Owner’s Manual
PDUMH15NET/PDUMH20NET
Switched Rack PDU
• 120V, 60 Hz AC Input and Output
PDUMH15HVNET/PDUMH20HVNET
Switched Rack PDU
• 208/230V, 50/60 Hz AC Input and Output
Important Safety Instructions 2
Installation 3
Features 6
Technical Support 8
Warranty and Product Registration 8
Español 9
Français 17
Русский 25
Deutsch 33
PROTECT YOUR INVESTMENT!
Register your product for quicker service
and ultimate peace of mind.
You could also win an
ISOBAR6ULTRA surge protector—
a $100 value!
www.tripplite.com/warranty
TrippLite.Eaton.com/support
Copyright © 2023 Tripp Lite. All rights reserved.
2
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be
followed during the installation, operation, and storage of this product.
Failure to heed these instructions and warnings may affect the product
warranty.
CAUTION Only those who are properly trained or qualified to use this device should
do so. Anyone who is not trained or qualified should not use this device unless it is under the
supervision of someone who is properly trained or qualified to do so.
Children must be supervised to ensure that they do not use the device as a toy.
Never use the device if the cord and plug are damaged; if it is not working properly,
or if it has been dropped or damaged, take it to an authorized service center for inspection
and repair.
If the power cord is damaged, it must be replaced by the manufacturer, its authorized service
agent, or by qualified personnel in order to avoid a danger.
Important Safety Instructions
The PDU provides the convenience of multiple outlets, but DOES NOT provide surge or line
noise protection for connected equipment.
The PDU is designed for indoor use only, in a controlled environment, away from excess
moisture, temperature extremes, conductive contaminants, dust or direct sunlight.
Keep indoor ambient temperature between 32°F and 122°F (0°C and 50°C).
The PDU must be installed by a qualified technician only.
Do not attempt to mount the PDU to an insecure or unstable surface.
Install in accordance with National Electrical Code standards. Be sure to use the proper
overcurrent protection for the installation, in accordance with the plug/equipment rating.
Connect the PDU to an outlet that is in accordance with your local building codes and that is
adequately protected against excess currents, short circuits and earth faults.
The electrical outlets supplying power to the equipment should be installed near the equipment
and easily accessible.
Do not connect the PDU to an ungrounded outlet or to extension cords or adapters that
eliminate the connection to ground.
Be sure to provide a local disconnect device on any models that are permanently installed
without a plug that is easily accessible.
Never attempt to install electrical equipment during a thunderstorm.
Individual equipment connected to the PDU should not draw more current than the individual
PDU’s outlet’s rating.
The total load connected to the PDU must not exceed the maximum load rating for the PDU.
Do not attempt to modify the PDU, input plugs or power cables.
Do not drill into or attempt to open any part of the PDU housing. There are no user-serviceable
parts inside.
Do not attempt to use the PDU if any part of it becomes damaged.
Use of this equipment in life support applications where failure of this equipment can
reasonably be expected to cause the failure of the life support equipment or to significantly
affect its safety or effectiveness is not recommended.
A
B
A
1-1 C
D
1-2
A
B
C
D
1-3
A
B
C
D
3
Installation
Mounting the PDU
The PDU supports five primary mounting configurations: 1U Rack, 0U Rack (Vertical), Wall, Under-
Counter and Reduced-Depth.
Note: Regardless of configuration, the user must determine the fitness of hardware and procedures before
mounting. The PDU and included hardware are designed for common rack and rack enclosure types and may
not be appropriate for all applications. Exact mounting configurations may vary. Screws for attaching the
mounting brackets to the PDU are included. Use only the screws supplied by the manufacturer, or their exact
equivalent (#6-32, 3/16" flat head).
1-1 1U Rack Mounting: Use 3 screws A to
attach each of the 2 longer mounting
brackets B to the PDU as shown. You
can mount the PDU in a recessed
position by attaching the mounting
brackets so they extend beyond the front
panel of the PDU. Mount the PDU in the
rack by inserting 4 user-supplied screws
C through the mounting brackets D and
into the mounting holes of the rack rails.
1-2 0U Rack Mounting: Use 3 screws A to
attach each of the 2 shorter mounting
brackets B to the PDU as shown. Mount
the PDU vertically by inserting 2 or more
user-supplied screws C through the
mounting brackets D and into mounting
points in the rack or rack enclosure.
1-3 Wall Mounting: Use 3 screws A to
attach each of the 2 shorter mounting
brackets B to the PDU as shown. Mount
the PDU to the wall by inserting 2 or
more user-supplied screws C through
the mounting brackets D and into
secure mounting points.

Produktspezifikationen

Marke: Tripp Lite
Kategorie: Nicht kategorisiert
Modell: PDUMH15HVNET
Breite: 375.2 mm
Tiefe: 440.2 mm
Gewicht: 4040 g
Produktfarbe: Schwarz
Höhe: 43.7 mm
Stecker: C14-Koppler
AC Eingangsfrequenz: 50 - 60 Hz
Verpackungsbreite: 525.8 mm
Verpackungstiefe: 584.2 mm
Verpackungshöhe: 144.8 mm
Paketgewicht: 5990 g
Montage: Horizontal
Zertifizierung: UL 60950-1 (USA, Canada), Class A (Emissions), NOM (Mexico), CE (IEC 60950)
Display: LCD
Ursprungsland: Taiwan
Kabellänge: 2 m
Gehäusematerial: Metall
LED-Anzeigen: Ja
Temperaturbereich bei Lagerung: -15 - 50 °C
Anzahl Produkte pro Versandkarton: 1 Stück(e)
Abmessungen (BxTxH): 439 x 376 x 28.7 mm
Nachhaltigkeitszertifikate: RoHS
Höhe bei Betrieb: 0 - 3000 m
Anzahl der AC-Ausgänge: 8 AC-Ausgänge
AC-Steckertypen: C13-Koppler
Stromstärke (maximal): 15 A
Nominale Eingang Spannung: 200-240 V
Nominale Ausgang Spannung: 200-240 V
Rack-Kapazität: 1U
PDU-Typen: Geändert

Brauchst du Hilfe?

Wenn Sie Hilfe mit Tripp Lite PDUMH15HVNET benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten