Mean Well EDR-75-24 Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Mean Well EDR-75-24 (3 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 6 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/3
Installation Manual
Type
EDR DIN rail power supply
Series EDR-75, EDR-120, EDR-150
EDR-75-12 INPUT: 100-240VAC 1.6A 50/60Hz OUTPUT: 12V 6.3A
EDR-75-24 INPUT: 100-240VAC 1.6A 50/60Hz OUTPUT: 24V 3.2A
EDR-75-48 INPUT: 100-240VAC 1.6A 50/60Hz OUTPUT: 48V 1.6A
EDR-120-12 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 12V 10A
EDR-120-24 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 24V 5A
EDR-120-48 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 48V 2.5A
EDR-150-24 INPUT: 100-120VAC 2.6A 50/60Hz OUTPUT: 24V 5.2A
200-240VAC 1.65A 50/60Hz 24V 6.5A
Introduction
EDR is a DIN rail power supply series with an economical price and slim design. Like other Mean Well’s DIN series,
they can be mounted on a TS35 Standard DIN rail.
Installation
( )1 Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a
heat source.
( )2 The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on
the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not
allowed.
( )3 Use copper wire only, and recommended wires are shown as below.
AWG 18 16 14 12
Rated Current of
Equipment (Amp) 7A 10A 15A 20A
Cross-section of
Lead(mm2 ) 0.8 1.3 2.1 3.3
Note: Current each wire carries should be de-rated to 80% of the current suggested
above when using 5 or more wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make
sure each contact is connected to wires to prevent too much current stress on a single contact.
( )4 Use wires that can withstand temperatures of at least 80°C, such as UL1007.
( )5 Recommended wire strapping length is 5mm (0.197”).
( )6 Recommended screwdriver is 3mm, slotted type.
Installation Manual
3
12
4
( )7 The recommended torque setting for terminals is shown as below.
Model I/P O/P
EDR-75 6.9 kgf-cm (6 Lb-in) 6.9 kgf-cm (6 Lb-in)
EDR-120 7.5 kgf-cm (6.5 Lb-in) 7.5 kgf-cm (6.5 Lb-in)
EDR-150 7.5 kgf-cm (6.5 Lb-in) 7.5 kgf-cm (6.5 Lb-in)
( )8 Suggested fuse and maximum number of the EDR PSUs that can be connected to a circuit breaker at 230V are
shown as below.
Model Fuse Circuit breaker
C16 D16
EDR-75 T3.15A/L250V 4 9
EDR-120 T4A/L250V 5 9
EDR-150 T4A/L250V 5 8
( ) 9 Mounting Instruction
Mount as shown in figure only, with input terminals down, or else sufficient cooling will not be possible.
Admissible DIN rail TS35/7.5 or TS35/15
For rail fastening
( )a Tilt the unit slightly rearwards.
( )b Fit the unit over top hat rail.
( )c Slide it downward until it hits the stop.
( )d Press against the bottom for locking.
( )e Shake the unit slightly to check the locking action.
( )11 For other information about the products, please refer to www.meanwell.com for details.
Warning / Caution !!
( )1Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do
not remove the case of the power supply by yourself!
( )2Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides
together is not allowed.
( )3Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection!
( )4 Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids.
( )5 Only install the unit in a pollution degree 2 environment (Note.1).
( )6 Please do not install the unit in places with high moisture or near the water.
( )7The maximum operating temperature is 45°C for NDR/EDR-75-12; 50°C for NDR/EDR-75-24/48,
NDR/EDR-120-12/24/48 and EDR-150-24, please do not install the unit in places with high ambient
temperature or near fire source.
"Click"
Installation Manual
( )8 The FG ( ) must be connected to PE (Protective Earth).
( )9 Output current and output wattage must not exceed the rated value on its specification.
( )10 Disconnect system from supply voltage:
Before commencing any installation, maintenance or modification work: Disconnect your system from
supply voltage. Make sure that inadvertent connection in circuit will be impossible!
( )11 For continued protection against risk of fire, replace only with same type and rating of fuse.
Pour ne pas compromettre la protection contre les risqué d’incendie, remplacer par un fusible de même
type et de memes caractéristiques nominales.
Note.1: Pollution Degree 2 applies where there is only non-conductive pollution that might temporarily become
conductive due to occasional condensation. Generally refer to dry, well-ventilated locations, such as
control cabinets.
Manufacturer
MEAN WELL ENTERPRISES Co., LTD.
No.28, Wuquan 3rd Rd., Wugu Dist.,
New Taipei City 24891, Taiwan
Tel: +886-2-2299-6100
Web: www.meanwell.com
Branch Office
China
MEAN WELL (GUANGZHOU)
ENTERPRISES Co., LTD.
2F, A Building, Yuean lndustry Park,
Huangcun,Dongpu Yown, Tianhe
District, Gungzhou, China
Post Code:510660
Tel: +86-20-2887-1200
Web: www.meanwell.com.cn
U.S.A.
MEAN WELL USA, INC.
44030 Fremont Blvd., Fremont,
CA 94538, U.S.A.
Tel: +1-510-683-8886
Web: www.meanwellusa.com
Europe
MEAN WELL EUROPE B.V.
Langs de Werf 8, 1185XT
Amstelveen, The Netherlands
Tel: +31-20-758-6000
Web: www.meanwell.eu


Produktspezifikationen

Marke: Mean Well
Kategorie: Nicht kategorisiert
Modell: EDR-75-24

Brauchst du Hilfe?

Wenn Sie Hilfe mit Mean Well EDR-75-24 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert Mean Well

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung für -Kategorien-