Vemer TDMU Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Vemer TDMU (1 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 157 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/1
ISCOM008-0802
Mod. TDMU
User Manual
TDMU MULTIFUNCTION TIME RELAY
Read all instructions carefully
The multifunction time relay
TDMU
is a device standardised in 1-module DIN container,
designed to operate in environments with normal pollution level.
The various alternatives of intervals and functions available made the device easy to adapt in
any type of automatism such as control of light, motors, heating, fun, pumps.
SAFETY WARNINGS
During the installation and operation of the instrument, proceed in accordance with the
instructions below:
1) The instrument should be installed by a competent operator following the
installation diagrams carefully
2) The instrument should be installed in a panel from which no access can be gained to
the terminals after installation
3) Do not power or connect the instrument if any part of it is damaged
4) The electrical system of the building in which the instruments is to be installed
should have a switch and a protective device against over-currents
5) The instrument is designed for installations with over-voltage category III and
pollution level 2, in accordance with the EN 61010-1 standard.
TECHNICAL SPECIFICATIONS
Power supply: AC/DC 12 ÷ 240V (AC 50/60Hz) -15% ÷ +10%
Consumption: AC 0,7÷3VA / DC 0,5÷1,7W
Supply indication: green LED
Time range with potentiometer: 0,1s ÷ 10 days
Output
Number of contacts: 1 changeover
Output indication: red LED multifunction
Contact capacity: 16A 250V AC1 / 24V DC
Inrush current: 30A / < 3 second
Minimum breaking capacity DC: 500mW
Breaking capacity: 4000VA / AC1 , 384W / DC
Mechanical life: 3x107
Electrical life: 0,7x105
Operating temperature: -20°C ÷ +55°C
Storage temperature: -30°C ÷ +70°C
Protection degree: IP40 from front panel
OPERATION
Operation conditions
While installing this device it is necessary to consider temperature rate of ambient devices
so the operation temperature stated in technical parameters is kept. It is necessary to
ensure air circulation so the operation temperature is not exceeded in any case.
It is necessary to avoid placing devices close to sources of electromagnetic disturbances to
ensure their correct function.
It is necessary to pay attention while connecting products to the circuit with appliances
that create electromagnetic disturbances (conductors, motors), or power cables close
to them. It is recommended to have the connection cables of a product (supply and
operating inputs) as short as possible and have them led separately into power conductors.
Handling and use
Use a screwdriver with an approximate width 2 mm for installation and setting
Do not use brute force to screw input terminals (maximally 0,5 N/m).
Do not put exceeded pressure on to the holding parts of terminals so the inner
construction of the device is not damaged.
Protect the device against falls and excessive vibrations
Do not overload relay output contacts, mainly while using loads of another category
then AC1
If contacts of relay melted while switching big loads, it is necessary to use an inserted
contactor or power relay rated for required load in the current installation.
For a correct setting of the relay, observe the following operations:
setting the
Rought time
with its potentiometer (see time ranges in the box
“OPERATING DIAGRAMS”)
setting the Fine time with its potentiometer (between 10% and 100% of the Rought
time setting)
setting the Function modes (ten mode available).
REFERENCE STANDARDS
Conformity to the EU directives:
2006/95/EC (Low Voltage)
89/336/EEC modi ed by 92/31/EEC and 93/68/EEC (EMC)
is declared with reference to the following harmonised standards:
Safety:
EN 61010-1
Electromagnetic compatibility:
EN 61000-6-2, EN 61000-6-4
Dimensions
Wiring diagram
Operating diagrams
1
10
ON
OFF
1
1 10
1
10
10
m
S
h
d
Rough time setting
Fine time setting
(% rough time)
Function setting
Time ranges
0,1-1 s
1-10 s
0,1-1 min
1-10 min
0,1-1 h
1-10 h
0,1-1 day
1-10 days
only ON
only OFF
Delay ON after energization
Delay OFF after energization
Cycler beginning with pause
after energisation
Cycler beginning with impulse
after energisation
Delay OFF after de-energisation,
instant make of output
Delay OFF responding to make of control
contact regardless its length
Delay OFF after break of control
contact with instant output
Delay OFF after make and break of
control contact
Memory (impulse) relay
Pulse generator
Un = 12 ÷ 240V


Produktspezifikationen

Marke: Vemer
Kategorie: Nicht kategorisiert
Modell: TDMU

Brauchst du Hilfe?

Wenn Sie Hilfe mit Vemer TDMU benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert Vemer

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung für -Kategorien-