Panduit Q1L2B1L2N24AFA0 Bedienungsanleitung

Panduit Stekkerdoos Q1L2B1L2N24AFA0

Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Panduit Q1L2B1L2N24AFA0 (3 Seiten) in der Kategorie Stekkerdoos. Dieser Bedienungsanleitung war für 8 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/3
SmartZone Network-Enabled MSPO Series
Rack PDU (for Aggregate and Per Outlet Power Monitoring with Switching) S P E C I F I C A T I O N S H E E T
k e y f e a t u r e s a n d b e n e f i t s
Aggregate
power monitoring
Performs real-time Rack PDU aggregate and per outlet monitoring at the individual device level
Per outlet monitoring Per outlet monitoring provides data to determine if power distribution is accurate allowing for PUE calculation and individual
servers to be identified as candidates for additional capacity, redeployment or decommissioning, improving overall data
center efficiency; monitors current, voltage, kVA, kWhr, kW, Frequency, and Power Factor loads to monitor, document, and
manage operational power utilization
Remote power
monitoring and
switching controls
Allow users to remotely access, configure, or manage units; or manage individual or a group of outlets such as turning
outlets off that are not in use (preventing overloads) or recycling power to locked-up equipment, minimizing costly
downtime and travel times to service equipment
Low profile breakers Low profile circuit breakers reduce the PDU depth preventing obstruction within the back of the cabinet
Time
delay sequencing
Executes time delay sequencing of individual power outlets to avoid circuit overload due to the high in rush of current
at equipment start up
Environmental
monitoring
Includes two available ports for the connection of (optional) environmental sensors that monitor cabinet conditions
such as temperature, humidity and airflow to facilitate capacity management and identify potential causes of
equipment failure
Alarm thresholds Enables users to define critical power or environmental thresholds that, if reached, will prompt alarm notifications for
resolution to ensure operational resilience
LCD digital display Displays a visible on-unit warning when the current draw of rack PDU is close to the maximum Amp draw levels,
helping to quickly identify and resolve concerns and avoid risk of overloaded circuits
Integrated
locking receptacle
Protects against vibration and external elements that can easily dislodge external locking clips or guides; works with
any standard IEC power cord
Customizable
configurations
Offers standard or customizable builds with single or three phase options, a range of current ratings, and different
power outlets that can be adapted for varying power requirements
SmartZone
Software integration
Captures actionable power and environmental data that can be utilized by SmartZone Software to enable data
center operational and energy efficiencies, capacity management, and resilience
t e c h n i c a l i n f o r m a t i o n
Dimensions: 32A or smaller vertical units: 70"H x 2.5"W x 2.36"D (1778mm x 64mm x 60mm)
50A or larger vertical units: 70"H x 3.25"W x 2.36"D (1778mm x 82mm x 60mm)
Horizontal units: 1.73"H x 17.0"W x 8.84"D (44mm x 432mm x 225mm)
Packaging: 3-meter or 10 foot long power cord, screws, and tool-less button mounting
Mounting: Vertical power strips provide multiple outlets and do not occupy any rack spaces
Horizontal units mount via EIA 19" equipment mounting rails
Amperage ratings: Global: 32 Amps
NA: 20, 30, 60 Amps
s p e c i f i c a t i o n s
Network-Enabled MSPO (Monitored and Switched Per Outlet) Series Rack Power Distribution Units (PDUs) safely
and efficiently manage and distribute power to installed equipment and are available in a range of electrical and outlet
configurations that cover all global regions. Network-Enabled MSPO Series Rack PDUs have remote switching
capabilities, enabling individual outlets or a group of outlets to be switched on or off to reboot equipment or restrict
unauthorized use of individual outlets. Power monitoring at the individual outlet level provides actionable management
data on the power consumption of each connected IT device enabling the redeployment or decommissioning of
individual servers to reclaim available or under-utilized power capacity. The Rack PDU is connected directly to the
network to provide local and remote monitoring of aggregate power, and environmental data, to quickly identify potential
power issues and reclaim available or under-utilized power capacity. Network-Enabled MS Series Rack PDUs integrate
with comprehensive DCIM software platforms, to access current and historical trending information and event
notification alarms. For more specialized applications, Panduit offers a custom made service which involves designing
and manufacturing a rack PDU to meet exact customer specifications.
www.pandu it.com
a p p l i c a t i o n s
The SmartZone Network-Enabled MSPO Series Rack PDU safely and efficiently manages and distributes power to multiple rack or cabinet
devices via a single power connector. It can be deployed and utilized as a standalone “intelligent” rack PDU.
The SmartZone Network-Enabled MSPO Series Rack PDU is available for order as standard “off-the-shelf units for most common
requirements, or as customized build configurations that are designed and manufactured to meet exact product requirements.
The SmartZone Network-Enabled MSPO Series Rack PDU offers a variety of horizontal and vertical mounting options that support simple flexible
installations for Panduit® Net-Access and Net-SERV ® Cabinets, or 2- and 4-post racks.
As part of an fully intelligent data center or DCIM solution, the SmartZone Network-Enabled MSPO Series Rack PDU captures aggregate Rack
PDU power and environmental data that can be used by SmartZone Software to more effectively manage and optimize operational efficiencies.
SmartZone Network-Enabled MSPO Series Rack PDU
(for Aggregate and Per Outlet Power Monitoring with Switching)
Parameter Value
Mounting Tool-less button style
Upgradability Firmware upgradeable
Network Connection RJ45 socket
Connectivity 10/100 MB Ethernet
Supported Protocols HTTP, HTTPS, SNMP, NTP, SMTP
Operating Temperature 50°F to 104°F (10°C to 40°C)
Rated Voltage 120, 208, or 230/400 VAC (Three phase), 120, 208, or 230 VAC (Single phase)
Rated Current Up to 63A AC Nominal
Rated Frequency 48 to 62Hz
t e s t d a t a
l o c a l d i s p l a y f e a t u r e s
1. Local LCD Display – Shows the firmware version number,
device model number, serial number, MAC Address, IP
Address, power and environmental sensor readings
2. Remote Sensors Includes two RJ45 connector ports to monitor
temperature and humidity, and transmits SNMP-based or email
alert notifications when conditions exceed dened thresholds
3. Network Connection – 10/100 MB Ethernet connection
for remote power monitoring
4. Reset – Reboots the processor
5. Mode Allows reset to defaults and changes the displayed
information on the LCD
2
n e t w o r k - e n a b l e d r a c k P D U c o n n e c t i o n t o t h e n e t w o r k
SmartZone Network-Enabled MSPO Series Rack PDU
(for Aggregate and Per Outlet Power Monitoring with Switching)
Item Number Item Description
SmartZone Network-Enabled MSPO Series Rack PDUs (Global)
Q1L2B2P6M24AQA0 32 A Three Phase Vertical Rack PDU, 230V/400V, 12 IEC C-13 and 12 IEC
C-19 locking, IEC-60309-6H 3P+N+E plug
Q1L2B2P6M24AFA0 32 A Three Phase Vertical Rack PDU, 230V/400V, 18 IEC C-13 and 6 IEC
C-19 locking, IEC-60309-6H 3P+N+E plug
Q1L2B3J2M24AFA0 32 A Single Phase Vertical Rack PDU, 230V, 18 IEC C-13 and 6 IEC C-19
locking, IEC-60309-6H 2P+E plug
SmartZone Network-Enabled MSPO Series Rack PDUs (NA)
P1L2B1L2N16BQA0 30 A Single Phase, Horizontal Rack PDU, 208V, 12 IEC C-13 and 4 IEC
C-19 locking receptacles, NEMA L6-30P plug
Q1L2B2W6N24AFA0 60 A Three Phase, Vertical Rack PDU, 208V, 12 IEC C-13 and 6 IEC C-19
locking receptacles, IEC-60309-9H 3P+E plug
Q1L2B1P3N24AFA0 30 A Three Phase Vertcial Rack PDU, 208V, 18 IEC C-13 and 6 IEC C-19
locking receptacles, NEMA L21-30P plug
Q1L1B1F0A24AFA0 20 A Single Phase Vertical Rack PDU, 208V, 18 IEC C-13 and 6 IEC C-19
receptacles, NEMA 6-20P plug
Q1L2B1L2N24AFA0 30 A Single Phase Vertical Rack PDU, 208V, 18 IEC C-13 and 6 IEC C-19
locking, NEMA L6-30P plug
(Optional) SmartZone Sensors
ZEAIR-02 Airflow Sensor
ZETHL-15 Humidity Sensor
ZEDIFFPRESS-01, 02, 03, 05 Differential Pressure Transducer
ZETHL-14 Temperature Sensor
ZEWS-03-03 Water Rope Sensor
p a r t n u m b e r s
© 2015 Panduit Corp.
ALL RIGHTS RESERVED.
PVSP113--WW-ENG
5/2015
WORLDWIDE SUBSIDIARIES AND SALES OFFICES
For a copy of Panduit product warranties, log on to www.panduit.com/warranty
PANDUIT CANADA
Markham, Ontario
cs-cdn@panduit.com
Phone: 800.777.3300
PANDUIT EUROPE LTD.
London, UK
cs-emea@panduit.com
Phone: 44.20.8601.7200
PANDUIT JAPAN
Tokyo, Japan
cs-japan@panduit.com
Phone: 81.3.6863.6000
PANDUIT SINGAPORE PTE. LTD.
Republic of Singapore
cs-ap@panduit.com
Phone: 65.6305.7575
PANDUIT AUSTRALIA PTY. LTD.
Victoria, Australia
cs-aus@panduit.com
Phone: 61.3.9794.9020
PANDUIT LATIN AMERICA
Guadalajara, Mexico
cs-la@panduit.com
Phone: 52.33.3777.6000
Contact Customer Service by email: cs@panduit.com
or by phone: 800.777.3300
Visit us at www.panduit.com
For more information