Hager HFD316 Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Hager HFD316 (2 Seiten) in der Kategorie Stromkreisunterbrecher. Dieser Bedienungsanleitung war für 37 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/2
HFD316
HFD316
Fuse comb. switch 3P - 160 A / T00
Technical characteristics
Architecture
Type of order Door coupling rotary drive
Number of poles 3 P
Type of pole 3 P
Main electrical features
Rated operational voltage Ue 380 / 415 V
Rated current 160 A
Voltage
Rated insulation voltage 750 V
Electric current
Short-circuit current with gI-gG fuses 50 kA
Rating current of fuse cartridge
6 / 10 / 16 / 20 / 25 / 32 / 40 / 50 / 63 / 80 / 100 /
125 / 160 A
Fuse
Fuse Size NH00
Dimensions
Height of installed product 162 mm
Width of installed product 148 mm
Power
Total power loss under IN 64.8 W
Power loss per pole at In 21.6 W
Contact rating with 400 V in AC1 105 kW
Cover, door
Interlockable Yes
Materials
Toggle colour Grey
Installation, mounting
Suitable for busbar mounting No
Suitable for front mounting center No
Suitable for front mounting No
Suitable for ground mounting Yes
Connection
Subject to technical modifications
Type of connection with screw
Cable
Length of conductors used for the heating
test (m) according to product standard 2 m
Conductor cross-section used for heating
test(mm²) according to product standard 70 mm²
Equipment
Number of auxiliary contacts as normally
closed contact 0
Number of auxiliary contacts as normally
open contact 0
Number of auxiliary contacts as change-
over contact 0
Can be accessorized Yes
Standards
Standard text IEC 60947-3
European directive RoHs voluntary compliance
European directive WEEE concerned
Safety
Protection index IP IP00
temperatur
Ambient air temperature during heating test
according to the product standard 24 °C
Max. admissible temperature on accessible
parts (intended to be touched) 80 °C
Max. admissible temperature on accessible
parts (manual operating means) 65 °C
Max. admissible temperature on access.
parts (not touched for normal operation) 90 °C
Max. admissible temperature on terminals 110 °C
Temp.-rise limits for access. parts (toggle)
according to product standard 25 K
Temp.-rise limits for access. parts (not
touched) according to product standard 50 K
Temp.rise limits for access. parts (to be
touched) according to product standard 40 K
Temperature-rise limits for terminals
according to the product standard 70 K
Temperature-rise measured on accessible
parts at In (manual operating means) 25 K
Temperature-rise measured on access.
parts at In (not touched normal operation) 50 K
Temperature-rise measured on accessible
parts at In (intended to be touched) 40 K
Temperature-rise measured on terminals at
In 70 K
Identification
meta_keyword
Switch disconnector with fuse;Load disconnecting
switch with fuse;Main switch;Switch;Disconnector
Subject to technical modifications


Produktspezifikationen

Marke: Hager
Kategorie: Stromkreisunterbrecher
Modell: HFD316
Produktfarbe: Grau
AC Eingangsspannung: 380 - 415 V
Anzahl: 1
Nachhaltigkeitszertifikate: RoHS