Installation instructions
AS-i Controllere
AC1318
AC1324
7390779 / 01 05 / 2011
UK
1 2345
2
1 Functions and features
• The controllere (AC1318 / AC1324 ) integrates one or two AS-i masters, both
according to the AS-i version 3.0, a mini controller and a DeviceNet interface.
• It controls the exchange of data to the sensor / actuator level
• processes the peripheral data in the integrated processor (signal preprocess-
ing),
• works as stand-alone controller with exchange of data to the PC (visualisation),
• communicates with the higher control level (in the gateway mode).
2 Programming interface RS232C
• Baud rate 4,800 to 115,200 baud
• Max. distance between controllere and PC: 20 m
• Potential separation from the controllere power supply
• Programming cable E70320 for connection to PC required
Contents
1 Functions and features 2 ........................................................................................
2 Programming interface RS232C 2 ..........................................................................
3 DeviceNet interface 3 .............................................................................................
4 Installation............................................................................................................3
5 Electrical connection 3 ............................................................................................
6 Operating and display elements 4 ..........................................................................
6.1 LED indicators and pin connection 5 ................................................................
6.2 Contrast setting 6 .............................................................................................
7 Operation .............................................................................................................6
7.1 Menu overview 6 ..............................................................................................
7.2 Menu navigation 7 ............................................................................................
3
UK
3 DeviceNet interface
• Baud rate 125 k, 250 k and 500 kbit / s
• Max. distance between controllere and host: depending on the baud rate
• Potential separation from the controllere power supply
• Up to 64 controllers connected in parallel
• Pin connection:
Pin 1: V-; Pin 2: CAN_L; Pin 3: Shield; Pin 4: CAN_H; Pin 5: V+
4 Installation
Fix the controllere onto a 35 mm DIN rail which has an electrically safe ground
connection. The protection rating of the unit is IP 20, therefore it should be
mounted in a protected location (e. g. control cabinet).
Ensure a condensation-free environment. Avoid excessive dust, vibration
and shock. The air circulation through the vents must not be impeded.
Avoid installation in direct vicinity of frequency inverters.
5 Electrical connection
Disconnect the installation from power. Connect the unit as indicated on the
terminals. Never connect the minus potentials to each other or the minus
potentials to the FE connection. Ensure an electrically save ground connec-
tion between AS-i controllere (terminal FE) and ground of the unit.
Disconnect the power supply before connecting the controllere.
To operate an AS-i system a special AS-i power supply is required. Connection is
made to the terminals AS-i + and AS-i -.
The AS-i system is operated ungrounded. AS-i + and AS-i - are to be
symmetrical to the ground potential of the installation.
Ensure a low-resistance connection of the symmetry point of the AS-i
power supply (terminal "shield") to the ground of the installation.
Supply the controllere with an additional 24 V DC voltage (20...30V PELV). The
connection is made to the terminals +24 V and 0 V.