Altronix ReServ 3WP Bedienungsanleitung
Lesen Sie kostenlos die đź“– deutsche Bedienungsanleitung fĂĽr Altronix ReServ 3WP (8 Seiten) in der Kategorie UPS. Dieser Bedienungsanleitung war fĂĽr 8 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet
Seite 1/8
Outdoor Video Surveillance UPS
Installation Guide
Models Include:
ReServ1WP
- Twelve (12) true sine wave regulated 24VAC outputs
and Four (4) regulated 12VDC outputs.
- 4 amp total supply current @ 24VAC and 2 amp total supply current @ 12VDC.
- PTC protected power-limited outputs.
ReServ2WP
- Sixteen (16) true sine wave regulated 24VAC outputs.
- 4 amp total supply current.
- PTC protected power-limited outputs.
ReServ3WP
- Sixteen (16) regulated 12VDC outputs.
- 8 amp total supply current.
- PTC protected power-limited outputs.
Rev. 082610 More than just power.™
- 2 - ReServWP
Overview:
ReServWP Outdoor Video Surveillance UPS units are designed to provide power for 24VAC and/or 12VDC cameras during
normal or power outage conditions. True sine wave regulated AC outputs and/or regulated DC outputs.
ReServWP Series Outdoor Video Surveillance UPS Configuration Reference Chart:
Altronix
Model Number
Output/Supply
Current (Amp
Ambient
Temperature
Input Rating
PTC Protected
Power-Limited
Outputs
24VAC Outputs
12VDC Outputs
Agency Listings
UL Listings
and
File Numbers
ReServ1WP
24VAC @ 4 amp (100VA)
and 12VDC @ 2 amp -33Âş - 30Âş C 115VAC
60Hz,
3.5 amp
16 12 4
UL File # E329542
UL 60950-1
UL/CUL Listed
for
Information
Technology
Equipment.
UL 60950-22
Information Technology
Equipment - Safety -
Part 22: Equipment to
be Installed Outdoors
24VAC @ 3.5 amp (85VA)
and 12VDC @ 2 amp -33Âş - 42Âş C
ReServ2WP
24VAC @ 4 amp (100VA) -33Âş - 30Âş C 115VAC
60Hz,
3.5 amp
16 16 ----
24VAC @ 3.5 amp (85VA) -33Âş - 42Âş C
ReServ3WP 12VDC @ 8 amp -33Âş - 42Âş C
115VAC
60Hz,
3.5 amp
16 16----
Specifications:
Stand-by Specifications:
Stand-by Batteries
ReServ1WP - 4 amp (100VA) load at 24VAC and 2 amp load at 12VDC max.
ReServ2WP - 4 amp (100VA) max. load at 24VAC
ReServ3WP - 8 amp (100VA) max. load at 12VDC
Two (2) 12VDC/7AH 45 minutes
Two (2) 12VDC/12AH 90 minutes
Installation Instructions:
This installation should be made by qualified service personnel and should conform to all local codes and in accordance
with the National Electrical Code. This product contains no serviceable parts.
1. Remove back plate inside the enclosure by removing four (4) mounting screws.
2. Mark and drill desired knockouts on the enclosure to facilitate wiring .(Fig. 1, pg. 3)
It is required to use UL Listed outdoor rated conduit hubs with a minimum outdoor rating of 4X.Note:
3. Secure back plate inside the enclosure with four (4) mounting screws.
4. Mount unit in the desired location with the appropriate fasteners utilizing the holes provided on the
enclosure’s flanges . Secure enclosure to earth ground. (Pgs. 7 and 8)
This product needs to be secured to the building/pole before operation.Note:
5. Connect AC power mains to the terminals marked [L] and [N], .(Figs. 2-3, pg. 5-6)
Output:
• PTCprotectedpower-limitedoutputsarerated@1amp.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Automaticswitchovertostand-bybatterywhenACfails.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatterysupervision(form“C”contacts).
Visual and Audio Indicators:
• AC/DCpowerLEDindicators.
• IndividualpoweroutputLEDindicators.
• LowvoltageinputandShutdownLEDindicators.
• AudioACFailandBatteryFailindicator.
Additional Features:
• TruesinewaveregulatedACoutputs(ReServ1WPand
ReServ2WP). Regulated DC outputs (ReServ1WP and
ReServ3WP).
• Unitmaintainscamerasynchronization.
• Easeofinstallationsavestimeandeliminatescostlylabor.
Enclosure Dimensions :(H x W x D)
• NEMA4/IP66Ratedenclosure.
• Accommodatesuptotwo(2)12VDC/7AHbatteriesor
two (2) 12VDC/12AH batteries.
 17.375”x12”x6.5”(441.3mmx304.8mmx165.1mm)
ReServWP - 3 -
 Use18AWGorlargerforallpowerconnections(Battery,output)(Figs. 2-3, pg. 5-6).
 Use18AWGto22AWGforpower-limitedcircuits(ACFail/LowBatteryreporting)(Figs. 2-3, pg. 5-6).
A readily accessible disconnect device shall be incorporated in the building installation wiring.Note:
Keep power-limited wiring separate from non power-limited wiring (115VAC 60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
6. The LEDs on the power supply board will illuminate when AC power is present.
7. Measure output voltage before connecting cameras/devices to outputs. This helps avoiding potential damage.
8. ReServ3WP only - Adjust voltage for every two (2) outputs using the corresponding trimpot(s) on the board prior
to connecting devices.
9. Connecting cameras/devices:
- Connect 12VDC cameras/devices to the terminals marked [P 1-4, N 1-4] .ReServ1WP (Fig. 2, pg. 5)
Connect 24VAC cameras/devices to the terminals marked [5-16] .(Fig. 2, pg. 5)
- Connect 24VAC cameras/devices to the terminals marked [1-16] .ReServ2WP (Fig. 2, pg. 5)
- Connect 12VDC cameras/devices to the terminals marked [P 1-16, N 1-16] .ReServ3WP (Fig. 3, pg. 6)
10. Connect batteries to the terminals marked [--BAT+] . Use two (2) 12VDC batteries connected in (Figs. 2-3, pg. 5-6)
series for 24VDC operation (battery leads included).
Use batteries - Casil CA1270 (12V/7AH), Genesis NP7-12 (12V/7AH) or NP7-12 (12V/12AH), Ultratech UT1270
(12V/7AH) or Ultratech UT12120 (12V/12AH).
11. ConnectappropriatesignalingnotificationdevicestoACFAILandBATFAIL(Figs. 2-3, pg. 5-6)
supervisory relay outputs.
12. The power LEDs on the unit for Outputs 1-16 will illuminate when AC power is present . (Figs. 2-3, pg. 5-6)
If any of the power LEDs are not illuminated the cause may be due to the following:Note:
a. AC mains and battery fail.
b. One (1) or more power output PTCs are tripped due to a short circuit or overload condition.
c. Unit damaged/defective.
To reset the PTC:
1. Disconnect corresponding camera/device connected to terminals marked [1-16] .(Figs. 2-3, pg. 5-6)
2. Eliminate the trouble condition (short circuit or overload).
3. Allow 1 minute for PTC to cool off (reset).
4. Connect corresponding cameras/devices to terminals marked [1-16] .(Figs. 2-3, pg. 5-6)
5. Power LEDs will illuminate indicating power has been restored to outputs .(Figs. 2-3, pg. 5-6)
WARNING: This installation should be made by qualified service personnel and should conform to all
local codes and in accordance with the National Electrical Code.
Right PanelLeft Panel
Suggested Locations
for Wire Entries
Bottom Panel
Fig. 1
Produktspezifikationen
Marke: | Altronix |
Kategorie: | UPS |
Modell: | ReServ 3WP |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Altronix ReServ 3WP benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung UPS Altronix
30 August 2024
30 August 2024
30 August 2024
30 August 2024
Bedienungsanleitung UPS
- UPS Approx
- UPS Gembird
- UPS HP
- UPS Voltcraft
- UPS AEG
- UPS Siemens
- UPS IKEA
- UPS Dell
- UPS LC-Power
- UPS Tripp Lite
- UPS GYS
- UPS Adj
- UPS Block
- UPS Digitus
- UPS APC
- UPS CyberPower
- UPS Eaton
- UPS EnerGenie
- UPS Emerson
- UPS Furman
- UPS Riello
- UPS Puls Dimension
- UPS Avocent
- UPS Atlantis Land
- UPS Vanson
- UPS Phoenix Contact
- UPS Minuteman
- UPS V7
- UPS Equip
- UPS Salicru
- UPS SurgeX
- UPS Bxterra
- UPS FSP
- UPS Ditek
- UPS PowerWalker
- UPS FSP/Fortron
- UPS East
- UPS Liebert
- UPS Murr Elektronik
- UPS Online USV
Neueste Bedienungsanleitung fĂĽr -Kategorien-
13 Oktober 2024
13 Oktober 2024
13 Oktober 2024
13 Oktober 2024
13 Oktober 2024
13 Oktober 2024
13 Oktober 2024
13 Oktober 2024
11 Oktober 2024
9 Oktober 2024