Vemer VCR Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Vemer VCR (1 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 85 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/1
V3IS00429-011
Mod. VCR
User Manual
VOLTAGE CONTROL RELAY
Read all the instructions carefully
Voltage control relay is an electronic control device to be mounted on a panel in a VCR
standard enclosure. It operates an external circuit following the tripping setting 2-DIN size
(direct or alternate voltage): threshold values, hysteresis and change-over delay can be
adjusted.
SAFETY INSTRUCTIONS
During the installation and operation of the device observe the following instructions:
1) The device must be installed by a qualified person, strictly following the wiring
diagrams.
2) The device must be installed in an electrical panel which, after installation, leaves
terminals inaccessible.
3) Do not power or connect the device if any part of it is damaged.
4) The electrical system in the building where the device is installed must feature a
circuit breaker and an overcurrent protection device.
5) The device is aimed for use in places with over-voltage category III and pollution
degree, 2 as per standards EN 61010-1.
Code Model Description
VE144200 VCR Voltage-control relay
TECHNICAL SPECIFICATIONS
• Powersupply:230VCA(-15%÷+10%),50/60Hz
• Consumption: 4VA
• Termination:6mm
2 metal blocks
• Output:changeovercontactrelay8A/250VAC(resistiveload)
• Inputsignal
 –10V÷100V
 –50V÷500V
• Fullscaleselectionbywiring(cfr.
Connection diagram
)
• Threshold:tobetrimmer-adjustedbetween10%and100%ofthefullscalevalue
• Hysteresis:tobetrimmer-adjustedbetween5%and50%ofthethresholdvalue
• Relayswitchingdelay:tobetrimmer-adjustedfrom0,1to10seconds
• Signallingby2LEDs
green = power on
red = relay off (alarm)
• Operatingtemperature:–5°C÷+50°C
• Storagetemperature:–10°C÷+70°C
• Inputimpedance:2M
• Enclosure:2DINsize
• Settingofmaximumorminimumrelaybyselector
• Settingofalarmstatusmemorybywayofselector
• Degreeofprotection:IP20/IP40whencorrectlyinstalledinanelectricalpanel
WIRING
• Powerthedeviceupbyconnectingterminal1tolineandterminal5toneutral.
• Connectthesignaltothemeasuringterminalsaccordingtorange(forusewithDCalso
observe polarity):
 –10V÷100Vbetweenterminals2and3
 –50V÷500Vbetweenterminals2and3,afterterminals3and4havebeen
short-circuited
OPERATION
• Selectmaximumorminimumrelaymodeusingtheselectoronthefrontofthedevice
(>Ur maximumrelay,<Ur minimum relay)
• Selectthresholdvoltageusingtrimmer
Sens
• Selecthysteresisvalueusingtrimmer
Hyst
• Selectthedelayvalueusingthe
Delay
trimmer.Thisisthetimeinterveningbetweenthe
momentUrisexceededandthemomenttherelayswitchesover
• Selector
memo
enablesthememorystoringfunction.Afteralarmandtheconsequent
relay switch over, the memory function keeps the acquired output status even when the
measured value is back in the useful range; memory is zeroed using the selector, so that
the device does not need to be switched off
RIFERENCE STANDARDS
ConformitytotheEUdirectives:
2006/95/EC(LowVoltage)
89/336/EECmodiedby92/31/EECand93/68/EEC(EMC)
is declared with reference to the following harmonised standards:
Safety:
EN61010-1
Electromagnetic compatibility:
EN61000-6-2,EN61000-6-4
Dimension
Connection diagram
Operating diagram
36 60
45
65
88
Hyst. (%)
Delay (s)
Sens. (%)
on
of f
memo
>
Ur
<
VCR
ON
OFF
Relay
>
230V
0V
Sens
Delay
0
6 7 8
6 7 8
<
Ur
Maximum relay mode
Rel ay OFF
Rel ay ON
Delay
Hyst
L
N
1
2
3
4
5
6
7
8
L
N
1
2
3
4
5
6
7
8
++
230V
Sens
0
0V
>
<
Ur
Minimum relay mode
Delay Delay
6 7 8
6 7 8
Rel ay OFF
Rel ay ON
Hyst


Produktspezifikationen