Operating instructions
Electronic pressure sensor
for industrial applications
PT24xx
80279283 / 00 03 / 2020
UK
2
1 Preliminary note
Symbols used
â–º Instructions
→ Cross-reference
Important note
Non-compliance can result in malfunction or interference.
Information
Supplementary note.
2 Safety instructions
• The device described is a subcomponent for integration into a system.
- The manufacturer of the system is responsible for the safety of the system.
- The system manufacturer undertakes to perform a risk assessment and to
create a documentation in accordance with legal and normative requirements
to be provided to the operator and user of the system. This documentation
must contain all necessary information and safety instructions for the operator,
the user and, if applicable, for any service personnel authorised by the
manufacturer of the system.
• Read this document before setting up the product and keep it during the entire
service life.
Contents
1 Preliminary note 2
...................................................................................................
2 Safety instructions 2
...............................................................................................
3 Functions and features 3
........................................................................................
3.1 Applications ...................................................................................................
3
4 Functions .............................................................................................................
4
5 Installation............................................................................................................5
6 Electrical connection 5
............................................................................................
3
UK
• The product must be suitable for the corresponding applications and
environmental conditions without any restrictions.
• Only use the product for its intended purpose (→ Functions and features).
• Only use the product for permissible media (→ Technical data).
• If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
• The manufacturer assumes no liability or warranty for any consequences
caused by tampering with the product or incorrect use by the operator.
• Installation, electrical connection, set-up, operation and maintenance of the unit
must be carried out by qualified personnel authorised by the machine operator.
• Protect units and cables against damage.
3 Functions and features
The pressure sensor detects the system pressure and converts it into an analogue
output signal.
3.1 Applications
• Type of pressure: relative pressure
Order number Measuring range
Static pressure
resistance (max.
permissible pressure)
Bursting
pressure
psi psi psi
PT2415 0...100 250 2900
PT2424 0...200 580 6525
PT2494 -14,5...200 580 6525
PT2434 0...300 940 8700
PT2443 0...500 1450 11600
PT2402 0...1000 2500 13050
PT2432 0...3000 7250 14500
PT2400 0...5000 14500 24650
Pressure Equipment Directive (PED):
The units comply with the Pressure Equipment Directive and are designed
and manufactured for group 2 fluids in accordance with the sound
engineering practice. Use of group 1 fluids on request!