Tripp Lite SUPDMB20K Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Tripp Lite SUPDMB20K (48 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 17 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/48
Owner’s Manual
SmartOnline® 16 & 20kVA UPS
with N+1 Configuration Options
Models: SU16KRT, SU16KRT-1TF, SU16KRT8, SU16KRTG, SU16KRTHW, SU20KRT,
SU20KRT-1TF, SU20KRT8, SU20KRTG, SU20KRTHW, SU20KRTHWTFASSM
Introduction 2
Important Safety Warnings 3
Mounting 4
Features 6
Connection 8
Manual Bypass Operation 10
Storage & Service 12
Warranty & Product Registration 12
Español 13
Français 25
Русский 37
PROTECT YOUR INVESTMENT!
Register your product for quicker service and ultimate peace of mind.
You could also win an ISOBAR6ULTRA surge protector—a $100 value!
www.tripplite.com/warranty
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2018 Tripp Lite. All rights reserved.
2
10kVA UPS Loads 10kVA and lower
Parallel
PDU
10kVA UPS
10kVA UPS Loads 10-20kVA
Parallel
PDU
10kVA UPS
Introduction
Your Tripp Lite 16/20kVA UPS system includes two 8/10kVA power modules along with a parallel PDU and communications cable that
combines the output of the two UPS power modules to directly power your equipment. Your UPS automatically supports N+1 fault tolerance
at load levels up to 50% and non-redundant operation at loads greater than 50%. The included parallel PDU with bypass switch also
enables hot-swappable replacement of either or both power modules without downtime. For additional configuration assistance, contact
Tripp Lite.
10kVA Redundant Configuration (10kVA max load) 20kVA Non-Redundant Configuration (20kVA max load)
Redundant Operation YES
Fault-Tolerance YES
Hot-Swappable UPS Replacement YES
Increased Capacity NO
Redundant Operation NO
Fault-Tolerance NO
Hot-Swappable UPS Replacement YES
Increased Capacity YES
When two UPS systems are
loaded to a maximum of 50%,
your conguration will receive full
redundancy—fault-tolerance with
full support for hot-swappable UPS
replacement in the case of sudden
UPS failure.
When two UPS systems are loaded to a maximum of 100%, your
configuration will receive the full capacity of both UPS systems
combined to power larger loads. This configuration does NOT
carry redundancy or fault-tolerance options. Hot-swappable UPS
replacement is possible if you put the PDU in bypass mode (See
” Section).Manual Bypass Operation
To ensure fault-tolerance, load the two parallel UPS systems to a
maximum of 50% of the combined rating for both UPS systems. For
example, if you have two 10kVA UPS systems, you will have fault-
tolerant operation if the load level remains at 10kVA or lower.
Your can use this configuration to grow your UPS power capacity to
16kVA (when two 8kVA UPS systems are used) or 20kVA (when two
10kVA UPS systems are used). In this configuration, fault-tolerance
is NOT available.
For 16/20KVA UPS Configurations
• Economy-mode operation is not supported
• For best results, connect an equal number of external battery packs to each UPS power module.
Note: Use the included 8/10kVA power module manual for UPS operation and configuration options once you have completed the setup of your 16/20kVA
UPS per the installation information on the following pages.
3
Important Safety Warnings
Location Warnings
Install your PDU indoors, away from excess moisture or heat, direct sunlight, dust and conductive contaminants.
Install your PDU in a structurally sound area. Your PDU is heavy; take care when moving and lifting the unit.
Only operate your PDU at indoor temperatures between 32° F and 104° F (between 0° C and 40° C). For best results, keep indoor
temperatures between 62° F and 84° F (between 17° C and 29° C).
Leave adequate space around all sides of the PDU for proper ventilation.
Do not install the PDU near magnetic storage media, as this may result in data corruption.
Equipment Connection Warnings
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the
life support equipment or to significantly affect its safety or effectiveness is not recommended.
When connecting to a UPS, the UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS is not
connected to an AC supply.
Maintenance Warnings
Your PDU does not require routine maintenance. Do not open for any reason. There are no user-serviceable parts inside.
Battery Warnings
Service and repair should be done only by trained personnel. During any service work to the UPS, it should be turned off or manually
bypassed via the PDU. Note that potentially lethal voltages exist within this unit as long as the battery supply is connected.
Do not connect or disconnect battery module(s) while the UPS is operating from the battery supply or when the detachable PDU is not in
bypass mode.
During “hot-swap” battery module replacement your UPS will be unable to provide battery backup in the event of a blackout.
SAVE THESE INSTRUCTIONS.
This manual contains important instructions and warnings that should be followed during the installation and maintenance of
all Tripp Lite Parallel PDUs. Failure to heed these warnings may affect your warranty.


Produktspezifikationen

Marke: Tripp Lite
Kategorie: Nicht kategorisiert
Modell: SUPDMB20K

Brauchst du Hilfe?

Wenn Sie Hilfe mit Tripp Lite SUPDMB20K benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert Tripp Lite

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung für -Kategorien-