Installation Instructions
Flow sensor
SF5201
SF5301
701725 / 02 05 / 2009
UK
2
Function and features
In conjunction with the VS3000 control monitor the flow sensor monitors flows in
liquids and gases.
The sensor / control monitor combination senses whether a preset flow value has
been reached (= medium flowing) or not (= medium not flowing) and provides a
switched signal.
Installation
The unit is adaptable for various process fittings (adapters to be ordered sepa-
rately as accessories).
In the case of horizontal pipes mount the unit from the side, if possible (fig. 1).•
When the unit is to be mounted at the bottom of the pipe, it should be free -
from deposits.
When the unit is to be mounted at the top of the pipe, it should be completely -
filled with the medium to be monitored.
In the case of vertical pipes mount the unit in a place where the medium flows •
upwards (fig. 2).
1 2
Components integrated in the pipes, bends, valves, reductions, etc. lead to turbu-
lence of the medium. This affects the function of the unit.
Recommendation: Adhere to the distances between sensor and sources of
interference:
5...10 x D
S
3...5 x D
S
D = pipe diameter; S = sources of interference
3
UK
1 2 3
î
í
ì
A
4
4: thread M18 x 1.5
Lubricate the nut (3) and all threads with grease to ensure the nut can be 1.
loosened and tightened several times.
Note: No grease must be applied to the sensor tip (A).
Screw the suitable adapter (2) onto the process fitting (1).2.
Insert the flow sensor into the adapter and tighten the nut (3); (max. tightening 3.
torque 50 Nm).
Insertion depth of the sensor: min. 12 mm in the pipe. When the adapters are
used which are available as accessories the correct depth is ensured.
Note: The sensor tip must not touch the pipe wall.
mounting dimension
with M12 adapter
mounting dimension
with G¼ adapter
mounting dimension
with G½ adapter
37
23,5
37
23,5
45
31


Produktspezifikationen

Marke: IFM
Kategorie: Nicht kategorisiert
Modell: SF5201

Brauchst du Hilfe?

Wenn Sie Hilfe mit IFM SF5201 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert IFM

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung für -Kategorien-