JUNG UDS4REGHE Bedienungsanleitung

JUNG Schalter UDS4REGHE

Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für JUNG UDS4REGHE (19 Seiten) in der Kategorie Schalter. Dieser Bedienungsanleitung war für 6 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/19
Universal dimming station 4-gang
Light Management
Universal dimming station 4-gang
Art. No. UDS 4 REGHE
Operating instructions
1 Safety instructions
Electrical equipment may only be installed and fitted by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. Always disconnect before carrying out work on the devise or
load. At the same time, take into account all circuit breakers that supply dangerous
voltage to the device or load.
Danger of electric shock. Device is not suitable for disconnection from supply voltage.
The load is not electrically isolated from the mains even when the device is switched off.
Do not connect any lights with integrated dimmers. Device can be damaged.
Do not connect any LED or compact fluorescent lamps that are not specifically suitable
for dimming. Device can be damaged.
Fire hazard. For operation with inductive transformers, each transformer must be fused
on the primary side in accordance with the manufacturer's instructions. Only safety
transformers according to EN 61558-2-6 may be used.
These instructions are an integral part of the product, and must remain with the end
customer.
2 Device components
Figure 1: Device components
(1) Load outputs A1...A4
(2) Keypad for local control
(3) Button , Prog LED Prog
(4) Status LEDs for load outputs A1...A4
(5) Connection of control sections or control voltage
(6) Activation outputs / Switching outputs A1'...A4' E1 ON/OFF...E4 ON/OFF
(7) Connection for central function Central ON/OFF
(8) Connection of hotel card switch
(9) Connection for mains supply
1/19
82577213
J:0082577213 10.12.2013
(10) DIN rail
Meaning of the LED in normal operation
Status LED (4) red and green light up. Initialisation of load output running
Status LED (4) green is illuminated.
Status LED (4) green off
Load output switched on
Load output switched off
Status LED (4) red flashes Control of load output via control section or
load output overtemperature
Status LEDs (4) red and green flash Short-circuit of load output
LED Local control is switched on orc
programming operation is switched on
LED ON flashes Local control of load output, on, brighter n
LED ON flashes Local control of load output, off, darker o
3 Function
Intended use
- Switching and dimming of incandescent lamps, HV halogen lamps and Tronic-
Transformers with halogen lamps or dimmable inductive transformers with halogen or LED
lamps, HV-LED lamps and compact fluorescent lamps
- Suitable for mixed load up to the specified output (see section Technical data)
- Control by means of sensor modules, push-button modules, push-buttons 24 V, push-
button modules 24 V or unlit installation buttons.
- Installation in distribution boxes on DIN rail according to EN 60715
i No mixed-load operation of Tronic and inductive transformers on the same load output.
i HV-LED and compact fluorescent lamps generate high pulsed currents, when they are
operated in the leading edge phase control. Depending on the design and power rating of
these lamps, the connected load of the specified values could vary.
i When connecting dimmable HV-LED lamps or compact fluorescent lamps, set the
operating mode that is suitable for this purpose. Do not connect any other loads.
Product characteristics
- Keypad for control of the dimmer station
- Control outputs for activation of feedback LEDs on the control sections. A1'...A4'
- Electronic short-circuit protection with permanent switch-off after 7 seconds at the latest
- Electronic over-temperature protection
- Switch-on brightness can be adjusted separately for each load output
- Switch-on brightness has been saved permanently.
- Bulb-preserving soft start
- Switch-off with dimming function
- Increase in output power possible through parallel switching of multiple outputs of a
dimmer station
- Connection for hotel card switch
- Central function Central ON, Central OFF
Common switching-on and switching-off of the load outputs
- Operation with pushbutton sensors 24 V or push-button modules 24 V: Parallel switching of
up to four relay or dimmer stations possible
- Operation with sensor modules or pushbutton modules: Parallel switching of two relay or
dimmer stations possible
- Automatic or manual setting of the dimming principle suitable for the load
i Power extension through power boosters (see power booster instructions) Do not connect
any HV-LED lamps or compact fluorescent lamps in combination with power boosters.
i Flickering of the connected lamps due to undershoot of the specified minimum load or
through centralised pulses from the power stations. These are not device faults.
i Brief flickering upon load detection of ohmic loads. No operation is possible during load
detection.
2/19
82577213
J:0082577213 10.12.2013
Light Management
Universal dimming station 4-gang
Behaviour on failure and return of the mains power supply
If only the main power supply fails, then the status of the load output remain intact at first. The
dimmer station initialises when the mains power supply returns. All load outputs are switched off
after initialisation.
i During initialisation the dimmer station cannot be operated. The green and red Status
LEDs (4) of all the load outputs illuminate. Initialisation is complete as soon as all A1...A4
the Status LEDs are off.
Behaviour on failure and return of the mains voltage on one or more load outputs
Should the mains voltage fail, the affected load outputs will switch off. When the mains voltage
returns, the affected load outputs will recalibrate themselves. During the calibration operation,
the green and red Status LEDs (4) illuminate and the load outputs cannot be operated. The load
outputs are switched off after calibration.
Function of hotel card switch
In combination with a hotel card switch, the light is switched on at switch-on brightness when
the hotel card is inserted. When the hotel card is removed, any switched-on lights remain
switched on for 1 minute and the dimmer station can be operated. When this time has elapsed,
the light is darkened to minimum brightness and is then switched off. The dimming function can
be set to steps of 30 seconds. When the dimming starts, the dimmer station can no longer be
operated.
i Only load outputs to whom the central function has been assigned are switched on, whilst
all the load outputs are switched off.
4 Operation
Figure 2: Keypad local control
(4) Status LEDs for load outputs in normal operation A1...A4
(11) Button : Local control c
(12) LED on: Local control or programming mode active c
(13) Button : Operate load output or select Master/Slave ON/n
(14) LED : Feedback LED, load output operation ON/n
(15) Button : Programming mode MODE
(16) Button : Operate load output or select Master/Slave OFF/o
(17) LED : Feedback LED, operate load output OFF/o
i If a hotel card switch is connected, the dimmer station can only be operated when the hotel
card is inserted.
3/19
82577213
J:0082577213 10.12.2013
Light Management
Universal dimming station 4-gang


Produktspezifikationen

Marke: JUNG
Kategorie: Schalter
Modell: UDS4REGHE

Brauchst du Hilfe?

Wenn Sie Hilfe mit JUNG UDS4REGHE benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Schalter JUNG

Bedienungsanleitung Schalter

Neueste Bedienungsanleitung für -Kategorien-