75W Single Output Industrial DIN RAIL
NDR- 75 seri es
Features
Universal AC input / Full range
Protections: Short Circuit / Overload /
Over voltage/Over Temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
EN6100-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
Description
NDR-75 is one economical slim 75W DIN rail power supply series, adapt to be installed on TS-35/7.5
or TS-35/15 mounting rails. The body is designed 32mm in width, which allows space saving inside the
cabinets. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to
EN6100-3-2, the norm the European Union regulates for harmonic current.
NDR-75 is designed with metal housing that enhances the unit s power dissipation. With working
eciency up to 89%, the entire series can operate at the ambient temperature between - °C and 20
70°C under air convection. It is equipped with constant current mode for over-load protection, tting
various inductive or capacitiv applications. The complete protection functions and relevant certicates e
for industrial control apparatus (UL508, TUV EN60950-1, and etc.) make NDR-75 a very competitive
power supply solution for industrial applications.
Model Encoding
NDR - 75 12
Applications
Industrial control system
Semiconductor fabrication equipment
Factory automation
Electro-mechanical apparatus
Output voltage
Output wattage
Series name
75W Single Output Industrial DIN RAIL
NDR- 75 series
SPECIFICATION
MODEL
NDR- -75 48
DC VOLTAGE
48V
RATED CURRENT
1.6A
CURRENT RANGE
0 ~ 1.6A
RATED POWER
76.8W
RIPPLE & NOISE (max.) Note.2
150mVp-p
VOLTAGE ADJ. RANGE
48 ~ 55V
VOLTAGE TOLERANCE Note.3
±1.0%
LINE REGULATION
±0.5%
LOAD REGULATION
±1.0%
SETUP, RISE TIME
1200ms, 60ms/230VAC 2000ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)
60ms/230VAC 12ms/115VAC at full load
VOLTAGE RANGE Note.6
90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
89%
AC CURRENT (Typ.)
1.45A/115VAC 0.9A/230VAC
INRUSH CURRENT (Typ.)
20A/115VAC 35A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE
56 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE
Protection type : Shut down o/p voltage, re-power on to recover
WORKING TEMP.
-20 ~ +70 (Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY
-40 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
± 0.03%/ (0 ~ 50 )
VIBRATION
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508, TUV EN60950-1 approved
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
EMC EMISSION
Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3- -32,
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A
MTBF
486.2K hrs min. MIL-HDBK-217F (25 )
DIMENSION
32*125.2*102mm (W*H*D)
PACKING
0.51Kg; 28pcs/15.3Kg/1.22CUFT
1. All parameters NOT Specially mentioned are measured at 230VAC input, rated load and 25 °C of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI” testing of component power supplies.”
5. Length of set up time is measured at cold first start. Turning ON/OFF power supply may lead to increase to the set up time.
75W Single Output Industrial DIN RAIL
NDR - 75 s e r i e s
Block Diagram
fosc : 85KHz
I/P
EMI FILTER
POWER
RECTIFIERS
+V
&
SWITCHING
&
-V
RECTIFIERS
FILTER
O.C.P.
O.L.P.
FG
DETECTION
PWM
CIRCUIT
O.T.P.
CONTROL
O.V.P.
Derating Curve
230VAC
Others
100
80
115VAC
60
12V(115VAC only)
(%)
50
40
LOAD
20
-20 -100 10
20
30
40 45 50
60
70 (VERTICAL)
AMBIENT TEMPERATURE ( )
Static Characteristics
100
90
80
70
(%)
60
A
D
50
40
90
100
125
135
145
155
165
175
180
200
230
264
INPUT VOLTAGE (V) 60Hz
File Name:NDR- - 7-75 SPEC 201 11


Produktspezifikationen

Marke: Vivotek
Kategorie: Nicht kategorisiert
Modell: NDR-75

Brauchst du Hilfe?

Wenn Sie Hilfe mit Vivotek NDR-75 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert Vivotek

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung für -Kategorien-