Danfoss ICAD 600B Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Danfoss ICAD 600B (6 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 13 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/6
Installation guide
Actuator
Type ICAD 600B / 600B-TS / 1200B
027R9001
027R9001
© Danfoss | Climate solutions | 2023.09 AN461947453648en-000101 | 1
Info for UK customers only : Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB
Імпортер:ТОВ з іі “Данфосс ТОВ” 04080, Київ 80, п/с 168, Україна
Nm LB-feet
mm
ICAD 600B
ICAD 600B-TS
ICAD 1200B
ICM + ICAD 600B/ICAD 600B-TS
1 2
3 4
5a 5b ICM + ICAD 1200B
Before installing ICAD on ICM please read
t she eparate guide
“Mechanical in Itallation ICAD onof CM”
ICAD 600B
ICAD 600B-TS
ICAD 1200B
mm in.
H45 1.77
L325 1
ring
Groove where
clamps hold onto
ICM top
New O-ring
“Quick start guide
DANFOSS
Buttons and display description in page 4
Max. 3 Max. 2.2
© Danfoss | Climate solutions | 2023.09 2 | AN461947453648en-000101
ICAD 600B / ICAD 600B / ICAD 1200B
ICAD 600B/1200B - Analog I/O for modulating control
ICAD 600B/600B-TS/1200B - Digital I/O for ON/OFF valve operation
External
voltage
24 V DC (+)
(–)
K
1
K
2
K
1
K
2
II III
Supply
D F G E
DI1 DI2
Control
ICAD
Danfoss
M27H0163_1
Neutral zone/3 points control
6
7
8
9
Control
Power supply cable
cable
Terminal box
2
1
3
Data cabl e
2
1
3
Power
Control
Data
2
1
3
(White/blue)
(White/orange)
(Orange)
(Blue)
A (Black)
(Black)
(White)
(Brown)
(Blue)
B (Brown)
C (Red)
D (Orange)
E (Yellow)
F (Green)
G (Blue)
ICAD back Ref Color
A (Black)
B (Brown)
C (Red)
D )(Orange
E (Yellow)
F )(Green
G (Blue)
EKC 347
EKC 315A
EKC 361
Only possible with EKC 347
A (Black)
B (Brown)
C (Red)
D (Orange)
E (Yellow)
F (Green)
G (Blue) EKE 347
Only possible with EKE 347
Only possible with EKE 347
A (Black)
B (Brown)
C (Red)
D )(Orange
E (Yellow)
F )(Green
G (Blue)
DC
Auxiliary relays
24 V DC
A Black - Common alarm
B Brown - ICM fully open
C Red - ICM fully closed
D Orange - GND ground
E Yellow + 0/4 20 mA Input
F Green + 0/2 10 V input or digital input for on/o control
G Blue + 0/4 20 mA Output
I Black + Fail safe supply. Batter 19y / UPS* V DC
II White + Supply voltage
24 V DC 2A, or more, per ICAD recommended
ICAD PSU must be SELV**, >15 W
III Brown -
IIII Blue +UPS Signal of Health - optional depending on ID31:
‘UPS supply’ set to ‘Yes’
Digital
output
1 White/Blue
2 White/Orange
3 Blue
4 Orange
(-) / TX+ Data – (B) / Transmit Pair(+)
GND / RX+ Ground / Receiving Pair(+)
(+) / TX- Data + (A) / Transmit Pair(-)
GND / RX- Ground / Receiving Pair(-)
*Uninterruptable Power Supply
**
The ICAD is a Class III appliance
RS 485 / Ethernet
RS 485 / Ethernet
Description
© Danfoss | Climate solutions | 2023.09 AN461947453648en-000101 | 3
ENGLISH
Installation
Do not install ICAD before welding. This apply for
electrical as well as for mechanical installation. Please
observe that ICAD when connected to 24 V DC, will
send out acoustic noise at stand still. This has no
inuence on the function/ operation of the ICAD.
Use
ICAD 600B, ICAD 600B-TS and ICAD 1200B can
be used together with the following Danfoss
valves (g. 1, 5a and 5b).
ICAD 600B ICAD 600B-TS ICAD 1200B
ICM 20 ICMTS 20 ICM 40
ICM 25 ICMTS 50 ICM 50
ICM 32 ICMTS 80 ICM 65
ICM 100
ICM 125
ICM 150
CVE pilot valve
Electrical data
Supply voltage is galvanically isolated from in-/output.
ICAD is a Class III product.
PSUs connected to ICAD must be SELV<100 VA
For UL compliance: PSU must be Class 2 NEC
Supply voltage
24 V DC (Tolerances; see below table)
Load ICAD 600B, ICAD 600B-TS: 1.2 A
ICAD 1200B: 2.0 A
24 Volt DC ONLY
Please observe cable voltage drop.
Distance between the applied DC transformer
and the ICAD terminal box may cause a
voltage drop. Cross section of cables and size
of DC transformer must be calculated so that
the voltage at all time at the ICAD terminal
box*, both during standstill and during
operation of ICAD, is within this range:
Prefabricated
ICAD cable length
Code number
1.5 m
027H0426
3 m
027H0438
10 m
027H0427
15 m
027H0435
Voltage ICAD terminal
(600B/1200B) [V DC]
Min. 21 22 23 24
Max. 26.4
* Do not measure inside the ICAD itself (value can be
checked in ICAD B menu).
Fail safe supply
24 V DC (Tolerances; see table above)
Load ICAD 600B, ICAD 600B-TS: 1.2 A
ICAD 1200B: 2.0 A
Data communication
RS 485: It is important that the installation of the data
communication cable is done correctly. For further
guidance, see literature No. RC8AC902.
Remember termination at the bus termination.
Max lenght of cable: 1200 m with specic cable and
limited data rate. Follow RS485 standard.
Insulation from power supply input, metallic part
and interface output : 500 V DC: *For input/output
connections
Anolog Input - Current or Voltage
Current
Input range: 0/4 – 20 mA
Max input range: 0 – 24 mA
Input resistance: 120 + diode voltage 0.7 V DCW
Measurement error: <±1.5% of the full scale
Reverse polarity protection: yes
Overcurrent protection: yes
Voltage
Input range: 0/2 – 10 V DC
Max input range: 0 – 12 V DC
Measurement error: <±1.5% of the full scale
Reverse polarity protection: yes
Analog Output
Output range: 0/4 – 20mA
Load: <800 W
Output error: <±1.5% of the full scale
Recommended external resistor for Hot application:
Rext=800 W-load 1W power rate
Digital Input - Digital ON/OFF input by means of voltfree
contact (Signal/Telecom relays with gold-plated contacts
recommended) – Voltage input used
Rth rise(OFF): >10 kW
Rth fall(ON): < 45 W
Digital Output - 3 pcs. NPN transistor output
External supply: 7 – 24 V DC (same supply as for
ICAD can be used, but please note
that the galvanically isolated
system will then be spoiled).
On resistance: 55 W + diode voltage 0.7 V DC
Max 70 at 50 mAW
Max Output current: 50 mA
Reverse polarity protection: Yes
Overcurrent protection: No
Temperature range (ambient)
-30 °C/+50 °C (-22 °F/122 °F)
Enclosure
IP67 (~NEMA 6)
Electrical connection
Connection to ICAD is done via M12 connectors. ICAD has
two M12 male and one M12 female connectors build-in:
Power supply: 4 poled M12 male connector
Control signals: 8 poled M12 male connector
Data communication: 4 poled M12 female connector
Power Supply cable with 4 poled M12 female connector
4 x 0.34 mm
2 (4 x ~22 AWG) (g. 6)
I: Black (+) 19 – 24 V DC fail safe
supply (optional)
II: White (+) 24 V DC
III: Brown (–) 24 V DC
IIII: Blue (+) UPS signal of health
Control cable with 8 poled M12 female connector
7 x 0.25 mm
2 (7 x ~24 AWG) (g. 7)
A: Black (–) Digital output
Common Alarm
B: Brown (–) Digital output
ICM fully open
C: Red (–) Digital output
ICM fully closed
D: Orange (–) GND - Ground
E: Yellow (+) Analog input 0/4 – 20 mA)
F: Green (+) Analog input 0/2 – 10 V /
DI1 - Digital ON/OFF input.
G: Blue (+) Analog output 0/4 – 20 mA)
Data communication cable with 4 poled M12 male
connector:
RS 485 / RS 485 /
Ethernet Ethernet
1: White/Blue (-) / TX+ Data (B) / Transmit
Pair(+)
2: White/Orange GND / RX+ Ground / Receiving
Pair(+)
3: Blue (+) / TX- Data + (A) / Transmit
Pair(-)
4: Orange GND / RX- Ground / Receiving
Pair(-)
Electrical installation
General procedure for ICAD 600B/ICAD 600B-TS/1200B
installed on all ICM, ICMTS & CVE valves.
All necessary electrical connections to be made.
Fig. 6
Analog operation - 7 wired cable (A-G)
Modulation control. Valve to be controlled from
Danfoss electronics, type EKC/EKE (g. 7), or third
party electronics (like e.g. PLC).
Connect analog input signals. Currrent (mA) or
Voltage (V). See for conguration Parameter list
of analog input signals
Yellow (+) and Orange (GND) are used for current
(mA) input
or
Green (+) and Orange (GND) are used for Voltage
(V) input
Blue (+) and Orange (GND) are used for current
(mA) output (optional, not mandatory)
Fig. 6
Digital operation - 7 wired cable (A-G)
ON/OFF ICM solenoid valve operation. ICM valve to
be controlled by means of a digital voltfree contact.
Connect digital input signals (g. 8). See
Parameter list for conguration of digital input
signals
Green (+) and Orange (GND) are connected to a
voltfree contact
Digital output signals are optional, not mandatory.
Black (–) and Orange (GND) are connected to
auxiliary relay for Common Alarm
Brown (–) and Orange (GND) are connected to an
auxiliary relay indicating ICM fully open
Red (–) and Orange (GND) are connected to an
auxiliary relay indicating ICM fully closed
Supply voltage - 4 wired cable(I, II, III, IIII)
ICAD must be connected to a normal 24 V DC
supply. As an option, a fail safe supply is possible by
means of a battery or UPS (Uninterruptible Power
Supply). When voltage is applied as described
below, ICAD is ready to be congurated.
See . Parameter list
ICAD conguration can be done independently
whether the ICAD is installed on the valve or not.
See .Mechanical installation
Connect the White (+) and Brown (–) to 24 V DC
supply voltage (g. 6)
Fail safe supply as an option (not mandatory).
Connect the Black (+) and Brown (–) to a fail safe
supply.
Mechanical installation
General procedure for ICAD 600B/ICAD 600B-TS/1200B
installed on all valves (g. 3).
Check that the two socket screws are fully
unscrewed counter clockwise with a
3 mm Hexagon key
If valve is tted with PTFE ring and O-ring, remove
both and replace it with O-ring included in ICAD
(as instructed in g. 3)
Mount ICAD by slowly lowering it on top of the
valve.
The magnet coupling will drag the valve and ICAD
together and in position
Push ICAD in place
Fasten valve and ICAD with the two socket set
screws using a 3 mm Hexagon key
Special moisture seal is damaged if screws are
removed (g. 3).


Produktspezifikationen

Marke: Danfoss
Kategorie: Nicht kategorisiert
Modell: ICAD 600B

Brauchst du Hilfe?

Wenn Sie Hilfe mit Danfoss ICAD 600B benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert Danfoss

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung für -Kategorien-