Hager VMLF908CUSPD Bedienungsanleitung

Hager Nicht kategorisiert VMLF908CUSPD

Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Hager VMLF908CUSPD (3 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 3 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/3
Design 10 Flush Consumer Unit
Instructions/Data Sheet
This Consumer Unit and Hager devices conform with the following standards:
Consumer Unit: BS EN 61439-3 including Annex ZB.
Switch-disconnectors: BS EN 60947-3.
Residual Current Circuit Breaker (RCCB): BS EN 61008-1
Residual current operated circuit breaker with integral overload (RCBO): BS EN 61009-1
Miniature Circuit Breaker (MCB): BS EN 60898-1
Passed hot-wire fire test for “non-combustible enclosure” in context of Regulation 421.1.201
indent (i) in BS 7671.
Use circuit as
normal
YES
YES
YES
RCCB
NO
NO
NO
NO
NO YES
YES
Does device
stay ON?
Does device
stay ON?
Does device
stay ON?
Does device
supply socket
outlets
Call an
electrician
Unplug all
appliances from
circuit and reset
device / replace fuse*
Plug in & switch on
appliances one at a time
until device trips / blows,
identifying faulty appliance
Unplug faulty
appliance until
repaired. Reset device.
Other appliance may
be used
Try & reset device once
MCB / Fuse
tripped
MCB
or RCBO
START
What device
is it?
Try & reset device once
Use circuit as
normal
Turn OFF
all MCB / fuse*
devices
Call an
electrician
Reset RCCB
Does device
stay ON?
Turn ON MCB / fuse*
devices one at a time
until RCCB trups again,
identifying faulty circuit
T
T
T
ON ON ON
Blank RCCB RCBO (two module) MCB RCBO Switch
(one module)
A
B
D
C
E
F
Size 4 Size 5 Size 6 Size 7
A 282 282 282 282
B 335 407 443 515
C 32 32 32 32
D 298 370 406 478
E 252 252 252 252
F 72 72 72 72
2.5mm
2.5mm
Installation Instructions:
All product(s) must be installed by a suitably competent electrician
Giving consideration to their intended use and in accordance with the current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work Act shall be complied with.
Only equipment and arrangements specied in Hager’s technical documentation / catalogue shall be used.
Install in the horizontal plane only.
Important notice:
To prevent potential overheating from loose connections the installer shall check connections are tight to the torque levels stated in these instructions
prior to energizing this board. This check should include factory made connections which may have loosened in transit.
Guidance Notes:
The total load must not exceed the rating of the incoming device or the assigned assembly rating (InA) whichever is the lower. Each neutral and earth
connection must correspond numerically to its outgoing way. Additional blanks (ref. JK01B) are available to cover spare ways.
A pack is provided to label this consumer unit, please consult us for spares or replacements.
Operating Instruction leaet is provided overleaf. This leaet should be left for the end user.
Single conductors below 1.5mm² need to be doubled back in the terminal bar.
Consumer Units incorporating RCDs in TT systems should incorporate an S type (time Delayed) RCCB, e.g. 100 mA s-type RCCB . Alternatively a main
switch with RCBO protection on all outgoing circuits should be used.
Precautions need to be taken to prevent faults to earth on the supply side of the RCD (as per BS7671 regulation 531.4.1)
For guidance when making connections in a consumer unit electrical safety rst /BEAMA document
“Guidance for installers when making connections in consumer units” is available from
hager.co.uk/63026.htm
Cable Access:
Cable access into the metal consumer unit must maintain the integrity of the non-combustable
consumer unit so far as reasonably practicable. This can generally be achieved by the installer
ensuring that cable access holes they make in the enclosure do not to leave gaps greater than:
¡ 2.5 mm for all other surfaces of the enclosure that are accessible after installation.
For rear cable access, the minimum number of knockout(s) shall be removed.
Tests on hager consumer units have indicated that there is no specic need for external re rated
cable glands or intumescent sealing in addition to the guidance below, with respect to achieving a non-combustible enclosure.
However this does not preclude the designer/installer from using re rated cable glands or external intumescent sealing should
they consider necessary. Internal intumescent pads shall not be used.
Fitting Hager MCBs and RCBOs:
Only equipment and arrangements specied in Hager’s
technical documentation / catalogue shall be used.
Isolate the electrical supply from the consumer unit.
1. Isolate the electrical supply from the consumer unit.
2. Remove the front cover, by loosening the two captive
screws.
3. Fully slacken the lower terminal of the device.
4. Fully open the bottom device clip (g 1.)
5. Locate the device onto the din rail, and busbar. Ensure that the busbar
tooth is within the device terminal cage.
6. Close the bottom device clip.
7. While holding the device rmly onto the busbar, fully tighten the lower
terminal screw.
8. After tting all outgoing devices and connecting all outgoing cables,
please check the tightness of all cable connections. This should
include all factory made connections, which may have loosened during
installation or transit.
g 1.
GB
1 ZD0828 - Issue 4
ZD0828ZD0828
4 ZD0828 - Issue 4
Torque Settings
Pz No. (mm)
Cables >1.5mm2
Tightening torque (N.m)
Cables ≤1.5mm2
Tightening torque (N.m)
Cable Stripping
(mm)
Single Cable Multi Cables Single Cable Multi Cable
Consumer unit terminals
Earth and neutral terminal bars 2 6.5 2 2 1.5 1.5 10
Isolation
SB switch disconnectors 2 6.5 3.6 3.6 3.6 3.6 15
Circuit protection
MTN MCB 2 6.5 2.8 2.8 2.8 2.8 13
NBN/NCN/NDN MCB 2 6.5 2.8 2.8 2.8 2.8 13
RCBO 2 5.5 2.1 2.1 2.1 2.1 13
RCCB 2 5.5 2.8 2.8 2.8 2.8 13
For boards with Surge Protection fitted (References ending in SPD)
GREEN/CLEAR RED
Where surge protective devices (SPDs) or other equipment are likely to
influence the verification test, or be damaged, such equipment shall be
disconnected before carrying out the insulation resistance test.
Warranty
This distribution board is offered with a 24 month warranty against defective material or manufacture. If a warranty claim is necessary, please
call the technical support number given at the bottom of the page and we will be pleased to help.
For dimensional information and weights please consult the Hager catalogue.
Hager Technical Help Line: 01952 675 689
Hager Technical Fax: 01952 675 557
Website: www.hager.co.uk
E-mail us: info@hager.co.uk
Twitter: @hageruk
After wiring installation, offer up cover &
door assembly, secure with the captive
screws.
Push internal chassis
until it is ush with the
wall surface. Tighten p2-x4
M5 wing nut to secure
internal chassis
Remove internal chassis.
(No requirement to disconnect factory cable connections)
Remove required KO’s before xing to stud wall &
use provided grommet strip or grommet accessory
VMGROM for cable protection
Back box xing points
Fixing height 1320mm Âą 50mm from back box bottom
face to the nished oor (Part M)
Box must be level at this stage
Top & bottom edge to be ush with front of stud work, with
left and right edges protruding slightly from stud work
Trim excess plaster from around
the box, loosely t p2-x4 M5 wing
nut to back box
1st x
complete
2nd x
complete
Offer up internal chassis, loacting chassis on
the metal studs
Accessories
Open Hole Grommet 38mm (10
Pack)
VMGROM
Cable Protector Plate VM02CE
Label Pack VAP00
1 Module Busbar Blank (25 pack) JK01B
Pozi n°8 or n°10
Box dimensions on page 4
1
3
5
7
2
4
6
8
The installer must ensure that all cables routed under the
chassis dinrail have adequate clearance and are NOT
subjected to any stress or pressure.
3 ZD0828 - Issue 42 ZD0828 - Issue 4
ZD0828 ZD0828
Interface characteristics
Rated & operational voltage (Un / Ue)
230V a.c. 50Hz
Rated insulation voltage (Ui)
320V a.c. 50Hz
Rated impulse withstand voltage (Uimp)
4kV
Rated current of the Assembly (InA)
100A
Note: Dependent upon rating of main incoming device
Rated current of an Outgoing circuit (Inc)
Circuit next to an RCCB: MCB & RCBO 6-50A
(marked rated current on device)
All other circuits MCB 6A - 63A (marked rated current on device)
All other circuits RCBO 6A - 50A (marked rated current on device)
Rated current of outgoing unit (Inc)
RCCB 80A (marked rated current on device)
Rated conditional short-circuit current of the ASSEMBLY (Icc)
Annex ZB: 16 kA rms at 250V, power factor 0.6 with equipment and arrangements specied in Hager’s technical documentation /
catalogue.
Protection against electric shock
Consumer unit shall be installed in an electrical system conforming to the current edition of IEC 60364 / BS 7671
Rated diversity factor (RDF) / Values of assumed loading
1way = 1.0
2way – 3way = 0.8
4way – 5way = 0.7
6way – 9way = 0.6
10way and above = 0.5
Note: RDF only applies to continuously and simultaneously loaded
circuits.
In principle, this means adjacent circuit-breakers having a load
‘on’ time exceeding 30 minutes or where a load not exceeding 30
minutes has an ‘off’ time less than the ‘on’ time, will need to have
the rated diversity factor applied as indicated.
Rated frequency (fn)
50 Hz
Pollution degree
2
Types of system earthing for which the ASSEMBLY is designed
TNC-S, TN-S when installed in an electrical installation complying with BS 7671
Hager recommends for TT systems a 100A type S time delayed RCCB or a main switch with RCBO protection only on all outgoing circuits.
Indoor use only
Stationary ASSEMBLY
Degree of protection
IP2XC with Door Open / closed and full compliment of outgoing devices and or blanks tted.
Intended use
Intended for use in domestic (residential) or similar premises.
Electromagnetic compatibility (EMC) classication
EMC Environment B
External design
VM: Wall-mounted, enclosed assembly.
Mechanical impact protection
IK 05
The type of construction
Fixed parts
Type A DBO (Distribution board for use by ordinary persons)


Produktspezifikationen

Marke: Hager
Kategorie: Nicht kategorisiert
Modell: VMLF908CUSPD

Brauchst du Hilfe?

Wenn Sie Hilfe mit Hager VMLF908CUSPD benĂśtigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert Hager

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung fĂźr -Kategorien-