IFM NN5010 Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für IFM NN5010 (4 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 19 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/4
701674/01 08/2004
UK
Operating instructions
Inductive proximity sensors NAMUR
NN****
2
Operating instructions (safety-related part ATEX)
Information on the safe use in hazardous areas
Function and features
Use in hazardous areas according to the classification
II 1G / 2G
Group II, category 1G / 2G, apparatus for gas atmosphere).
The unit conforms to the requirements of EN50014, EN50020, EN50284 and EN60947-5-6.
EC type test certificate
DMT 02 ATEX E028
Use in hazardous areas according to the classification
II 1D
(Group II, category 1D, apparatus for dust atmosphere).
The requirements of the prEN 61241-0, IEC 61241-11 (31H/171/CDV), EN 60947-5-6
standards are met.
EC type test certificate
BVS 04 ATEX E153
Marking
II 1G EEx ia IIB T6 CE0158 Ta max = 70°C
II 1D Ex iaD 20 T 90°C
Type NN****
II 1G EEx ia IIB T5 CE0158 Ta max = 80°C
II 1D Ex iaD 20 T 100°C
Type NN****
II 2G EEx ia IIC T6 CE0158 Ta max = 70°C
II 1D Ex iaD 20 T 90°C
Type NN****
II 2G EEx ia IIC T5 CE0158 Ta max = 80°C
II 1D Ex iaD 20 T 100°C
Type NN****
Installation / Setup
Only qualified staff with a knowledge of protection classes, regulations and provisions for
apparatus in hazardous locations may install, connect and set up the units.
Check whether the classification (see „Marking“ above and marking on the unit) is suitable
for the application.
Connection only to intrinsically safe certified circuits or evaluation amplifiers which do not
exceed the following maximum values of the units:
Ui = 15 V, Ii = 50 mA, Pi = 120 mW
3
UK
The wiring is indicated in the technical data sheet or on the type label.
Permissible operating temperature of the application (referred to the maximum permissible
power of 120 mW):
-20...+70°C 1G IIB T6
-20...+80°C 1G IIB T5
-20...+70°C 2G IIC T6
-20...+80°C 2G IIC T5
-20...+70°C 1D 90°C
-20...+80°C 1D 100°C
Maximum effective internal inductance (Li) and capacitance (Ci):
The values apply to potted cables.
Article no. Cable length Internal inductance
(total) in H
Internal capacitance
(total) in nF
NN5008 --- 130 140
NN5009 2 m 130 140
NN5010 6 m 135 140
NN5011 10 m 140 140
NN5013 --- 130 140
NN5015 --- 130 140
NN****) xx m *1) *2)
Articles with cable / units with cable
NN****) For cable units with potted different cable lengths the values of the cable must be
taken into account:
1.2 H (Li) / 50 pF (Ci) per metre of potted cable.
*1) Thus the maximum effective internal inductance of the unit results in:
Li = 130 H + cable length in (m) X 1.2 H. 
*2) Thus the maximum effective internal capacitance of the unit results in:
Ci = 140 nF + cable length in (m) X 0.05 nF.