Mach Power UPS-TRI30K Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Mach Power UPS-TRI30K (4 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 10 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/4
UPS ONLINE THREE PHASE
10KVA ~ 30KVA
DATASHEET
MOELLO: UPS-TRI10K / UPS-TRI20K / UPS-TRI30K
FEATURES
• High frequency and true online double-conversion
• DSP digitai contrai technology
• Input power factor correction (PFC)
• Wide input voltage range (190V - 485V)
• Output power factor 0.9
• Excellent load-carrying capability, linear derating between 50% and 100% load at 190 - 277 Vac
• Optimized battery configuration: 192V / 240V
• Cold start
• Auto sensing frequency
• ECO mode operation for energy saving
• 50 / 60Hz frequency conversion mode
• Selectable output voltage via LCD
• Selectable battery shutdown voltage (EOD) via LCD
• Power-on self test
• Advanced battery management (ABM)
• Short circuit and overload protection
• Automatic charging in OFF mode
• Auto control fan speed when loads varies
• Dual input
• Advanced quick charge technology, charging speed is increased double
• Configurable transfer time from battery to mains power, reducing the impact on grid or generator
• Automatic startup/shutdown function (optional), automatic transfer to bypass at light load, automatic
restart at acting load; energy-saving and enviranment-friendly
• Standard USB communication port
• Standard emergency power off (EPO)
• Standard maintenance bypass
• Optional extension battery bank
• Optional RS465 I SNMP I AS400 communication port
• Optional N+X redundancy parallel up to 6 units
• Optional battery temperature compensation
| DATASHEET
MAINS INPUT
DC INPUT
OUTPUT
FAN
INTELLIGENT SLOT 2
(SNMP / AS400 / RS485 OPTIONAL)
INTELLIGENT SLOT 1
(SNMP / AS400 / RS485 OPTIONAL)
BYPASS INPUT
MAINTENANCE
BYPASS
MAINS INPUT
BYPASS
BYPASS INPUT
BREAKER
PARALLEL CARD
(OPTIONAL)
USB EPO
BATTERY
TEMPERATURE
COMPENSATION
SPECIFICATION
UPS-TRI10K
10KVA / 9KW
40 x 9Ah
MODEL
Capacity
INPUT
Rated voltage
Voltage range
Rated frequency
Frequency range
Power factor
Total harmonic distortion THDI
Bypass voltage range
OUTPUT
Voltage
Voltage regulation
Frequency
Waveform
Crest factor
Total harmonic distortion THDV
Transfer time
lnverter overload capability
Bypass overload capability
BATTERIES
DC voltage
lnbuilt battery space *
Typical recharge time
SYSTEM
Efficiency
Display
Alarm
UPS-TRI20K
20KVA / 18KW
360 V /380V /400 V/ 415 Vac
277 - 485 Vac (no derating)
190 - 277Vac (linear derating between 50% and 100% load)
50 / 60 Hz (auto-sense)
40 ~ 70 Hz
≥ 0.99
≤5%
-40% - + 15% (settable)
360 V/ 360 V/ 400 V/ 415 Vac (settable)
±1%
Synchronized with utility in mains mode; 50 / 60 ± 0.1Hz in battery mode
Sinusoidal
3:1
≤ 2% (linear load); ≤ 5% (non-linear load)
Mains mode to battery mode: 0ms; lnverter mode to bypass mode: 0ms
102% - 125%: transfer to bypass in 10 mins;
125% - 150%: transfer to bypass in 1 min;
> 150%: transfer to bypass in 0.5 s
240 Vdc; Long time model: 192 Vdc
40 x 7/9Ah
4 Hours
≥ 93%, ECO mode 96%
LCD+ LED
Battery mode, low battery, fans fault etc.
UPS-TRI30K
30KVA / 27KW
60 x 7/9Ah
* battery not included
| DATASHEET


Produktspezifikationen

Marke: Mach Power
Kategorie: Nicht kategorisiert
Modell: UPS-TRI30K

Brauchst du Hilfe?

Wenn Sie Hilfe mit Mach Power UPS-TRI30K benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert Mach Power

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung für -Kategorien-