IQAir® Perfect 16ID-Series
MERV16 Micro-Particle Filtration System
Perfect 16
Installation Manual
Application
The Perfect 16 ID Series is a V-bank filter system that connects to the return air duct or supply air duct of a forced air system.
This Residential / Commercial Air Filtration System has been designed to provide the highest possible air cleaning rate at the
lowest possible pressure drop for residential and commercial forced air systems.Two models are available. The ID-2225 is ideal
for airflow rates up to 1200 cfm (2040 m3/h) and the ID-2530 for airflow rates up to 2000 cfm (3400 m3/h).
Features
Ultra efficient: MERV16 certified (ASHRAE 52.2)
Low air resistance: 0.22 “w.c. ( 54 Pa) at rated airflow
Long filter life: 3 years in average home use
Quick and easy filter replacement: No tools needed
Easy installation: Requires no electrical connections
Rugged steel cabinet: Supports weight of furnace
Medical grade finish: Powder coated galvanized steel
Fully insulated for installation in unconditioned environments
Swiss made quality: 10 year warranty
Product Data
High-Performance Medical-Grade Residential/Commercial
Air Filtration System
System All measurements in inch (mm)
W
H
L
ID-2225: Provide 24 1/2 (622) service clearance in front of unit.
ID-2530: Provide 28 1/2 (721) service clearance in front of unit.
Page 2
Performance Data
Usage vs. Resistance
Average home based on 50% duty cycle
ID-2225 at 1200 cfm ID-2530 at 2000 cfm
in H2O Pa in H2O Pa
new 0.18 44 0.22 54
3 months 0.18 45 0.22 55
6 months 0.19 47 0.23 57
9 months 0.20 50 0.24 60
12 months 0.21 53 0.26 64
15 months 0.22 56 0.28 70
18 months 0.24 59 0.31 78
21 months 0.25 62 0.35 87
24 months 0.26 66 0.39 97
27 months 0.28 71 0.44 110
30 months 0.31 77 0.50 125
33 months 0.34 85 0.57 142
36 months 0.38 94 0.64 161
Minimum Efficiency Reporting Data
ID-2225 ID-2530
Minimum Efficiency Reporting
Value (MERV) MERV 16@492 fpm (2.5m/s) MERV 16@492 fpm (2.5 m/s)
Rated airflow 1400 cfm (2380 m3/h) 2000 cfm (3400 m3/h)
Composite Average Efficiency
E1 (0.3 – 1.0 µm) = 96.7%
E2 (1.0 – 3.0 µm) = 97.7%
E3 (3.0 – 10.0 µm) = 98.5%
E1 (0.3 – 1.0 µm) = 95.9%
E2 (1.0 – 3.0 µm) = 97.3%
E3 (3.0 – 10.0 µm) = 98.3%
Media area 170 sq.ft. (15.8 m2/h) 210 sq.ft. (19.5 m2/h)
Airflow vs. Filter System Resistance
ID-2225 ID-2530
cfm (m3/h) in H2O Pa in H2O Pa
600 (1020) 0.06 14 0.03 8
800 (1360) 0.09 21 0.04 12
1200 (2040) 0.18 44 0.10 24
1600 (2720) 0.33 82 0.15 38
2000 (3400) 0.49 122 0.22 54
ID-2225
ID-2530
Based on ASHRAE 52.2 Air Cleaner Performance Reports from Intertek Testing
Services (ETL SEMKO), Cortland, NY
Page 3
Filter Usage

Produktspezifikationen

Marke: IQAir
Kategorie: Luchtreiniger
Modell: Perfect 16

Brauchst du Hilfe?

Wenn Sie Hilfe mit IQAir Perfect 16 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Luchtreiniger IQAir

Bedienungsanleitung Luchtreiniger

Neueste Bedienungsanleitung für -Kategorien-