IFM AC2488 Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für IFM AC2488 (7 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 8 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/7
Operating instructions
AS-i CompactModule M8
AC2488
AC2489
7390940/04 10/2018
UK
2
1 Preliminary note
Technical data, approvals, accessories and further information at
www.ifm.com.
1.1 Safety instructions
• Read this document before setting up the product and keep it during the entire
service life.
• The product must be suitable for the corresponding applications and
environmental conditions without any restrictions.
• Only use the product for its intended purpose (→ Functions and features).
• If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
• The manufacturer assumes no liability or warranty for any consequences
caused by tampering with the product or incorrect use by the operator.
• Installation, electrical connection, set-up, operation and maintenance of the
product must be carried out by qualified personnel authorised by the machine
operator.
• The plant manufacturer is responsible for the safety of the plant in which the
device is installed.
• If the device is used in a way that is not intended by the manufacturer, the
protection supported by the device may be impaired.
• Protect units and cables against damage.
1.2 Symbols used
â–º Instructions
> Reaction, result
Important note
Non-compliance may result in malfunction or interference.
Information
Supplementary note
3
UK
2 Functions and features
• AC2488: 8 inputs CTT3 (AS-i profile S-7.A.A) / AS-interface version 3.0 /
master profile M4 / extended addressing mode: yes / maximum number of
modules per master: 62
• AC2489: 2x4 inputs (AS-i profile 2x S-0.A.E) / AS-interface version 3.0,
backwards compatible / master profile M3 or M4 / extended address mode:
yes / maximum number of modules per master: 31 (2 independent A/B slaves
per module)
3 Installation
â–º Disconnect power before installation.
â–º For installation choose a flat mounting surface.
The entire bottom of the module must lie flat on the mounting surface.
â–º Fix the module onto the mounting surface using M4 screws and washers.
4 Electrical connection
The unit must be connected by a qualified electrician.
The national and international regulations for the installation of electrical equipment
must be adhered to.
â–º Disconnect the installation from power and connect the unit.
To ensure the protection rating:
â–º Connect the plugs of the sensors to the M8 sockets.
â–º Tighten firmly, recommended tightening torque 0.3...0.5 Nm.
â–º Cover the unused sockets with the enclosed protective caps.
â–º Tighten firmly, recommended tightening torque 0.3...0.5 Nm.


Produktspezifikationen

Marke: IFM
Kategorie: Nicht kategorisiert
Modell: AC2488

Brauchst du Hilfe?

Wenn Sie Hilfe mit IFM AC2488 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert IFM

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung für -Kategorien-