Programmable Relay I/O Card
Model: RELAYIOCARD
Copyright © 2010 Tripp Lite. All rights reserved. All trademarks are the property of their respective owners.
1111 W. 35th Street, Chicago, IL 60609 USA
www.tripplite.com
Use of this equipment in life support applications where failure of this equipment can reasonably be expected
to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not
recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen
or nitrous oxide.
1 Introduction 2
1.1 Product Features 2
1.2 Package Contents 2
2 Installation and Setup 2
2.1 System Requirements 2
2.2 Communications Setup 2
2.3 Configuration 3
2.4 AS400 Configuration 4
3 Specifications 5
4 Warranty & Warranty Registration 5
Español 6
Français 11
201011142 932815.indb 1 1/6/2011 9:15:13 AM
2
1. Introduction
2. Installation and Setup
1.1 Product Features
The RELAYIOCARD is a programmable UPS management device featuring:
• 6 programmable relay output contacts
• Configurable normal open or normal close for each relay contact
• Configurable UPS shutdown delay time
• Configurable input signal to shutdown UPS or test battery
The RELAYIOCARD allows you to:
• Monitor UPS status and events
• Perform remote system shutdowns and battery tests
1.2 Package Contents
This Package Contains:
• RELAYIOCARD
• Configuration Cable
• Faceplates
• Owner’s Manual
2.1 System Requirements
The RELAYIOCARD supports all Tripp Lite SmartOnline™ UPS Systems and select SmartPro™ UPS Systems, including
SMART1050SLT, SMART1500SLT, SMART2200RMXL2U, SMX1050SLT, SMX1500SLT, SMART3000SLT, SMART2200SLT,
SM2200RMNAFTA, SMART2600RM2U, SMART3000RM2U, SMART1500CRMXL, SMART1500SLTXL, SMART750XLa,
SMX3000XLRT2U and SMX2200XLRT2U. Supported systems must run a UPS protocol of 3008 or above.
To determine your UPS protocol:
1. Open Tripp Lite PowerAlert software.
2. Click on the “Misc” button on the main screen of the PowerAlert console.
3. View the protocol variable.
2.2 Communications Setup
1. Connect Tx to pin 2, Rx to pin 3 and GND-C to pin 5 of RS-232 DB9 port.
2. In the Windows environment, launch the Hyper Terminal program, then open the specified COM port.
3. Set the following properties – Baud rate: 2400, Data Bits: 8, Parity: None, Stop Bit: 1, Flow Control: None.
201011142 932815.indb 2 1/6/2011 9:15:14 AM
3
2. Note: Contacts R1~R6 can be configured for different power events.
3. to configure the input signal.Press 2
In this menu, the input signal can be redefined as a shutdown UPS signal or battery
test signal. The UPS shutdown delay time can be adjusted to a maximum of 9999
seconds.
4. to configure the normal open or normal close for each relay.Press 3
Once the configuration is complete, SW2 must be switched ON to apply the
new settings. To automatically reset to default settings, switch SW2 to the OFF
position.
5. to quit the configuration session. When the system prompts you to save your settings, press to save or to ignore.
Press 0
Y N
Application Example
Using the default settings, set SW1 and SW2 to OFF. Apply 12V DC to Common
contact and connect the lamps to R1~R6 terminals. Install a push button from the
Common contact to the input terminal. Press the button for at least 3 seconds to shut
down the UPS remotely.
2. Installation and Setup (continued)
2.3 Configuration
1. Press Enter RELAYIOCARD to open the main menu of the .
Press 1 to configure the alarm event for R1~R6.
+---------------------------+
| UPS Relay Card |
+---------------------------+
Firmware Version: Relay Card V1.4
[1].Customize Output Relay
[2].Configure Input Signal
[3] Customize Normal Open or Normal Close
[0].Quit
Please Enter Your Choice =>
+----- ----------------------+
| Custom ize Outpu t Relay |
+-------- -------------------+
Relay Sele cted Even t
[1].Relay1: Summary Al arm
[2].Relay2: Power Fail
[3].Relay3: Battery Lo w
[4].Relay4: On Bypass
[5].Relay5: Overload
[6] Relay6: Over Tempe rature
[0].Back T o Previous Menu
Please Enter Your Choice =>
+---------------------------+
| Configure Input Signal |
+---------------------------+
[1].Act as Shutdown or Test: Shutdown
[2].Input Signal Confirm: 3 Seconds
[3].Delay Before Shutdown: 30 Seconds
[0].Back To Previous Menu
Please Enter Your Choice =>
+---------------------------+
| Customize Output Relay |
+---------------------------+
Relay Selected Event
[1].Relay1: Normal Close
[2].Relay2: Normal Open
[3].Relay3: Normal Close
[4].Relay4: Normal Open
[5].Relay5: Normal Close
[6].Relay6: Normal Open
[0].Back To Previous Menu
Please Enter Your Choice =>
Common
GND-R
R1
R2
R3
R4
R5
Input
+12V
Summary Alarm
Power Fail
Battery Low
On Bypass
Overload
Shutdown UPS
R6
Over Temperature
201011142 932815.indb 3 1/6/2011 9:15:15 AM


Produktspezifikationen

Marke: Tripp Lite
Kategorie: Kabel für Computer und Peripheriegeräte
Modell: AS400CABLEKIT2
Produktfarbe: Grün
Kabellänge: 1.8 m
Kompatible Produkte: Tripp Lite SmartOnline, SmartPro
Anschluss 1: DB9
Anschluss 2: DB9

Brauchst du Hilfe?

Wenn Sie Hilfe mit Tripp Lite AS400CABLEKIT2 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Kabel für Computer und Peripheriegeräte Tripp Lite

Bedienungsanleitung Kabel für Computer und Peripheriegeräte

Neueste Bedienungsanleitung für -Kategorien-