Aritech ATS1290 Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Aritech ATS1290 (24 Seiten) in der Kategorie Sicherheit. Dieser Bedienungsanleitung war für 19 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/24
ATS1290
IADS DGP
EN
FR
NL
IT
DA
FI
DE
2006 GE Security B.V. 1055375
A
1
S
R
B
2
A
T
B
A
3
U
V
B
All rights reserved. 07/2006
www.gesecurity.net
EN
ATS129
0
IADS DGP available menus
1-DGP Status
0-Exit, Menu:
Operating
*=-,#=+,0=Exit
Dev:16 A:0 T:0
*=-,#=+,0=Exit
DGP1 I:17-32 O:17-32
*=-,#=+,0=Exit
V-bus: 12,7 Vdc
*=-,#=+,0=Exit
I-bus: 3 mA
*=-,#=+,0=Exit
2-Device Status
0-Exit,Menu:
17/0,PIR,T0
Input No:
17/0, Normal
*=-,#=+,0=Exit
3-Device Settings
0-Exit,Menu:
17/0,PIR,T0
Input No:
17/0,Loc1:0
*,Value:
Or
17/0,1:00000000
*,Bits:
4-Reset Settings
0-Exit,Menu:
17/0,PIR,T0
Input No:
17/0,Reset(Y/N)?
*=Yes,#=No
5-Learn Mode
0-Exit,Menu
Start Learn Mode?
*=Yes,#=No:
6-DGP Mode
0-Exit,Menu:
1 DGP address
*=Change,#=Enter
Extended Mode
*=Change,#=Enter
7-Factory Defaults
0-Exit,Menu:
Set Factory Defaults?
*=Yes,#=No:
EN
ATS129
0
IADS DG
P
Introduction
The ATS1290 is an interface between the ATS LAN bus and an IADS bus
(Intelligent Addressable Device System bus). It provides two-wire
bidirectional communications with up to 32 individually addressed IADS
modules. It is intended to be sitting on the LAN of any existing
configuration of ATS products to expand the system with addressable
modules. A maximum of 15 ATS1290 DGPs can be connected to the
LAN.
Mounting the unit
Mount the ATS1290 PCB in any existing ATS series enclosure that
supports the BB format.
Connections CON1 (see fig , and )
COMMS
+
-
12 VDC power supply. It is recommended that where the
distance between an ATS1290 and the nearest device is
more than 100 meters, a separate power supply be
used. Refer to the Remote DGP section. When using an
external power supply, use a fused power output (1 A
fast).
COMMS
D+
D -
Positive and negative data connection of the system
databus. Units can be up to 1.5 km from the ATS control
panel, depending on the cable used. See the ATS control
panel installation guide for details.
TAMP
Ti
Tc
The PCB tamper switch is connected in parallel to the
external tamper connection. Tamper switch requires
normally open contacts.
Depending on the type of housing used, you can use the PCB
tamper or connect an external tamper.
CON10 (see fig , )
Earth connection. Connect the shield of the ATS COMMS cable. At the
other end of the cable the shielding must be connected to one system
earth. See the ATS control panel installation guide. This is not
applicable for the possible shielding of the IADS -bus.
DGP dipswitch settings (see fig , & fig )
ADDR DIP switches 1 to 4 are used to identify the DGP number to
the ATS control panel. Select the required DGP number and
set the address DIP switch as indicated in figure .
LEDs (see fig , )
RX LED flashes to indicate polling data is being received on the
system databus from the ATS control panel. If the LED does
not flash, the control panel is not operational or the
databus is faulty (usually cabling).
TX LED flashes to indicate the DGP is replying to polling from
the ATS control panel. If the RX LED flashes but the TX LED
does not, it indicates that the DGP is not programmed to be
polled in the control panel or that it is addressed
incorrectly.
Connections CON2 (see fig , & fig )
PID Connection to all Addressable modules. Requires one + and
one – terminal to be connected. This will provide power
supply and data.
Modules provide for two bus terminals (see ) or only one terminal
(see & ). The bus loop does not need special termination.
IADS configurations
There are two main configurations:
Point identification solution based on I/O modules.
Intelligent addressable detectors solution.
Due to very complicated cable length calculation, it is not
recommended to combine intelligent addressable detectors
with I/O modules.
Point identification solution
In the point identification solution, only I/O modules (integrated and
standalone I/O) are recommended. In this configuration conventional
detectors with additional IADS modules (AD011/AD111) are used.
This configuration is based on a 4-wire system:
Data + power for I/O - 2 wires.
Power for detectors - 2 wires.
The ATS1290 can support 32 inputs in this configuration. Detectors
themselves need to be powered by a separate power supply.
This is an optimised solution for retrofit.
Intelligent addressable detectors solution
This configuration is based on a 2-wire system:
2
Data + power for all addressable detectors
The ATS1290 can support 16 detectors. For some modules, 2 inputs are
necessary, and therefore the expanded addressing mode could be
used to stay into the range of 32 addresses on the ATS1290.
Cable topology IADS – BUS (see fig )
A - DGP, B - control panel
In principle, the bus topology is free. Shown are several topologies (see
figure ):
1. Distributed (all IADS modules distributed across the line).
2. Star (all modules with own branches to a star point).
3. Lumped (all IADS modules at the end).
Recommended cable type
Use cables with as low resistance and capacitance as possible.
If a shielded cable is used for the IADS bus, this must not be connected
to either earth, PID- or PID+. If connected, it would result in additional
capacity and it will reduce the distance of the IADS bus.
The Table 1 below shows the maximum cable lengths in metres for
different cable types. The number of modules and module load are
taken into account. Check the module manuals for the "Unit Load". 1
Unit Load corresponds to 300 µA typical current.
The absolute minimum working voltage of the IADS DGP is
10.5 VDC with battery operation (measured on COMMS 12 VDC
power supply of the DGP).
Table 1. Maximum cable lengths (meters) with a minimum DGP voltage
of 10.5V
4 Wire IADS bus
External powered IADS modules
(4 wire IADS bus)
32 IADS modules:
AD011 (UL=1), AD111 (UL=2)
Cable type 2 x 0.5 mm 2 x 2 x 0.5 mm
# Wires 1 + 1 2 + 2
IADS bus 0.5 mm 1 mm
Distributed S 1 x 800 m 1 x 1600 m
Star T 16 x 200 m 16 x 400 m
U 1 x 80 m 1 x 880 m Lumped
V 16 x 40 m 16 x 40 m
2 Wire IADS bus
IADS modules powered out of the IADS bus
(2 wire IADS bus)
16 IADS modules:
EV435-AD (UL=8), EV435AM-AD (UL=16)
Cable type 2 x 0.5 mm 2 x 2 x 0.5 mm
# Wires 1 + 1 2 + 2
IADS bus 0.5 mm 1 mm
Distributed S 1 x 200 m 1 x 400 m
Star T 16 x 200 m 16 x 400 m
U 1 x 40 m 1 x 80 m Lumped
V 16 x 10 m 16 x 20 m
The distances S, T, U and V are referred to in Fig .
The power supply of conventional detectors is not taken into
account.
IADS module address setting and zone/output numbering
The address setting for the IADS module is directly linked to the zone
and output number the module will have in the control panel. IADS
module numbering starts from DIP switch setting 0.
Table 2. Address setting examples
1st DGP
address
Internal module
(e.g. EV435-AD) address
DIP switch setting on
internal module
17 0 00000000
18 1 10000000
19 2 01000000
4th DGP
address
Internal module
(e.g. EV435-AD) address
DIP switch setting on
internal module
65 0 00000000
66 1 10000000
67 2 01000000
15th DGP
address
Internal module
(e.g. EV435-AD) address
DIP switch setting on
internal module
241 0 00000000
242 1 10000000
243 2 01000000
Combine functionality to one output
For some applications, it is good practice to combine functionality to
one output to save outputs for other purposes. For example, enabling
and disabling walk test LEDs for the AD111.
Normally one output, of which can enable/disable the walk test LED, is
directly linked from the control panel to the IADS module. Each output
can control one walk test LED of one IADS module.
It is also possible to control all walk test LEDs of all AD111 by one
output. The only requirement is that the output needs to be within the
DGP range. Program the "ATS style output" for all relevant IADS
modules to one specific output. If more areas need to be controlled
separately, more outputs need to be reserved.
Learning IADS modules
IADS modules need to be recognised by the ATS1290 IADS DGP before
the device will be able to transfer status information or can be
configured by the IADS DGP.
To facilitate this, the ATS1290 IADS DGP has a jumper (JP2, fig , ).
Shorting this jumper with a screwdriver for a few seconds will start the
learn mode by which modules will become known. Any additional
settings regarding configuration of the module are available either by
jumper/DIP switch settings or via configuration menu, which is a part
of the ATS1290 menu. For more information on the available settings
of a module, see the manual of that module.
ATS1290 programming menu
The ATS1290 provides for additional settings available through the
onboard menu. To enter this menu:
Connect the ATS1290 to the ATS control panel.
In the ATS control panel Installation Programming menu:
o Activate polling to the ATS1290 (installer-menu 4).
o Enter installer-menu 28 – Remote Devices.
o Select 1-DGP.
o Select the ATS1290 DGP address.
You are now in the ATS1290 DGP menu.
Menu explanation
1. Status
Retrieve information regarding the status of the ATS1290.
Use the ENTER key to move through the different information screens.
1.1. Operational status
Indicates module status: DGP-Tamper, Module missing, multiple
modules, etc.
1.2. Device info
Shows in one line the number of modules known to the system, the
number of modules in alarm and the number of modules in tamper.
3


Produktspezifikationen

Marke: Aritech
Kategorie: Sicherheit
Modell: ATS1290

Brauchst du Hilfe?

Wenn Sie Hilfe mit Aritech ATS1290 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Sicherheit Aritech

Bedienungsanleitung Sicherheit

Neueste Bedienungsanleitung für -Kategorien-