Hager WGCXT1RJ6KB Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Hager WGCXT1RJ6KB (4 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 17 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/4
www.hager.com
Safety instructions
Electrical equipment must only be installed and assembled by a qualied
electrician in accordance with the relevant installation standards, regulations,
directives and safety and accident prevention directives of the country.
Failure to comply with these installation instructions may result in damage to
the device, re or other hazards.
Function
The RJ45 outlets are used for data transmission in local area networks. The RJ11
outlets are designed for telephone and data applications. Each jack is equipped with a
dust protection slider.
Correct use
- For the ush-mounted installation in standard wall boxes
(recommended wall box depth ≥ 35 mm).
- Only suitable for use in indoor areas with no drip and no spray water.
Technical data
RJ45 outlets
Voltage proof (contact-to-contact): 1000 V DC or AC peak
Current rating: 0.75 A
Insulation resistance: 500 MΩ at 100 V DC
Signal contact resistance: 20 mΩ
Type of connection: IDC terminals
Design: according to IEC 60603-7
Colour code A and B: according to TIA/EIA 568-B.2
RJ45 Cat.5e modules
Transmission bandwidth: max. 100 MHz
Conductor (solid): 0.51 ... 0.64 mm (AWG 24-22)Ø
Cat.5e, unshielded (UTP): according to ISO/IEC 11801
RJ45 outlet Cat.5e / Cat.6 / Cat.6A
RJ11 outlet / RJ11 + RJ45 outlet
Hager Muse / Hager Inspire
Installation manual
2
RJ45 Cat.6 modules
Transmission bandwidth: max. 250 MHz
Conductor (solid): 0.51 ... 0.64 mm (AWG 24-22)Ø
Cat.6, unshielded (UTP): according to ISO/IEC 11801, 2nd edition
RJ45 Cat.6A modules
Transmission bandwidth: max. 500 MHz
Conductor (solid): 0.41 ... 0.64 mm (AWG 26-22)Ø
Cat.6A, unshielded (UTP): according to ISO/IEC 11801, edition 2.2
RJ11 outlet
Compliance: YD/T 577
Information for electricians
Installation and electrical connection
Preparing the device for installation
(for example “RJ11 + RJ45 outlet”)
Notches
Frame
1A Hager Muse
Frame
Notches
Hager Inspire1B
Cover
plate
Carefully loosen the frame on the notches with a flat-blade screwdriver. Lift up and
remove the frame ( ).1A/1B
Hager Inspire: 1BRemove the cover plate also with a flat-blade screwdriver ( ).
3
Connecting the RJ45 data module
Remove the cover plate of the data module with a flat-blade screwdriver.
2A
UTP
30 mm
Strip 30 mm of cable jacket ( ).2A
Position and terminate first pair according to colour code A or B:
RJ45 pin assignment TIA/EIA 568B TIA/EIA 568A
1white/orange white/green
2 orange green
3 white/green white/orange
4 blue blue
5white/blue white/blue
6green orange
7 white/brown white/brown
8brown brown
As with the first pair position and terminate each subsequent pair one at a time until
termination is complete.
Fix the cover plate back to the module.
Connecting the RJ11 telephone module
3A 10 mm
Strip 10 mm of cable jacket ( ).3A
Position first pair according to colour code:
RJ11 pin assignment
2blue/white
3 white/blue
4white/red
5red/white
Fix the cover plate back to the module.


Produktspezifikationen

Marke: Hager
Kategorie: Nicht kategorisiert
Modell: WGCXT1RJ6KB

Brauchst du Hilfe?

Wenn Sie Hilfe mit Hager WGCXT1RJ6KB benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert Hager

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung für -Kategorien-