APC Symmetra LX Bedienungsanleitung
Lesen Sie kostenlos die đ deutsche Bedienungsanleitung fĂźr APC Symmetra LX (2 Seiten) in der Kategorie Batterie. Dieser Bedienungsanleitung war fĂźr 37 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet
Seite 1/2
Symmetra LX
Start-Up Guide
Extended Run Cabinets
For use with Symmetra LX UPS models:
990-1873-001 04/2005
ÂŽ
200V, 4â8 kVA
208/240V, 4â8 kVA
220/230/240V, 4â8 kVA
200V, 4â16 kVA
208/240V, 4â16 kVA
220/230/240V, 4â16 kVA
READ FIRST
This guide is applicable for the Symmetra LX tower and rack-mount
extended run cabinet models. These units provide extended run time for the
Symmetra LX tower or rack-mount UPS models.
See and retain the product documentation shipped with your system for
other important installation, operation, and maintenance instructions.
Illustrations are representative. The Symmetra LX configuration, including
components and optional APC equipment, may be different from the models
shown in this guide.
Entire contents copyright 2005 by American Power Conversion Corporation.
All rights reserved. Reproduction in whole or in part without permission is
prohibited.
APC, the APC logo, InfraStruXure, PowerChute, Smart-UPS and Symmetra
are registered trademarks of American Power Conversion Corporation. All
other trademarks are the property of their respective owners.
9-Battery
Rack-mount
Extended Run
9-Battery
Tower
Extended Run
3-Battery
Rack-mount
Extended Run
Overview
1. Read Safety and General Information Instructions
2. Refer to the UPS Documentation
If installing the Symmetra LX and the Extended Run Cabinet(s),
install according to the instructions in the Symmetra LX Start-Up
Guide shipped with the UPS.
3. Install the Extended Run Cabinet(s)
Perform the physical installation for the extended run cabinet(s).
See the included Symmetra LX Physical Installation Guide.
4. Follow the proceeding Start-Up Instructions
See these instructions once the physical installation for the
Extended Run Cabinet(s) is complete. This section contains
information on how to connect, test, and start the unit.
Electrical
Hazard
⢠Read, understand and follow ALL safety
instructions contained in the Symmetra LX Safety
Instructions and General Information Guide.
⢠Failure to follow safety instructions and warnings
could result in equipment damage, serious injury,
or death.
Start-Up Instructions
1. Connect the first Extended Run Cabinet
1.1 Remove the screw and battery connector cover from the
back of the UPS.
1.2 Connect the power cable of the first extended run cabinet
to the UPS battery connector .
1.3 Set the dial of the extended run cabinet to â2â.
1.4 Connect the communications cable from the extended run
communications connector on the UPS to the connector on
the extended run cabinet .
Note
The illustrations shown in this section are applicable for the
tower and rack-mount extended run cabinets.
Note
If connecting to a UPS with integrated extended run, set the
dial of the first extended run cabinet to â3â instead of â2â.
2. Connect additional Extended Run Cabinets
Connect each additonal extended run cabinet to the previously installed
cabinet. The Symmetra LX supports a maximum of seven cabinets.
2.1 Remove the screw and UPS battery connector panel from the
previously installed cabinet.
2.2 Connect the power cable from the new cabinet into the battery
connector of the previous cabinet.
2.3 Set the dial of the new cabinet to a number that is one higher
than that of the previous cabinet .
2.4 Connect the communications cable from the communications
connector of the new cabinet to that of the previous cabinet .
3. Verify Connection
3.1 Check that the green status light on the rear of each cabinet will light.
3.2 Check that the front display shows the correct dial number.
3.3 Refer to the status menu on the UPS PowerView display (see the
Symmetra LX Operations Guide) to verify that the number of battery
modules matches the total number of battery modules installed in the
UPS and all extended run cabinets. Also, verify there are no bad
battery modules present.
Note
⢠To verify the connection, the UPS must be on. For further
information, see the Symmetra LX Start-Up Guide.
⢠Messages regarding battery quantity may be visible on the UPS
PowerView display.
Troubleshooting
It is assumed that the Symmetra LX is powered and functioning during these startup
procedures. If the problem persists, call technical support. Visit the the APC website at
http://www.apc.com/support for contact information.
Problem Possible Cause Solution
The green status LED (rear
of frame), and the front
display (front of frame) do
not light after the
communication cable is
installed.
There is no battery power
present at the frame.
Check that the battery cable
and battery modules are
properly installed.
The communication cable is
not installed
Check that the
communication cable is
properly installed.
The green status LED
lights, but the front display
does not show the frame
number.
The display cable is not
connected.
See the Extended Run
Cabinet Physical Installation
Guide for proper cable
connection instruction.
There is a potential hardware
failure.
Call technical support.
The front display
continuously flashes on
and off.
More than one frame is set
with the same frame number.
Check that frame numbers
are not duplicated on the
communication card(s).
An âXR frame failureâ is
reported. The front display
flashes an error code.
The âE_Oâ frame error code
may indicate that the battery
cable is not installed.
Check that the battery cable
is properly installed. If the
error code continues to flash,
call technical support.
The âE_7â frame error code
may indicate that the
communication cable is not
installed
Check that the
communication cable is
properly installed. If the error
code continues, call
technical support.
All other LED error codes
could indicate a potential
hardware failure.
Call technical support and
report the error code.
The front display
alternately flashes the
frame number and either
âLxâ , âCxâ, or âRxâ.
A failed battery module has
been detected in the location
displayed.
Replace the battery module.
To obtain a replacement
battery, see the APC
website.
The number of battery
modules reported is
inaccurate.
One or more battery module
disconnect switches are off
(opened).
Check that the disconnect
switch on all modules is
closed (counter-clockwise).
Battery modules are not
installed correctly.
Check that all battery
modules are properly
installed in the extended run
frame(s).
Produktspezifikationen
Marke: | APC |
Kategorie: | Batterie |
Modell: | Symmetra LX |
Akku-/Batteriekapazität: | 864000 mAh |
Gewicht: | 29100 g |
Produktfarbe: | Silber |
Akku-/Batterietechnologie: | Plombierte Bleisäure (VRLA) |
Betriebstemperatur: | 0 - 40 °C |
Relative Luftfeuchtigkeit in Betrieb: | 0 - 95 % |
Paketgewicht: | 32280 g |
Zertifizierung: | CSA, UL 1778 |
Warentarifnummer (HS): | 85079080 |
Temperaturbereich bei Lagerung: | -15 - 45 °C |
Luftfeuchtigkeit bei Lagerung: | 0 - 95 % |
Akku-/Batteriespannung: | 120 V |
Batteriekapazität: | 864 Ah |
Formfaktor: | 1U |
Abmessungen (BxTxH): | 210 x 546 x 140 mm |
Verpackungsabmessungen (BxTxH): | 286 x 750 x 385 mm |
Batterie Lebensdauer: | 3 Jahr(e) |
HĂśhe bei Betrieb: | 0 - 3000 m |
Brauchst du Hilfe?
Wenn Sie Hilfe mit APC Symmetra LX benĂśtigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Batterie APC
29 Mai 2024
12 Mai 2024
5 Februar 2024
19 September 2023
4 September 2023
14 August 2023
4 November 2022
31 Oktober 2022
13 Oktober 2022
Bedienungsanleitung Batterie
- Batterie Hama
- Batterie Kensington
- Batterie Nedis
- Batterie Sandberg
- Batterie Sony
- Batterie Targus
- Batterie Watson
- Batterie LG
- Batterie Bosch
- Batterie Parkside
- Batterie Canon
- Batterie Conrad
- Batterie Black And Decker
- Batterie FERM
- Batterie Ryobi
- Batterie Mestic
- Batterie Hilti
- Batterie Worx
- Batterie Sennheiser
- Batterie Shure
- Batterie Abus
- Batterie Kress
- Batterie Metabo
- Batterie Olympus
- Batterie Scheppach
- Batterie Varta
- Batterie Biltema
- Batterie TOA
- Batterie Tripp Lite
- Batterie Ansmann
- Batterie Husqvarna
- Batterie Scosche
- Batterie Honeywell
- Batterie Nikon
- Batterie Cramer
- Batterie Florabest
- Batterie Zipper
- Batterie Xtorm
- Batterie Vetus
- Batterie Thomann
- Batterie Safescan
- Batterie Milwaukee
- Batterie Toolcraft
- Batterie Huawei
- Batterie Victron Energy
- Batterie EGO
- Batterie Gardena
- Batterie HQ
- Batterie Cobra
- Batterie Ozito
- Batterie CyberPower
- Batterie Fluke
- Batterie EnerGenie
- Batterie Hähnel
- Batterie Energizer
- Batterie Variotek
- Batterie Sungrow
- Batterie Growatt
- Batterie SolarEdge
- Batterie Renata
- Batterie LSI
- Batterie Arris
- Batterie Duracell
- Batterie Crestron
- Batterie BlackVue
- Batterie For_Q
- Batterie Bolt
- Batterie Anton/Bauer
- Batterie HART
- Batterie FeinTech
- Batterie Levolta
- Batterie Enerdrive
Neueste Bedienungsanleitung fĂźr -Kategorien-
8 August 2024
8 August 2024
24 Juni 2024
14 Juni 2024
9 Juni 2024
9 Juni 2024
9 Juni 2024
9 Juni 2024
9 Juni 2024
9 Juni 2024