706415_UK.doc 706415/00 Page 1 of15 © ifm
efector gmbh
RM30xx ProfiNet
Brief instructions
efector400
706415_UK.doc 706415/00 Page 2 of15 © ifm
efector gmbh
Contents
The description may contain deviations from the user system, because different
manufacturers or software versions may require different installations!
The description was created based on Siemens S7 version V5.4 + SP4.
1 Installation ................................................................................................................................. 3
1.1Software ................................................................................................................................... 3
1.2Hardware ................................................................................................................................. 5
2Setting the encoder function: .................................................................................................. 6
2.1Selection of the correct encoder: ............................................................................................. 6
2.2Multiturn encoder ifm Telegram 860 (standard): ..................................................................... 7
3Setting of the measuring units (measuring range): ............................................................... 8
3.1Setting examples ..................................................................................................................... 9
3.2Setting examples with high and low word.............................................................................. 10
4 1List of variables, reset and preset ......................................................................................... 1 
4.1Display variables .................................................................................................................... 11
4.2Reset: ..................................................................................................................................... 12
4.3Preset: .................................................................................................................................... 12
5View in TiA portal .................................................................................................................... 13
5.1Installation .............................................................................................................................. 13
5.2Setting the encoder function .................................................................................................. 14
5.3List of variables, reset and preset: ......................................................................................... 14
6Other: ........................................................................................................................................ 15
Safety instructions
ï‚· Please read the product description prior to set-up of the unit. Ensure that the product is suitable for
your application without any restrictions.
ï‚· The unit complies with the relevant regulations and EC directives.
ï‚· Improper or non-intended use may lead to malfunctions of the unit or to unwanted effects in your
application.
ï‚· That is why installation, electrical connection, set-up, operation and maintenance of the unit must be
carried out by qualified personnel authorised by the machine operator.
706415_UK.doc 706415/00 Page 3 of15 © ifm
efector gmbh
1 Installation
1.1 Software
1. Download the GSD file from www.ifm.com => Article => [More information] => [Software
download] => Device master data (GSD) file
Example: RM3011 gsdml file
2. Extras => Administer GSD => Install GSDML
3. Additional Field Devices => Encoder, select ifm Encoder (see chapter 2)
Standard (optional): for controllers which support the IRT* function.
Standard, no PDEV: for controllers which do not support the IRT* function
*IRT = Isochronous Real Time (frequency rate <1ms; jitter accuracy 1µs)
706415_UK.doc 706415/00 Page 4 of15 © ifm
efector gmbh
4. Drag the encoder into the project and assign a device name and address
5. Assign device name
6. Parameter setting of the encoder (see chapter 3)
7. Set the requested variables (see chapter 4)
706415_UK.doc 706415/00 Page 5 of15 © ifm
efector gmbh
1.2 Hardware
Overview and connection
Port 1: Communication to the encoder
Power: Voltage supply
Port 2: Communication to further field devices
706415_UK.doc 706415/00 Page 6 of15 © ifm
efector gmbh
2 Setting the encoder function:
2.1 Selection of the correct encoder:
Standard (optional): for controllers which support the IRT* function.
Singleturn: 8192 signals
Multiturn: 8192 signals x 4096 revolutions
Standard, no PDEV: for controllers which do not support the IRT* function
Singleturn: 8192 signals
Multiturn: 8192 signals x 4096 revolutions
For detailed information see operating instructions
Hardware catalogue :
706415_UK.doc 706415/00 Page 8 of15 © ifm
efector gmbh
3 Setting of the measuring units (measuring range):
Simplified representation:
Measuring units per rev.
Standard: 8192
Revolutions
Standard: 4096
The resolution per revolution are the pulses which are provided for a revolution. The
revolutions are the further pulses for another entire revolution.
Example: 8192 x 2 revolutions = total: 16384
(1,2,…8192, 8193,…16383, 16384,1,2,…)
Input of the figures:
Maximum units:
8192 units x 4096 revolutions => total measuring range 33 554 432
The revolutions must never be more than 4096, therefore the number of total measuring units
is irrelevant.
Example:
7096 units x 2048 revolutions = 14 532 608 total measuring range => OK.
196 units x 4097 revolutions = 803 012 total measuring range => not OK.
Integers:
Only integer values may be entered.
Example:
8192 units x 2.5 revolutions = 20 480 total measuring range => not OK.
706415_UK.doc 706415/00 Page 10 of15 © ifm
efector gmbh
3.2 Setting examples with high and low word
For some controllers the value for the total measuring range must be converted to a high
word and a low word.
Standard setting 8192 units x 4096 revolutions:


8192 units x 4096 revolutions => total measuring range 33 554 432
total measuring range 33 554 432 in hex => 0200 0000 hex
high word 0200 hex in decimal => 512
low word 0000 hex in decimal => 0
200 units x 24 revolutions - enable scaling:
200 units x 24 revolutions => total measuring range 4800
total measuring range 4800 in hex => 0000 12C0 hex
high word 0000 hex in decimal => 0
low word 12C0 hex in decimal => 4800
200 units x 1 revolution - enable scaling:
200 units x 1 revolution => total measuring range 200
total measuring range 200 in hex => 0000 00C8 hex
high word 0000 hex in decimal => 0
low word    00C8 hex in decimal  => 200