Operating instructions
Electronic temperature sensor
TK7110
TK7310
TK7460
UK
80261999 / 00 03 / 2017
2
1 Safety instructions
• Please read this document prior to set-up of the unit. Ensure that the product is
suitable for your application without any restrictions.
• If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property can occur.
• Improper or non-intended use may lead to malfunctions of the unit or to un-
wanted effects in your application. That is why installation, electrical connec-
tion, set-up, operation and maintenance of the unit must only be carried out by
qualified personnel authorised by the machine operator.
• In order to guarantee the correct condition of the device for the operating time
the device must only be used in media to which the wetted parts are sufficiently
resistant (→ Technical data).
• The responsibility whether the measurement devices are suitable for the
respective application lies with the operator. The manufacturer assumes no
liability for consequences of misuse by the operator. Improper installation and
use of the devices result in a loss of the warranty claims.
2 Functions and features
The unit detects the system temperature in machines and installations.
Contents
1 Safety instructions 2
...............................................................................................
2 Functions and features 2
........................................................................................
3 Function ...............................................................................................................
3
3.1 TK7110, TK7310 (2 x NO) .............................................................................
3
3.2 TK7460 (1 x NO + 1 x NC) ............................................................................
3
4 Installation............................................................................................................4
5 Electrical connection 4
............................................................................................
6 Setting..................................................................................................................5
3
UK
3 Function
The unit generates 2 output signals. The two switch points SET1 and SET2 are
separately adjustable.
The hysteresis is fixed. It is 5 K.
3.1 TK7110, TK7310 (2 x NO)
• With rising temperature OUT1 closes / OUT2 closes when the value SET1 /
SET2 is reached.
• With falling temperature OUT1 opens / OUT2 opens, when the value SET1
minus hysteresis / SET2 minus hysteresis is reached.
SET1 HY HY
T T
OUT1
SET2
OUT2
T = Temperature; HY = Hysteresis
3.2 TK7460 (1 x NO + 1 x NC)
• With rising temperature OUT1 closes / OUT2 opens when the value SET1 /
SET2 is reached.
• With falling temperature OUT1 opens / OUT2 closes, when the value SET1
minus hysteresis / SET2 minus hysteresis is reached.
SET1
T T
OUT1
HY HY
SET2
OUT2
T = Temperature; HY = Hysteresis