Hager TXA624D Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Hager TXA624D (2 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 6 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/2
6LE002722A
TYA624B
Output 4gang shutter 24 V
TYA624D
Output 4gang shutter/blind
24 V
TXA624D
Output 4gang shutter/blind
24 V
z
6LE002722A1
Safety instructions
Electrical equipment may only be installed and
assembled by a qualiîš¿ed electrician in accor-
dance with the relevant installation standards,
guidelines, regulations, directives, safety and
accident prevention regulations of the country.
Failure to comply with these installation in-
structions may result in damage to the device,
îš¿re or other hazards.
Hazard due to electric shock. Disconnect be-
fore working on the device or load. Take into
account all circuit breakers that supply dan-
gerous voltages to the device or load.
Connect one motor per output only. If several
motors are connected, motors or device might
be destroyed.
Use drives with mechanical or electrical îš¿nal
position switches only. Check îš¿nal position
switches for correct adjustment. Observe mo-
tor manufacturer's data. The device can be da-
maged.
Risk of injury. Use the device to control blind
and shutter drives or awnings only. Do not
switch any other loads.
Observe the motor manufacturer's data regar-
ding change-over time and max. switch-on time
(ED).
These instructions are an integral component
of the product and must be retained by the end
user.
Design and layout of the device
C2
C1
C4C4
C3C3
30V DC
3 5
+
7 9
4 6 8 10
-
-+
1
2
C1 C3
C2 C4
auto
(1)
(2) (3)
(4) (5)
(6)
(3)
Figure 1: device overview
(1) Slide switch /auto
(2) KNX bus connection terminal
(3) Connections of loads
(4) Labelling îš¿eld with cover
(5) Illuminated programming button
(6) Operation button for manual operation per
output with status LED
Function
System information
This device is a product of KNX system and corre-
sponds to the KNX guidelines. Detailed specialised
knowledge obtained from KNX training courses is
required for comprehension. The planning, installa-
tion and commissioning of the device is carried out
with the help of KNX-certiîš¿ed software.
Systemlink commissioning
The function of the device is software-dependent.
The software is to be taken from the product
database. You can îš¿nd the latest version of the
product database, technical descriptions as well as
conversion and additional support programmes on
our website.
Easylink commissioning
The function of the device is conîš¿guration-depen-
dent. The conîš¿guration can also be done using
devices developed specially for simple setting and
start-up.
This type of conîš¿guration is only possible with
devices of the easylink system. Easylink stands for
easy, visually supported start-up. Preconîš¿gured
standard functions are assigned to the in/outputs
by means of a service module.
Functional description
The devices are used to control motor-operated
building îš¿ttings such as shutters and blinds via the
KNX bus. The devices have 4 outputs from which
each output can be activated independently.
Correct use
- Switching of electrically driven 24 V motors for
blinds, shutters, awnings and similar hangings.
- Mounting on DIN rail according to
DIN EN 60715 in the distribution box.
Product characteristics
- independent outputs, activation via KNX bus.
- Status display of the outputs on the device.
- manual activation of the outputs on the device
possible, building site operation.
- Position can be started directly.
- 3 Alarms.
- Scene function.
- Forced position by higher-level controller.
Blind actuators only
- Slat position directly controllable.
Operation
Manual operation switch on/off
Bus voltage supply is present.
zPush switch (1) to position .
Manual operation is switched on, the outputs
can be controlled using the operation buttons
(6) independently of each other.
During manual operation, the controller is deac-
tivated via the KNX bus.
Systemlink commissioning: depending on the
programming, the manual operation is activated
permanently or for a time period conîš¿gured via
the application software.
If the manual operation is blocked via the appli-
cation software, no activation takes place.
Or
zMove switch (1) to position .auto
The manual operation is switched off. Opera-
tion takes place solely via the KNX bus. The
output takes the position predeîš¿ned by the bus
controller.
Operating outputs in manual operation
Operation takes place per output by brief repeated
presses on the operation button (6) (table 1).
Status Behaviour when
briey pressing the
button
Manual operation is
switched on, initial
operation of an output.
Move DOWN, re-
gardless of output
status.
Movement operation
active, status LED of the
button (6) lights up.
Movement operation
stops.
Output is in standby,
status LED of the button
(6) is off.
Movement operation
in opposite direction of
the last movement.
Table 1: manual operation
Information for electricians
Installation and electrical connection
DANGER!
Touching live parts can result in an
electric shock!
An electric shock can be lethal!
Disconnect the connecting cables
before working on the device and
cover all live parts in the area!
ç
CAUTION!
Risk of destruction if parallel connec-
tion of several motors on one output!
Final position switches could fuse
together. Motors, hangings and the
device may be destroyed!
Only connect one motor per
output!
ç
P
P
z
Bn,.:
M
`
Installing the appliance
Observe temperature range. Provide sufîš¿cient
cooling.
zMount device onto DIN rail in accordance with
DIN EN 60715.
Connect device
+
-
C2
C1
C4C4
C3C3
30V DC
3 5
+
7 9
4 6 8 10
-
-+
1
2
C1 C3
C2 C4
24 V DC max.
auto
24 V max.s
Fig 2: device connection
Fig 3: installation/deinstallation
with plug-in terminals
Connect bus cable via connecting terminal (2).
zConnect bus voltage.
zConnect motors.
P
Start-up
Systemlink: loading physical address and
application software
The switch for manual operation (1) is in position
auto.
zSwitch on bus voltage.
zPress programming button (5).
The button lights up.
If the button does not light up, no bus voltage
is present.
zLoad the physical address into the device.
Status LED of the button goes out.
zLoad application software.
zNote down the physical address on the labelling
îš¿eld (4).
Easylink
Information on the system conîš¿guration can be
taken from the extensive description of the service
module easylink.
Starting up the device
zSwitch the operating voltage on.
Determine operation time and slat adjusting
time
In blind/roller shutter operation, the operation time
for positioning the sunshade is important. The posi-
tion is calculated based on the operation time. The
slat adjusting time for slat blinds, determined by
the design, is part of the total operation time. The
opening angle of the slats is therefore set as ope-
ration time between opened and closed position.
The operation time for UP is normally longer
than the operation time for DOWN and must be
measured separately if necessary.
zMeasure UP and DOWN operation time of the
hanging.
zMeasure slat adjusting time between OPEN
and CLOSED.
zEnter measured values into the parameter
setting – ... or .running time slat step time
Functional test
The functionality of the outputs is displayed via the
status LED of the operation button (6).
Appendix
Technical data
Supply voltage KNX 21-32V SELVs
Own consumption on the KNX bus:
- typical 5,2 mA (TYA..)
5 mA (TXA..)
- in standby 4,5 mA (TYA..)
3 mA (TXA..)
Breaking capacity µ 6A DC1 24V s
Energy dissipation 2 W
Switching current smax. 6 A
Operating altitude max. 2000 m
Degree of contamination 2
Surge voltage 4 kV
Degree of protection of housing IP20
P
P
Degree of protection of housing
under front panel IP30
Impact protection IK 04
Overvoltage class III
Operating temperature -5°C…+45°C
Storage/transport temperature -20°C … +70°C
Maximum switching cycle rate
at full load 20 switching cycle/minute
Connection capacity 0.75 mm²…2.5 mm²
Dimension 4 TE, 4 x 17.5 mm
Communication media KNX TP 1
Conîš¿guration mode S-Mode, easy link
controller (TXA624D)
Troubleshooting
Manual operation not possible
Cause 1: switch (1) not moved to .
Move switch to .
Cause 2: manual operation has not been enabled
(Systemlink).
Enable manual operation via application soft-
ware.
Bus operation is not possible
Cause 1: bus voltage is not present.
Check bus connection terminal for correct
polarity.
Check bus voltage by briey pressing the pro-
gramming button (5), red LED lights up if bus
voltage is present.
Cause 2: manual operation is active. Switch (1) is
in position .
Move switch (1) to position .auto
Shutters/blinds do not move to the îš¿nal
position
Cause: Operation time for the shutters/blinds set
incorrectly.
Check operation times. Measure again and
reprogram if necessary.
Correct Disposal of This product
(Waste Electrical & Electronic
Equipment).
(Applicable in the European Union and other European
countries with separate collection systems).
This marking shown on the product or its literature
indicates that it hould not be disposed with other
household wasted at the end of its working life. To prevent
possible harm to the environment or human health from
uncontrolled waste disposal, please separate this from
other types of wastes and recycle it responsibly to
promote the sustainable reuse of material resources.
Household users should contact either the retailer where
they purchased this product, or their local government
oce, for details of where and how they can take this item
for environmentally safe recycling.
Business users should contact their supplier and check
the terms and conditions of the purchase contract. This
product should not be mixed with other commercial
wastes of disposal.
Usable in all Europe
Ã¥
and in Switzerland
2 Hager 12.16 - 6LE002722AHager Controls S.A.S., 33 rue Saint-Nicolas, B.P. 10140, 67703 SAVERNE CEDEX, France - www.hager.com


Produktspezifikationen

Marke: Hager
Kategorie: Nicht kategorisiert
Modell: TXA624D

Brauchst du Hilfe?

Wenn Sie Hilfe mit Hager TXA624D benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert Hager

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung für -Kategorien-