Relay switch insert 2-channel
Relay switch insert 2-channel
Relay switch insert 2-channel
Relay switch insert 2-channel
Relay switch insert 2-channelRelay switch insert 2-channel
Art. no.: 1702SE
Operating instructions
Operating instructions
Operating instructions
Operating instructionsOperating instructions
1
1
1
11 Safety instructions
Safety instructions
Safety instructions
Safety instructionsSafety instructions
Electrical devices may only be mounted and connected by electrically skilled persons.
Electrical devices may only be mounted and connected by electrically skilled persons.
Electrical devices may only be mounted and connected by electrically skilled persons.
Electrical devices may only be mounted and connected by electrically skilled persons.Electrical devices may only be mounted and connected by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Serious injuries, fire or property damage possible. Please read and follow manual fully.Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. Always disconnect before carrying out work on the device or load.
Danger of electric shock. Always disconnect before carrying out work on the device or load.
Danger of electric shock. Always disconnect before carrying out work on the device or load.
Danger of electric shock. Always disconnect before carrying out work on the device or load.Danger of electric shock. Always disconnect before carrying out work on the device or load.
These instructions are an integral part of the product, and must remain with the end customer.
These instructions are an integral part of the product, and must remain with the end customer.
These instructions are an integral part of the product, and must remain with the end customer.
These instructions are an integral part of the product, and must remain with the end customer.These instructions are an integral part of the product, and must remain with the end customer.
2
2
2
22 Intended use
Intended use
Intended use
Intended useIntended use
– Switching of lighting and motors
– Mounting in appliance box according to DIN 49073
– Operation with suitable cover from LB management
3
3
3
33 Product characteristics
Product characteristics
Product characteristics
Product characteristicsProduct characteristics
In combination with 2-gang push-button top
– Two independent outputs
– Time function for output a2
a2
a2
a2a2 adjustable
– Connection of extensions possible
In combination with 1-gang push-button top
– Output a2
a2
a2
a2a2 switches depending on output a1
a1
a1
a1a1 e.g. to switch on ventilation, depending on the
lighting, and switch it off with a delay.
– Switch-on delay of output a2
a2
a2
a2a2 adjustable
– Switch-off delay for output a2
a2
a2
a2a2 can be preset
– Connection of extensions possible
4
4
4
44 Operation with 2-gang push-button top
Operation with 2-gang push-button top
Operation with 2-gang push-button top
Operation with 2-gang push-button topOperation with 2-gang push-button top
Switch load
Switch load
Switch load
Switch loadSwitch load
– Left: operation of output a1
a1
a1
a1a1.
– Right: operation of output a2
a2
a2
a2a2.
ï¿ Press push-button.
Output a1
a1
a1
a1a1, a2
a2
a2
a2a2 switches on and off.
Extension unit operation
Extension unit operation
Extension unit operation
Extension unit operationExtension unit operation
Operation via 3-wire extension with 2-gang push-button top: Press top to switch on, press bot-
tom to switch off.
A 2-wire extension or push-button always switches both outputs.
Rotary dimmer extension only switches output a1
a1
a1
a1a1.
Time function
Time function
Time function
Time functionTime function
If a time function is set for output a2
a2
a2
a2a2 (see Setting the time function/switch-off delay), it switches
off after the set time has expired. The time function starts as soon as output a2
a2
a2
a2a2 is switched on.
To terminate the time function prematurely, output a2
a2
a2
a2a2 must be switched off manually.
The time function cannot be restarted by pressing again.
1 / 7
82401733 07.01.2021
J0082401733
LB management
LB management
LB management
LB managementLB management
Relay switch insert 2-channel
5
5
5
55 Operation with 1-gang push-button top
Operation with 1-gang push-button top
Operation with 1-gang push-button top
Operation with 1-gang push-button topOperation with 1-gang push-button top
Switch load
Switch load
Switch load
Switch loadSwitch load
With the 1-gang push-button top, output a2
a2
a2
a2a2 switches depending on the switching state of output
a1
a1
a1
a1a1.
ï¿ Press push-button.
Output a1
a1
a1
a1a1 switches on or off.
Output a2
a2
a2
a2a2 switches immediately or with a delay.
Extension unit operation
Extension unit operation
Extension unit operation
Extension unit operationExtension unit operation
Operation using 2-wire extension, push-button or rotary dimmer extension corresponds to oper-
ation on the main device.
Operation via 3-wire extension with 1-gang push-button top: Press top to switch on, press bot-
tom to switch off.
Switch-on delay for output a2
Switch-on delay for output a2
Switch-on delay for output a2
Switch-on delay for output a2Switch-on delay for output a2
For output a2
a2
a2
a2a2, a switch-on delay of 3 minutes is activated at the factory. It starts as soon as out-
put a1
a1
a1
a1a1 is switched on. If output a1
a1
a1
a1a1 is switched off again before the switch-on delay has expired,
output a2
a2
a2
a2a2 remains switched off.
Deactivate switch-on delay for output a2
Deactivate switch-on delay for output a2
Deactivate switch-on delay for output a2
Deactivate switch-on delay for output a2Deactivate switch-on delay for output a2
Requirements: Both outputs are switched off.
ï¿ Press the button cover over entire surface for longer than 4 seconds.
Output a1
a1
a1
a1a1 is switched on immediately. After 4 seconds, output a2
a2
a2
a2a2 is briefly switched on.
ï¿ Release the push-button top.
The switch-on delay is deactivated. Both outputs are switched on simultaneously.
Activate switch-on delay of output a2
Activate switch-on delay of output a2
Activate switch-on delay of output a2
Activate switch-on delay of output a2Activate switch-on delay of output a2
Requirements: Both outputs are switched off.
ï¿ Press the button cover over entire surface for longer than 4 seconds.
Both outputs are switched on immediately. After 4 seconds, output a2
a2
a2
a2a2 is switched off.
ï¿ Release the push-button top.
The switch-on delay is switched on.
Switch-off delay
Switch-off delay
Switch-off delay
Switch-off delaySwitch-off delay
For output a2
a2
a2
a2a2 a switch-off delay can be set (see Setting the time function/switch-off delay). It
starts as soon as output a1
a1
a1
a1a1 is switched off.
If output a1
a1
a1
a1a1 is switched on before output a2
a2
a2
a2a2 is switched off, the switch-off delay of output a2
a2
a2
a2a2 is
only restarted if:
– output a1
a1
a1
a1a1 is switched off when the switch-on delay for output a2
a2
a2
a2a2 is switched off.
– output a1
a1
a1
a1a1 is switched off after more than 3 minutes when the switch-on delay for output a2
a2
a2
a2a2
is switched on.
6
6
6
66 Operation with standard motion detector
Operation with standard motion detector
Operation with standard motion detector
Operation with standard motion detectorOperation with standard motion detector
The behavior described here requires the cover and insert to comply with release status V02 or
higher.
The motion detector switches on output a1
a1
a1
a1a1 and switches it off again after the run-on time of
2 minutes set in the motion detector has expired.
During movement, the motion detector switches output a2
a2
a2
a2a2 on, independent of the brightness
and after the switch-on delay has elapsed. After the switch-off delay for output a2
a2
a2
a2a2 has elapsed,
the motion detector switches the output off again.
2 / 7
82401733 07.01.2021
J0082401733
LB management
LB management
LB management
LB managementLB management
Relay switch insert 2-channel
Switch-on delay
Switch-on delay
Switch-on delay
Switch-on delaySwitch-on delay
The switch-on delay for output a2
a2
a2
a2a2 is switched on or off at the insert. For this, a 1-gang push-but-
ton top is placed on the insert instead of the motion detector and is then replaced by the motion
detector again after the switch-on delay has been set, see also operation with 1-gang push-but-
ton top.
Output a2
a2
a2
a2a2 is only switched on if movement is detected during the active switch-on delay or if
output a1
a1
a1
a1a1 is switched on for more than 3 minutes.
Switch-off delay
Switch-off delay
Switch-off delay
Switch-off delaySwitch-off delay
The switch-off delay for output a2
a2
a2
a2a2 is set at the insert as described (see Setting the time function/
switch-off delay).
– The switch-off delay for output a2
a2
a2
a2a2 only starts when movement is no longer detected and
output a1
a1
a1
a1a1 is switched off.
– If only output a2
a2
a2
a2a2 has switched on, the switch-off delay is 1 minute.
– If outputs a1
a1
a1
a1a1 and a2
a2
a2
a2a2 have switched on, the switch-off delay is the time set on the insert.
7
7
7
77 Operation with Bluetooth motion detector
Operation with Bluetooth motion detector
Operation with Bluetooth motion detector
Operation with Bluetooth motion detectorOperation with Bluetooth motion detector
During movement, the motion detector switches output a1
a1
a1
a1a1 depending on the brightness and out-
put a2
a2
a2
a2a2 independently of the brightness and after the switch-on delay has expired. After the run-
on time for output a1
a1
a1
a1a1 and the switch-off delay for output a2
a2
a2
a2a2 set in the motion detector have ex-
pired, the motion detector switches the outputs off again.
Run-on time
Run-on time
Run-on time
Run-on timeRun-on time
The run-on time for output a1
a1
a1
a1a1 is set in the motion detector via app. The run-on time starts when
movement is no longer detected.
Switch-on delay
Switch-on delay
Switch-on delay
Switch-on delaySwitch-on delay
The switch-on delay for output a2
a2
a2
a2a2 is controlled by the insert and is 2 minutes in the default set-
ting. Output a2
a2
a2
a2a2 is only switched on if movement is detected during the active switch-on delay.
Switch-off delay
Switch-off delay
Switch-off delay
Switch-off delaySwitch-off delay
The switch-off delay for output a2
a2
a2
a2a2 is controlled by the cover and is 5 minutes in the default set-
ting. The switch-off delay for output a2
a2
a2
a2a2 starts when movement is no longer detected and output
a1
a1
a1
a1a1 is switched off.
If only output a2
a2
a2
a2a2 has switched on, the preset switch-off delay is extended by up to
1 minute.
8
8
8
88 Operation with timer with display
Operation with timer with display
Operation with timer with display
Operation with timer with displayOperation with timer with display
In combination with a timer with display, the switch insert behaves as with a 1-gang push-button
top. The timer switches output a1
a1
a1
a1a1 on or off manually or automatically. Output a2
a2
a2
a2a2 switches imme-
diately or with a time delay, depending on output a1
a1
a1
a1a1.
Deactivate switch-on delay for output a2
Deactivate switch-on delay for output a2
Deactivate switch-on delay for output a2
Deactivate switch-on delay for output a2Deactivate switch-on delay for output a2
The switch-on delay for output a2
a2
a2
a2a2 is switched off at the insert (factory default: switched on).
Requirements: Both outputs are switched off.
ï¿ Press and for longer than 4 seconds.Æž ÆŸ
Output a1
a1
a1
a1a1 is switched on immediately. After 4 seconds, output a2
a2
a2
a2a2 is briefly switched on.
ï¿ Release both buttons and .Æž ÆŸ
The switch-on delay is deactivated. Both outputs are switched on simultaneously.
Activate switch-on delay of output a2
Activate switch-on delay of output a2
Activate switch-on delay of output a2
Activate switch-on delay of output a2Activate switch-on delay of output a2
The switch-on delay for output a2
a2
a2
a2a2 is switched on at the insert (factory default: switched on).
Requirements: Both outputs are switched off.
3 / 7
82401733 07.01.2021
J0082401733
Produktspezifikationen
Marke: | JUNG |
Kategorie: | Schalten |
Modell: | 1702SE |
Brauchst du Hilfe?
Wenn Sie Hilfe mit JUNG 1702SE benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Schalten JUNG
20 September 2024
3 September 2024
2 September 2024
1 September 2024
28 August 2024
28 August 2024
28 August 2024
23 August 2024
23 August 2024
13 August 2024
Bedienungsanleitung Schalten
- Schalten Asus
- Schalten Belkin
- Schalten Hama
- Schalten HP
- Schalten LogiLink
- Schalten Manhattan
- Schalten Nedis
- Schalten Philips
- Schalten SilverCrest
- Schalten Panasonic
- Schalten Brennenstuhl
- Schalten Clas Ohlson
- Schalten Cotech
- Schalten Profile
- Schalten ZyXEL
- Schalten Bosch
- Schalten Yamaha
- Schalten Powerfix
- Schalten CSL
- Schalten Eminent
- Schalten Linksys
- Schalten Netgear
- Schalten König
- Schalten PCE
- Schalten Renkforce
- Schalten Trotec
- Schalten Schneider
- Schalten Rex
- Schalten Kaiser
- Schalten Vivanco
- Schalten Abus
- Schalten Elro
- Schalten Smartwares
- Schalten Tesla
- Schalten Perel
- Schalten Nexa
- Schalten Tork
- Schalten GEV
- Schalten Goobay
- Schalten Lindy
- Schalten Tripp Lite
- Schalten Ansmann
- Schalten Mercusys
- Schalten Marmitek
- Schalten Honeywell
- Schalten TRENDnet
- Schalten TP-Link
- Schalten Kathrein
- Schalten Flamingo
- Schalten Alcatel
- Schalten Tiptel
- Schalten Black Box
- Schalten Alpine
- Schalten Techly
- Schalten Ebode
- Schalten Theben
- Schalten Vacmaster
- Schalten GAO
- Schalten Hager
- Schalten Behringer
- Schalten Omnitronic
- Schalten Monoprice
- Schalten Ecler
- Schalten Monacor
- Schalten Huawei
- Schalten Victron Energy
- Schalten Ei Electronics
- Schalten Edimax
- Schalten Totolink
- Schalten D-Link
- Schalten Sylvania
- Schalten Audiovox
- Schalten B-Tech
- Schalten QNAP
- Schalten SPC
- Schalten Speaka
- Schalten Digitus
- Schalten Sygonix
- Schalten DataVideo
- Schalten Lancom
- Schalten LevelOne
- Schalten Merten
- Schalten APC
- Schalten Eberle
- Schalten Cisco
- Schalten Delta Dore
- Schalten Grässlin
- Schalten Tenda
- Schalten CyberPower
- Schalten Boss
- Schalten IFM
- Schalten Intertechno
- Schalten Elation
- Schalten Ubiquiti Networks
- Schalten Kramer
- Schalten Aeon Labs
- Schalten Intellinet
- Schalten Eaton
- Schalten AV:link
- Schalten Hikvision
- Schalten Vemer
- Schalten PreSonus
- Schalten Planet
- Schalten EnGenius
- Schalten Finder
- Schalten Mikrotik
- Schalten Shimano
- Schalten Homematic IP
- Schalten Berker
- Schalten Dormakaba
- Schalten Emerson
- Schalten Generac
- Schalten Intermatic
- Schalten KlikaanKlikuit
- Schalten Mercury
- Schalten Paladin
- Schalten Provision ISR
- Schalten Robbe
- Schalten SEC24
- Schalten Steren
- Schalten Suevia
- Schalten AMX
- Schalten Triax
- Schalten WHALE
- Schalten Vimar
- Schalten Cudy
- Schalten Siig
- Schalten Electro Harmonix
- Schalten RGBlink
- Schalten Iogear
- Schalten StarTech.com
- Schalten Smart-AVI
- Schalten Dahua Technology
- Schalten PAC
- Schalten Gefen
- Schalten Avocent
- Schalten Legrand
- Schalten Atlantis Land
- Schalten CYP
- Schalten H-Tronic
- Schalten ATen
- Schalten Axing
- Schalten KanexPro
- Schalten SmartAVI
- Schalten Advantech
- Schalten Kraus & Naimer
- Schalten Chacon
- Schalten Juniper
- Schalten Fibaro
- Schalten Phoenix Contact
- Schalten Audac
- Schalten OSD Audio
- Schalten Wentronic
- Schalten SunBriteTV
- Schalten BZBGear
- Schalten Crestron
- Schalten Kemo
- Schalten ORNO
- Schalten Extron
- Schalten Atlona
- Schalten Equip
- Schalten Heitronic
- Schalten Hamlet
- Schalten STI
- Schalten Matrox
- Schalten Blustream
- Schalten Vivolink
- Schalten Mach Power
- Schalten Ernitec
- Schalten Cambium Networks
- Schalten ConnectPro
- Schalten Micro Connect
- Schalten Intelix
- Schalten ICasa
- Schalten Maclean Energy
- Schalten Cooking Performance Group
- Schalten Flic
- Schalten Liberty
- Schalten Noark
- Schalten 2USB
- Schalten KVM-TEC
- Schalten Setti+
- Schalten PureLink
Neueste Bedienungsanleitung für -Kategorien-
15 Oktober 2024
12 Oktober 2024
11 Oktober 2024
8 Oktober 2024
8 Oktober 2024
5 Oktober 2024
4 Oktober 2024
4 Oktober 2024
4 Oktober 2024
3 Oktober 2024