5.50 General Catalogue • Modular Devices • Technical
Transformers
Safety Transformers
These transformers are designed to ensure personal safety, their
primary winding are electrically separated from their secondary
windings and they are intended to feed separated extra low voltage
circuits U 50V. A thermal overload, in the primary windings, ensures
that if a short circuit or an overload occurs in the output it will not
damage the device.
Bell Transformers
Bell transformers are similar to safety transformers but the
secondary voltages do not exceed 24 volts, they are also similarly
protected against short circuits and overloads, by thermal protection
in the primary winding.
Compliance with the Standards
The bell and safety transformers conform with BS EN 61558.
Where transformers are to be used in a common enclosure with other
devices heat dissipation inserts LZ060 should be used.
Recommendation of Use
• To link only one secondary (never link both simultaneously)
• Do not connect (in series or in parallel) secondaries of different
transformers
24 V230 V
U1
U2
U3
Technical Specification
ST301 ST303 ST305 ST312 ST313 ST314 ST315
Nominal Power 4VA 8VA 16VA 25VA 16VA 40VA 63VA
Designation Bell Bell Bell Safety Safety Safety Safety
Primary Voltage 230 Volts 230 Volts 230 Volts 230 Volts 230 Volts 230 Volts 230 Volts
Secondary Voltage U2 8 Volts 8 Volts 8 Volts 12 Volts 12 Volts 12 Volts 12 Volts
In = 0.5A In =1A In = 2A In = 2.08A In = 1.33A In = 3.33A In = 5.25A
U3 12 Volts 12 Volts 12 Volts 24 Volts 24 Volts 24 Volts 24 Volts
In = 0.33A In = 0.67A In = 1.33A In = 1.04A In = 0.67A In = 1.67A In = 2.63A
No Load U2 12 Volts 15 Volts 12 Volts 14 Volts 16 Volts 14 Volts 14 Volts
Secondary Voltage U3 18 Volts 22 Volts 19 Volts 29 Volts 30 Volts 27Volts 27 Volts
Galvanic Insulation 4kV 4kV 4kV 4kV 4kV 4kV 4kV
Max Functional Temperature 35ºC 35ºC 35ºC 35ºC 35ºC 35ºC 35ºC
Overload and S/C Protection Thermal cut out in the primary winding
Insulation Class HHBBBBH