- Messung Smartwares
- Messung Garmin
- Messung GOCLEVER
- Messung Perel
- Messung Workzone
- Messung Microlife
- Messung Rossmax
- Messung Amprobe
- Messung Meec Tools
- Messung Metrix
- Messung IHealth
- Messung Ansmann
- Messung Westfalia
- Messung Livington
- Messung Silverline
- Messung Yato
- Messung Be Cool
- Messung Toolland
- Messung AS Schwabe
- Messung Hager
- Messung Kyoritsu
- Messung Eurolite
- Messung GW Instek
- Messung KERN
- Messung Milwaukee
- Messung Eizo
- Messung Testo
- Messung Victron Energy
- Messung Peak
- Messung Kübler
- Messung Carrier
- Messung Lund
- Messung SHX
- Messung Gima
- Messung Testboy
- Messung Danfoss
- Messung Fantini Cosmi
- Messung Multimetrix
- Messung Extech
- Messung BENNING
- Messung Fluke
- Messung FLIR
- Messung Vemer
- Messung Oregon Scientific
- Messung Ridgid
- Messung Stabila
- Messung Hikmicro
- Messung Entes
- Messung Gossen Metrawatt
- Messung Hameg
- Messung Joy-it
- Messung Megger
- Messung Muller
- Messung PCE Instruments
- Messung RK Technology
- Messung Sanwa
- Messung Sonel
- Messung Uni-T
- Messung VirtuFit
- Messung Wachendorff
- Messung TFA Dostmann
- Messung Vimar
- Messung Owon
- Messung PeakTech
- Messung Comark
- Messung Dahua Technology
- Messung YSI
- Messung Aluratek
- Messung SRS
- Messung H-Tronic
- Messung HT Instruments
- Messung Beha-Amprobe
- Messung Chauvin Arnoux
- Messung Werma
- Messung Eastron
- Messung Emko
- Messung Pancontrol
- Messung X-Rite
- Messung CESYS
- Messung Trumeter
- Messung Kemo
- Messung ORNO
- Messung Tempest
- Messung TDE Instruments
- Messung Zircon
- Messung Kreg
- Messung Apollo Ultrasonic
- Messung BJZ
- Messung Adwa
- Messung Greisinger
- Messung Qubino
- Messung Beckmann & Egle
- Messung Weidmüller
- Messung Janitza
- Messung CEM
- Messung Klein Tools
- Messung Daytronic
- Messung AREXX
- Messung Delta Ohm
- Messung Camille Bauer
- Messung Rigel Medical
- Messung UHoo
- Messung Seaward
- Messung AstroAI
- Messung P3 International
- Messung Seek Thermal
- Messung ClimeMET
- Messung Fixpoint
- Messung Condtrol
- Messung Cliff
- Messung Water-i.d.
- Messung Stahlwille
- Messung KS Tools
- Messung AkYtec
Neueste Bedienungsanleitung für -Kategorien-
4 August 2024
24 Juni 2024
24 Juni 2024
23 Juni 2024
23 Juni 2024
23 Juni 2024
23 Juni 2024
22 Juni 2024
21 Juni 2024
21 Juni 2024