Fujitsu Airstage AJH144LELBH Bedienungsanleitung
Fujitsu
Klimaanlage
Airstage AJH144LELBH
Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Fujitsu Airstage AJH144LELBH (20 Seiten) in der Kategorie Klimaanlage. Dieser Bedienungsanleitung war für 11 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet
Seite 1/20

EnglishDeutschFrançaisEspañolItalianoEλληvIkάPortuguêsРусскийTürkçe
INSTALLATION MANUAL
INSTALLATIONSANLEITUNG
MANUEL D'INSTALLATION
MANUAL DE INSTALACIÓN
MANUALE D'INSTALLAZIONE
ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
MANUAL DE INSTALAÇÃO
РУКОВОДСТВО ПО УСТАНОВКЕ
KURULUM KILAVUZU
OUTDOOR UNIT
AUSSENGERÄT
UNITÉ EXTÉRIEURE
UNIDAD EXTERIOR
UNITÀ ESTERNA
ΕΞΩΤΕΡΙΚΉ ΜΟΝΆΔΑ
UNIDADE EXTERIOR
ВНЕШНИЙ МОДУЛЬ
DIŞ ÜNİTE
For authorized service personnel only.
Nur für autorisiertes Fachpersonal.
Pour le personnel de service agrée uniquement.
Únicamente para personal de servicio autorizado.
A uso esclusivo del personale tecnico autorizzato.
Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό.
Somente para o pessoal do serviço técnico autorizado.
Только для .авторизованного обслуживающего персонала
Yalnızca yetkili servis personeli için.
PART No. 9380545347
AJ*072LELBH
AJ*090LELBH
AJ*108LELBH
AJ*126LELBH
AJ*144LELBH
AJ*162LELBH
[Original instructions]

En-1
1. SAFETY PRECAUTIONS
• Be sure to read this Installation manual thoroughly before installation.
• The warnings and precautions indicated in this Installation manual contain important
information pertaining to your safety. Be sure to observe them.
• After installing the unit, perform a test run to make sure the unit operates normally. Then,
explain to the customer how to operate and maintain the unit.
• Please pass this Installation manual together with the Operating manual to the customer.
Please ask the customer to keep the Operating manual and Installation manual at hand
for future reference during the moving or repair of the main unit.
WARNING This mark indicates procedures which, if improperly per-
formed, might lead to the death or serious injury of the user.
Consult the retail store or professional technicians to install the main unit according to
the Installation manual.
Improper installation will cause serious accidents such as refrigerant leakage, water
leakage, electric shock, and fire.
Manufacturer's guarantee will be invalid when instructions in the Installation manual are
ignored during installation.
For installation purposes, be sure to use the parts supplied by the manufacturer or other
prescribed parts.
Using non-specified parts will cause serious accidents such as falling unit, refrigerant
leakage, water leakage, electric shock, and fire.
To install a unit that uses the R410A refrigerant, use dedicated tools and piping materi-
als that have been manufactured specifically for R410A use.
Because the pressure of the R410A refrigerant is approximately 1.6 times higher than
the R22, failure to use dedicated piping material or improper installation can cause
rupture or injury.
It will also cause serious accidents such as refrigerant leakage, water leakage, electric
shock, and fire.
Do not use this equipment with air or any other unspecified refrigerant in the refrigerant
lines.
Excess pressure can cause a rupture.
Be sure to install the unit as prescribed, so that it can withstand earthquakes and
typhoons or other strong winds.
Improper installation can cause the unit to topple or fall, or other accidents.
Ensure that the outdoor unit is securely installed at a place that can withstand the
weight of the unit.
Improper installation will cause injuries caused by falling unit.
If there is a refrigerant leakage, make sure that it does not exceed the concentration
limit.
If a refrigerant leakage exceeds the concentration limit, it can lead to accidents such as
oxygen starvation.
If a refrigerant leakage occurs during operation, immediately vacate the premises and
thoroughly ventilate the area.
If the refrigerant is exposed to fire, it will create a hazardous gas.
Electrical work must be performed in accordance with this Installation manual by a
person certified under the national or regional regulations. Be sure to use a dedicated
circuit for the unit.
An insufficient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or fire.
For wiring, use the prescribed type of cables, connect them securely, making sure that
there are no external forces of the cables applied to the terminal connections.
Improperly connected or secured cables can cause serious accidents such as overheat-
ing the terminals, electric shock, or fire.
Securely install the electrical box cover on the unit.
An improperly installed electrical box cover can cause serious accidents such as electric
shock or fire through exposure to dust or water.
Do not turn ON the power until all work has been completed.
Turning ON the power before the work is completed can cause serious accidents such
as electric shock or fire.
After the installation, make sure there is no refrigerant leakage.
If the refrigerant leaks into the room and becomes exposed to a source of fire such as a
fan heater, stove, or burner, it will create a hazardous gas.
Use a wall hole pipe. Otherwise, it may cause a short circuit.
Do not place the outdoor unit near the handrail of the balcony.
Children may climb onto the outdoor unit, lean over the handrail and fall over.
Use only a specified power cable. Poor connection, poor insulation, and exceeding the
allowable current will lead to electric shock and fire.
Attach the connecting cables securely to the terminal. Or secure it firmly with a “wiring
suppressor”.
Loose connection will lead to malfunction, electric shock, and fire.
Be sure to install an earth leakage breaker that can shut down all power supplies within
the system at the same time.
If you do not install a breaker, it may cause electric shock and fire.
During installation, make sure that the refrigerant pipe is attached firmly before you run
the compressor.
Do not operate the compressor under the condition of refrigerant piping not attached
properly with 2-way or 3-way valve open. This may cause abnormal pressure in the
refrigeration cycle that leads to rupture and even injury.
During the pump-down operation, make sure that the compressor is turned off be-
fore you remove the refrigerant piping. Do not remove the connection pipe while the
compressor is in operation with 2-way or 3-way valve open. This may cause abnormal
pressure in the refrigeration cycle that leads to breakage and even injury.
INSTALLATION MANUAL
VRF system outdoor unit
PART No. 9380545347
Contents
1. SAFETY PRECAUTIONS …………………………………………………………………1
2. ABOUT THIS PRODUCT ………………………………………………………………… 2
2.1. Precautions for using R410A refrigerant …………………………………………2
2.2. Special tools for R410A ……………………………………………………………2
2.3. Accessories …………………………………………………………………………2
2.4. Combinations ……………………………………………………………………… 3
2.5. Optional parts ……………………………………………………………………… 3
3. INSTALLATION WORK …………………………………………………………………… 3
3.1. Selecting an installation location ………………………………………………… 3
3.2. Drain processing …………………………………………………………………… 3
3.3. Installation dimensions …………………………………………………………… 3
3.4. Transporting the unit ………………………………………………………………4
3.5. Installing the unit …………………………………………………………………… 5
4. SYSTEM CONFIGURATION ………………………………………………………………5
4.1. System confi guration ……………………………………………………………… 5
4.2. Pipe selection ……………………………………………………………………… 5
4.3. Protection of pipes ………………………………………………………………… 6
5. PIPE INSTALLATION ………………………………………………………………………6
5.1. Brazing ………………………………………………………………………………6
5.2. Indoor unit pipe connections ……………………………………………………… 6
5.3. Opening the knockout hole ……………………………………………………… 7
5.4. Pipe connection …………………………………………………………………… 7
6. ELECTRICAL WIRING ……………………………………………………………………8
6.1. The precautions of electrical wiring ………………………………………………8
6.2. Knockout hole ……………………………………………………………………… 8
6.3. Selecting power supply cable and breaker ………………………………………8
6.4. Transmission line ……………………………………………………………………9
6.5. Wiring method ………………………………………………………………………9
6.6. External input and external output …………………………………………… 11
7. FIELD SETTING ………………………………………………………………………… 12
7.1. Field setting switches …………………………………………………………… 12
7.2. DIP switch setting ……………………………………………………………… 12
7.3. Rotary switch setting …………………………………………………………… 12
7.4. Push button setting ……………………………………………………………… 12
7.5. Address setting for signal amplifi ers …………………………………………… 14
7.6. Indoor unit address setting ……………………………………………………… 14
7.7. Resistance measurement of transmission cable
(Measure with breaker OFF) …………………………………………………… 14
8. PIPE INSTALLATION II ………………………………………………………………… 15
8.1. Sealing test ……………………………………………………………………… 15
8.2. Vacuum process ………………………………………………………………… 15
8.3. Additional charging ……………………………………………………………… 15
8.4. Installing insulation ……………………………………………………………… 16
8.5. Filling with putty ………………………………………………………………… 16
9. TEST RUN ……………………………………………………………………………… 16
9.1. Indoor unit connection check …………………………………………………… 16
9.2. Pre-check for test run …………………………………………………………… 17
9.3. Test run method ………………………………………………………………… 17
9.4. Checklist ………………………………………………………………………… 17
10. LED STATUS …………………………………………………………………………… 18
10.1. Normal operation codes ………………………………………………………… 18
10.2. Error codes ……………………………………………………………………… 18
11. INFORMATION ………………………………………………………………………… 18

En-2
CAUTION
This mark indicates procedures which, if improperly per-
formed, might possibly result in personal harm to the user, or
damage to property.
This unit must be installed by qualified personnel with a capacity certificate for handling
refrigerant fluids. Refer to regulation and laws in use on installation place.
The installation must be carried out in compliance with regulations in force in the place
of installation and the installation instructions of the manufacturer.
This unit is part of a set constituting an air conditioner. It must not be installed alone or
with non-authorized by the manufacturer.
This unit contains no user-serviceable parts. Always consult authorized service person-
nel to repairs.
When moving, consult authorized service personnel for disconnection and installation
of the unit.
Be sure to use a dedicated power circuit.
Never use a power supply shared by another appliance.
072/090 model
• This product is conformed to IEC/EN61000-3-2.
• This product is designed for professional use.
• On the power supply connection, obtain the connection permission of the distribution
network operator.
108/126/144/162 model
• This equipment complies with IEC 61000-3-12 provided that the short-circuit power
Ssc is greater than or equal to following table at the interface point between the user's
supply and the public system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution network operator if neces-
sary, that the equipment is connected only to a supply with a short-circuit power Ssc
than or equal to following table.
Model Short-circuit power Ssc
AJ*108LELBH 5.456 MVA
AJ*126LELBH 2.832 MVA
AJ*144LELBH 2.832 MVA
AJ*162LELBH 3.417 MVA
162 model
• This unit must be connected to a power supply with impedance of 0.441 ohm and
below. If the power supply does not satisfy this requirement, please consult the power
supplier.
Do not install the unit in the following areas:
• For the installation conditions if installing in an area of high salt damage such as the
coast, follow the Design & Technical Manual.
• Area filled with mineral oil or containing a large amount of splashed oil or steam, such
as a kitchen.
It will deteriorate plastic parts, causing the parts to fall or the unit to leak water.
• Area that generates substances that adversely affect the equipment, such as sulfuric
gas, chlorine gas, acid, or alkali.
It will cause the copper pipes and brazed joints to corrode, which can cause refriger-
ant leakage.
• Area containing equipment that generates electromagnetic interference.
It will cause the control system to malfunction, preventing the unit from operating
normally.
• Area that can cause combustible gas to leak, contains suspended carbon fibers or
flammable dust, or volatile flammables such as paint thinner or gasoline.
If gas leaks and settles around the unit, it can cause a fire.
• Avoid installing the unit at places where it will come into contact with animals’ urine or
ammonia.
The units are not explosion proof and therefore should not be installed in explosive
atmosphere.
Do not use the unit for special purposes, such as storing food, raising animals, growing
plants, or preserving precision devices or art objects. It can degrade the quality of the
preserved or stored objects.
Ground the unit. Do not connect the ground cable to a gas pipe, water pipe, lightning
rod, or a telephone ground cable. Improper grounding may cause electric shock.
Perform draining for the unit according to the Installation manual. Check that the water
is properly drained.
If the drain processing is improperly installed, water may drip down from the unit, wet-
ting the furniture.
Do not touch the fins with bare hands.
Be sure not to start or stop the operation of air conditioning with power breaker. Other-
wise, it may cause malfunction or water leakage.
When setting it up near the equipment that generates electromagnetic waves and the
equipment that generates the higher harmonics wave, be sure to take measures against
noise. Otherwise, it may cause malfunction or failure.
When energizing to the crankcase heater, please turn on the power 12 hours or earlier
before operation begins. When the energizing time is short, it may cause failure. Be-
sides, please do not turn off power during the busy season.
This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety. Children should be supervised to ensure that they
do not play with the appliance.
2. ABOUT THIS PRODUCT
2.1. Precautions for using R410A refrigerant
Pay careful attention to the following points:
Since the working pressure is 1.6 times higher than that of R22 models, some of the
piping and installation and service tools are special. (See the table in the SPECIAL
TOOLS FOR R410A section.)
Especially, when replacing a conventional refrigerant (other than R410A) model with
a new refrigerant R410A model, always replace the conventional piping and flare nuts
with the R410A piping and flare nuts.
Models that use refrigerant R410A have a different charging port thread diameter to pre-
vent erroneous charging with R22, R407C and for safety. Therefore, check beforehand.
[The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.]
Be more careful than the installation of the refrigerant (other than R410A) models, not
to enter foreign matters (oil, water, etc.) and other refrigerant into the piping. Also, when
storing the piping, securely seal the openings by pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composition
of the gas and liquid phases, and always charge from the liquid phase side whose
composition is stable.
2.2. Special tools for R410A
Tool name Contents of change for R22 tool
Gauge manifold
Pressure is huge and cannot be measured with a conven-
tional gauge. To prevent erroneous mixing of other refriger-
ants, the diameter of each port has been changed.
It is recommended to use a gauge manifold with a high
pressure display range -0.1 to 5.3 MPa and a low pressure
display range -0.1 to 3.8 MPa.
Charging hose To increase pressure resistance, the hose material and base
size were changed.
Vacuum pump
A conventional vacuum pump can be used by installing a
vacuum pump adapter.
• A conventional vacuum pump can be used by installing a
vacuum pump adapter.
• Be sure that the pump oil does not back flow into the
system. Use one capable for vacuum suction of -100.7kPa
(5 Ton, -755mmHg).
Gas leakage detector Special gas leakage detector for HFC refrigerant R410A.
2.3. Accessories
Use connecting parts as required.
Do not throw away the connecting parts until the installation has been complete.
Name and shape Q’ty Application
Specifications
manual
1 —
Installation manual
1
(This manual)
Drain cap
9
For outdoor unit drain piping
work
Drain pipe
1
For outdoor unit drain piping
work
Joint pipe A 1
(090 model
only)
For connecting gas pipe
(L type)
Joint pipe B 1
(090 model
only)
For connecting gas pipe
(Straight type)
Joint pipe C 1
(090 model
only)
For connecting liquid pipe
(Straight type)
Joint pipe A-L 1
(108/126/
144/162
model only)
For connecting gas pipe
(L type)
Joint pipe B-L 1
(108/126/
144/162
model only)
For connecting gas pipe
(Straight type)
Push mount cable tie
2
For binding transmission cable
Grommet edging
2
For power supply cable and con-
nection cable installation.
Attach to the knockout hole.

En-4
3.3.1 Single outdoor unit installation
When the upward area is open
Unit: mm
(1) Obstacles at rear only
100 or more
(2) Obstacles at rear and sides only
100 or more
300 or
more
80 or
more
(3) Obstacles at front only
1000 or more
(4) Obstacles at front and rear only
1000 or more
100 or more
When an obstruction is present also in the upward area
Unit: mm
(1) Obstacles at rear and above only
100 or
more
Max.
500
1000 or
more
(2) Obstacles at rear, sides, and above only
1500 or
more
80 or
more
100 or more
300 or
more
3.3.2 Multiple outdoor unit installation
• Provide at least 100 mm of space between the outdoor units if multiple units are
installed.
• When routing the piping from the side of an outdoor unit, provide space for the piping.
When the upward area is open
Unit: mm
(1) Obstacles at rear only
300 or
more
(2) Obstacles at front only
1500 or more
(3) Obstacles at front and rear only
500 or more
1500 or more
When an obstruction is present also in the upward area
Unit: mm
(1) Obstacles at rear and above only
• Up to 3 units can be installed side by side.
• When 4 units or more are arranged in a line, provide the space as shown below.
1500 or
more
500 or
more
Max.
300
1500 or
more
3.3.3 Outdoor units installation in multi row
* The following settings are not recommended in case of cooling by a low outside tem-
perature. Unit: mm
(1) Single parallel unit arrangement (2) Multiple parallel unit arrangement
100 or
more
600 or more
1000 or more
2000 or
more
500 or
more
600 or more
1500 or more
3000 or
more
3.4. Transporting the unit
WARNING
Do not touch the fins. Otherwise, personal injury could result.
CAUTION
When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or fingers may be pinched.
Hoisting method
• When hoisting the outdoor unit, hook the rope on the outside of the foot as shown in the
figure.
• Use sufficiently strong rope to bear the unit’s weight.
• Place protective board or filler cloth at the place where the cabinet may come into
contact with the rope to prevent damages. Without using them, the cabinet may be dam-
aged or deformed.
• The center of gravity of the outdoor unit is shifted to the right. Be careful not to tilt to the
heavy side causing it to fall.
• To prevent an accident caused by the unit swinging or falling down, do not apply any
impact to the unit when it is hanging.
• When hoisting, do not hook the rope to the thermistor holder on the back of the outdoor
unit.
Protective
boards
Foot Light
side
Heavy
side
700 to
1000 mm
Product mass (kg)
AJ*072LELAH 170
AJ*090LELAH 177
AJ*108LELAH 178
AJ*126LELAH 213
AJ*144LELAH 213
AJ*162LELAH 217
Lifting by forklift
• When using the forklift to lift the unit, pass
the forklift arms through the opening space
of the wooden delivery pallet.
• Be careful not to damaged.
Wooden delivery
pallet
Carrying by hand
• Carry slowly in the manner
as shown on “Fig. B” hold-
ing the handles “Fig. A”
in right and left sides. (Be
careful not to touch with
hands or objects.)
• Be sure to hold the
handles on the sides of
the unit. Otherwise, the
suction grilles on the
sides of the unit may be
deformed.
Handle
Handle
Handle
Fig. A Fig. B

En-6
Table. B (Diameter of piping used between outdoor unit and first separation
tube or header)
For the following installation conditions, it is necessary to increase the piping size.
• Condition 1: Total indoor unit capacity ratio 110%˃
• Condition 2: Between outdoor unit and first separation tube or header 70 m˃
If both conditions 1 and 2 are met, condition 2 is followed.
Model
Outdoor
unit
cooling
capacity
[kW]
Diameter of piping [mm (in)]
Liquid pipe Gas pipe
Stan-
dard
Condi-
tion 1
Condi-
tion 2
Stan-
dard
Condi-
tion 1
Condi-
tion 2
AJ*072
LELBH 22.4 9.52
(3/8) ←12.70
(1/2)
19.05
(3/4) ←22.22
(7/8)
AJ*090
LELBH 28.0 9.52
(3/8)
12.70
(1/2) ←22.22
(7/8) ← ←
AJ*108
LELBH 33.5 12.70
(1/2) ← ← 28.58
(1-1/8) ← ←
AJ*126
LELBH 40.0 12.70
(1/2) ← ← 28.58
(1-1/8) ← ←
AJ*144
LELBH 45.0 12.70
(1/2) ← ← 28.58
(1-1/8) ← ←
AJ*162
LELBH 50.0 12.70
(1/2) ← ← 28.58
(1-1/8) ← ←
Table. C (Diameter of piping used between separation tubes)
(If pipe diameter C > B, select pipe size from table B)
Total cooling
capacity of indoor
unit [kW]
Outside diameter [mm (in)] Separation
tube *4 Header *4
Liquid pipe Gas pipe
x < 11.2 9.52 (3/8) 15.88 (5/8)
UTP-AX054A UTR-H0906L
UTR-H0908L
11.2 x < 14.0 9.52 (3/8) 19.05 (3/4)≤
14.0 x < 19.7 12.70 (1/2) 19.05 (3/4)≤
19.7 x < 28.1 12.70 (1/2) 22.22 (7/8) UTP-AX090A≤
28.1 x 12.70 (1/2) 28.58 (1-1/8) UTP-AX180A≤UTR-H1806L
UTR-H1808L
*4: For the installation method, please refer to the installation manuals for indoor unit,
separation tubes or headers.
Use a standard separation tube for pipe branching. Do not use a T tube as it does not
separate the refrigerant evenly.
Table. D (Diameter of piping used between separation tube and indoor unit)
(If pipe diameter D > C, select pipe size from table C)
Model code of indoor
unit
Cooling capacity of indoor
unit (kW)
Outside diameter [mm (in)]
Liquid pipe Gas pipe
04, 07, 09 1.1, 2.2, 2.8 6.35 (1/4) 9.52 (3/8) (*5)
12, 14, 18 3.6, 4.5, 5.6 6.35 (1/4) 12.70 (1/2)
24, 30, 34, 36, 45,
54, 60
7.1, 9.0, 10.0, 11.2, 12.5, 14.0,
18.0 9.52 (3/8) 15.88 (5/8)
72, 90 22.4, 25.0 9.52 (3/8) 19.05 (3/4)
96 28.0 9.52 (3/8) 22.22 (7/8)
*5: Between separation tube and Indoor unit > 20 m 12.70 mm (1/2 in).→
Table. E (Indoor unit capacity comparison table - The indication of power is
different depending on the model.)
Model code of
indoor unit
04/
004
07/
007
09/
009
12/
012
14/
014
18/
018
24/
024
30/
030
34/
034
36/
036
45/
045
54/
054
60/
060
72/
072
90/
090
96/
096
Capacity [kW]
1.1 2.2 2.8 3.6 4.5 5.6 7.1 9.0
10.0 11.2 12.5 14.0 18.0 22.4 25.0 28.0
In the case of ARXD007GLEH: equivalent to model code of indoor unit
Model code 007 Capacity=2.2kW→
4.3. Protection of pipes
Location Working period Protection method
Outdoor 1 month or more Pinch pipes
Less than 1 month Pinch or tape pipes
Indoor — Pinch or tape pipes
• Protect the pipes to prevent the entry of moisture and dust.
• Especially pay attention when passing the pipes through a hole or connecting the end of
a pipe to the outdoor unit.
5. PIPE INSTALLATION
5.1. Brazing
CAUTION
If air or another type of refrigerant enters the refrigera-
tion cycle, the internal pressure in the refrigeration
cycle will become abnormally high and prevent the
unit from exerting its full performance.
Pressure regulating valve
Cap
Nitrogen gas
Brazing area
Apply nitrogen gas while brazing the pipes.
Nitrogen gas pressure: 0.02 MPa (= pressure felt suf-
ficiently on the back of your hand)
If a pipe is brazed without applying nitrogen gas, it will create an oxidation film.
This can degrade performance or damage the parts in the unit (such as the compressor
or valves).
Do not use flux to braze pipes. If the flux is the chlorine type, it will cause the pipes to
corrode.
In additio
n, if the flux contains fluoride, it will affect the refrigerant piping system due to
deterioration of refrigerant oil.
For brazing material, use phosphor copper that does not require flux.
5.2. Indoor unit pipe connections
CAUTION
For details, refer to the Installation Instruction Sheet of each part.
Separation tube
A
BA
B
B
A
± 15°
GOOD GOOD
Horizontal Vertical
Horizontal line
or
A:
Outdoor unit or Refrigerant
branch kit
B:
Indoor unit or Refrigerant
branch kit
PROHIBITED
Header
C
H1
α
1
β
1
D
H2
α2
β2
GOOD
GOOD
Horizontal line
Horizontal line
View D
View C
Horizontal line
Vertical line
Gas pipe
Liquid pipe
Outdoor
unit side
Outdoor
unit side
H1 = 0 to 10 mm
H2 = 0 to 10 mm
(α1: 0° to 1°)
β1: -10° to 10°
(α2: 0° to 1°)
β2: -10° to 10°
PROHIBITED
CAUTION
Do not connect a separation tube after a header.
Leave the distance 0.5 m or more for straight part to branch tube and header.
To indoor unit
To indoor unit
To indoor unit
Main pipe
Main pipe
0.5 m or more
0.5 m or more
To indoor unit
Separation tube
Header
To indoor unit
0.5 m or more
0.5 m or more
To indoor unit
Separation tube
Header

En-7
5.4.2 Removing the pinch pipe
WARNING
Remove the pinch pipe only when the internal gas is completely drained as shown on
the below instructions.
If gas still remains inside, the piping may crack if you melt the brazing filler metal of the
junction area with a burner.
Before connecting the piping, remove the pinch pipe in accordance with the following
instructions:
1) Verify that the liquid
side and gas side
3-way valves are
closed.
2) Cut the end of the liquid
side and gas side pinch
pipe and vent the gas
inside the pinch pipe.
3) After all the gas is vented, melt
the brazing filler metal on con-
necting part using a torch and
remove the pinch pipe.
3-way valves
Pinch pipes End of pinch pipes
5.4.3 Pipe connection
CAUTION
Seal the pipe route hole with putty (locally purchased) such that there are no gaps.
Small insects or animals that are trapped in the outdoor unit may cause a short circuit in
the electrical component box.
To prevent pipe damage; do not make sharp bends.
Bend the pipe at a radius of 70 mm or greater.
Do not bent pipe many times at same part to prevent break.
After completing all the pipe connection by brazing, perform the indoor unit pipe connec-
tion with a flare joint.
When removing the pinch pipe or brazing the joint pipe, carry out the work while cooling
down the 3-way valve sufficiently.
• Braze the joint pipe onto the 3-way valves at the liquid and gas side. Install the joint pipe
appropriately so that it can be connected easily with the main pipe.
• Braze the joint pipe at the liquid and gas side with the main pipe.
* Be sure to supply nitrogen when brazing.
Connection example
Front connection Bottom connection
Liquid pipe
(locally
purchased)
Gas pipe
(locally purchased)
C (accessory)
A (accessory)
Liquid pipe
(locally purchased)
Gas pipe
(locally
purchased)
B (accessory)
C (accessory)
A: Joint pipe A (090 model), Joint pipe A-L (108/126/144/162 model)
B: Joint pipe B (090 model), Joint pipe B-L (108/126/144/162 model)
C: Joint pipe C (090 model)
5.4.4 Handling precautions for the valves
• Mounted part of Blank cap is sealed for protection.
• Fasten blank cap tightly after opening valves.
Operating the valves
• Use a hexagon wrench.
Liquid valve: size 4 mm, Gas valve: size 8 mm.
Opening:
(1) Insert the hexagon wrench into the
valve shaft, and turn it counterclock-
wise.
(2) Stop turning when the valve shaft can
no longer be turned. (Open position)
Closing:
(1) Insert the hexagon wrench into the
valve shaft, and turn it clockwise.
(2) Stop turning when the valve shaft can
no longer be turned. (Closed position)
Opening
direction
Hexagon wrench
Seal
(blank cap
installation
portion)
Liquid
pipe Gas pipe
Opening
direction
5.3. Opening the knockout hole
CAUTION
Be careful not to deform or scratch the panel while opening the knockout holes.
To protect the piping insulation after opening a knockout hole, remove any burrs from
the edge of the hole. It is recommended to apply rust prevention paint to the edge of the
hole.
• Pipes can be connected from 3 directions, front, lateral side and bottom. (Fig. A)
• When connecting at the bottom, remove the service panel and piping cover on the front
of the outdoor unit, and open the knockout hole provided at the bottom corner of the
piping outlet.
9221
61 100
94 21
61 94
60 12
14 90
Unit: mm
Fig. A
Service panel
Top view of
the base
Front connection Lateral connection Bottom connection
• It can be installed as shown on “Fig. B” cutting out the 2 slits as indicated on “Fig. C”.
(When cutting slits, use a steel saw.)
Slit
Slit
Fig. B
Bottom
connection
Fig. C
5.4. Pipe connection
CAUTION
Do not use mineral oil on a flared part. Prevent mineral oil from getting into the system
as this would reduce the lifetime of the units.
While brazing the pipes, be sure to blow dry nitrogen gas through them.
The maximum lengths of this product are shown in the table. If the units are further
apart than this, correct operation cannot be guaranteed.
5.4.1 Bending pipes
CAUTION
To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of
curvature of 100 mm or more.
If the pipe is bent repeatedly at the same place, it will break.
• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes at an angle of more than 90°.
• When pipes are repeatedly bent or stretched, the material will harden, making it difficult
to bend or stretch them anymore.
• Do not bend or stretch the pipes more than 3 times.

En-10
6.5.2 Wiring procedure
• Remove the service panel. And connect the cable to the terminal in accordance with the
terminal name plate.
• Use a ring terminal to connect the electric cables to the power supply terminal board.
• Keep the earth cable longer than the other cables.
• After connecting the electric cable, secure them with a cable clamp.
• Connect the cable without applying excessive tension.
• Use the specified cable type and connect the cable securely.
Secure with a cable
clamp as shown in the
figure below.
Tightening torque
[N·m (kgf·cm)]
M3 screw 0.5 to 0.6 (5 to 6)
M5 screw 2.0 to 3.0 (20 to 30)
072, 090, 108 model
Power supply terminal
Ring terminal (M5)
Transmission terminal (M3)
Power supply cable
Power supply
cable
Transmission cable
Transmission cable
Push mount
cable tie
(accessory)
Push mount
cable tie
(accessory)
Cable clamp
Cable tie
Earth (ground)
cable
8 to 10 mm
45 to 50 mm
25 to
40 mm
25 to
30 mm
126, 144, 162 model
Power supply terminal
Ring terminal (M5)
Transmission
terminal (M3)
Power supply cable
Power supply
cable Transmission cable
Transmission
cable
Push mount cable tie (accessory)
Push mount
cable tie
(accessory)
Cable clamp
Cable tie
Earth (ground)
cable
8 to 10 mm
55 to 60 mm
55 to 60 mm
25 to 40 mm
35 to 40 mm
35 to 40 mm
126, 144
model
126, 144,
162 model
162 model
How to connect wiring to the terminal
Caution when wiring cable
(1) Use ring terminals with insulating sleeves as shown in the figure to connect to the
terminal block.
(2) Securely clamp the ring terminals to the cables using an appropriate tool so that
the cables do not come loose.
(3) Use the specified cables, connect them securely, and fasten them so that there is
no stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-
driver that is too small, otherwise, the screw heads may be damaged and prevent
the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table below for the terminal screw tightening torques.
Strip 10 mm
Cable
Screw with
special washer
Ring terminal
Terminal block
Ring terminal
Sleeve
Screw with
special washer
Ring terminal
Cable
Shielding the transmission cable
Connect both ends of the shielded
wire of the transmission cable to
the earth (ground) terminal of the
equipment or to the earth (ground)
screw near the terminal.
Be sure to use one side of a
twisted-pair cable when using
transmission cable with 2 sets of
twisted-pair cables.
Wind with insulation tape to prevent short circuit
Use one side
of the twisted
pair cable
Connect both ends of shielded
wire to earth (Ground).

En-11
6.6. External input and external output
6.6.1 Terminal position
CN136 BLK
EXT. OUT. 1
CN137 BLU
EXT. OUT. 2
CN131
YEL
CN132
GRN
CN134 RED
CN133
WHT
CN135
ORG
EXT. IN. 1
PLUSE. IN
EXT. IN. 4
EXT. IN. 2
EXT. IN. 3
CN115 BLK
BASE HEATER
Base heater
(CN115: Black) Outdoor unit PC board
Input 4
(CN134: Red)
Input 3
(CN133: White)
Input 2
(CN132: Green)
Input 1
(CN131: Yellow)
Input 5 (CN135: Orange)
Output 1 (CN136: Black)
Output 2
(CN137: Blue)
CAUTION
Do not bundle the cable for base heater with other cables.
When connecting
cable to Input 2
Cable (for external
input and output)
Push mount cable tie (accessory)
(tightened with transmission cable)
Push mount cable tie
(accessory) (tightened
with transmission
cable)
Cable (for external input and output)
* If the outdoor unit is not installed in the wall, cover the exposed
part of cable with a 1 mm thick or more insulation tubing.
Connection
example
(Power supply
terminal of 162
model is different
from drawing.)
6.6.2 External input terminal
Setting to low noise mode, cooling priority/heating priority selection, outdoor unit operation
peak control setting, emergency/batch stop and electricity meter pulse are possible from
the outside.
Wiring method and specifications
* A twisted pair cable (22 AWG (0.33 mm²)) should be used. Maximum length of cable is
150 m.
* Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed
* For each input, pin No. 1 is of positive polarity and pin No. 2 is of ground level.
Connected unit Connected unit Connected unit Connected unit Connected unit
Input 1
CN131
(Yellow)
Input 2
CN132
(Green)
Input 3
CN133
(White)
Input 4
CN134
(Red)
Input 5
CN135
(Orange)
P.C.B
Operation behavior
Each input terminal works as follows.
Connector Input signal Status
Input 1
CN131 (Yellow)
OFF Normal operation
ON Low noise mode operation
Input 2
CN132 (Green) (*1)
OFF Cooling priority
ON Heating priority
Input 3
CN133 (White)
OFF Normal operation
ON Outdoor unit operation peak control
Input 4
CN134 (Red)
OFF Normal operation
ON Batch stop or Emergency stop operation (*2, *3)
Input 5
CN135 (Orange)
(*4)
No pulse No information from electricity meter
Pulse Power usage information from electricity meter
The operations of each input terminal and the selection of function are set with the push
button on the PC board of outdoor unit. About the setting, please refer to “7.4. Push button
setting”.
NOTES:
*1: The “external input priority mode” must be set by pressing push button on PC board
of outdoor unit. (Refer to “7. FIELD SETTING”.)
*2: Batch stop or Emergency stop pattern can be selected by outdoor unit PC board
push button. (Refer to “7. FIELD SETTING”.)
*3: The emergency stop function mounted in this model does not guarantee the regula-
tions of each country. For this reason, sufficient checking is necessary regarding
use.
Especially, since the fact that the equipment may not be emergency-stopped in the
case of breaking of the wiring to the external input terminals and communication
line, communication error due to noise, VRF external input circuit trouble, etc. must
be considered, the provision of double measures that add direct interruption of the
power supply by switch, etc. is recommended as a precaution.
*4: Pulse input to CN135 must be width 50 ms or more, and must be interval 50 ms or
more.
6.6.3 External output terminal
You can detect the operation condition of outdoor unit and the abnormal situation of both
indoor and outdoor unit.
Wiring method and specifications
Error status
This output indicates the outdoor unit
and connected indoor unit's “Normal” or
“Error” status.
Operation status
This output indicates the outdoor unit's
“Operation” status.
Connector Output
voltage Status
Output1
CN136
(Black)
0V Normal
DC 12-24 V
(*5)
Error
Output2
CN137
(Blue)
0V Stop
DC 12-24 V
(*5)
Operation
P.C.B
CN136 (Black) or
CN137 (Blue)
DC power supply
(External) 12-24 V
Connected load (Operation Indica-
tor or Error Indicator)
Connected unit
*5: Provide a DC 12 to 24 V power supply.
Select a power supply capacity with an ample surplus for the connected load.
*6: The allowable current is 30 mA or less.
Provide a load resistance such that the current becomes 30 mA or less.
*7: Polarity is [+] for pin 1 and [-] for pin 2. Connect correctly.
Do not impress a voltage exceeding 24 V across pins 1-2.
* A twisted pair cable (0.33 mm² (22AWG)) should be used.
Maximum length of cable is 150 m.
* Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
6.6.4 Base heater terminal
This is the output signal for base heater. Output signal ON, when the outdoor temperature
goes down below 2°C, and signal OFF at the outdoor temperature 4°C.
Voltage:
power supply input voltage
cable
(0.82 mm2 (18AWG))
P.C.B.
Base heater *9
CN115
(Black)
*8
*8: Connect to pin 1 and pin 3. No connection pin 2 and pin 4.
*9: The allowable current is 1 A or less.

En-12
7.3. Rotary switch setting
The rotary switch (REF AD) sets the refrigerant circuit address of the outdoor unit. Config-
ure the settings only on the master unit of a refrigerant system.
If multiple refrigerant systems are connected, set the rotary switch (REF AD) as shown in
the table below.
Refrigerant
circuit
address
Rotary
Switch
Setting Setting Setting
range Type of switch
Refrigerant
circuit
address
0–99
Setting
example
63
REF AD
× 10
REF AD × 1
Rotary Switch (REF AD × 1): Factory setting “0”
Rotary Switch (REF AD × 10): Factory setting “0”
REF AD
×10 ×1
0 0 0
1 0 1
2 0 2
⁞ ⁞ ⁞
98 9 8
99 9 9
7.4. Push button setting
Various functions can be set. Set when necessary.
Perform settings after all indoor units have stopped operation.
Table. A: List of Settings
No Setting Item
7-segment display Factory
default
First 2
digits
Last 2
digits
00
Pipe length set-
ting (*1)
Standard (40 to 65 m)
0 0
0 0
Short (less than 40 m) 0 1
Medium (65 to 90 m) 0 2
Long 1 (90 to 120 m) 0 3
Prohibited 0 4
Pipe length means the length between master outdoor unit and the nearest indoor
unit.
10 Prohibited (Factory default) 1 0 0 0
11
Cooling capacity
shift (*1)
Normal mode
1 1
0 0
Save energy mode 0 1
High power mode 1 0 2
High power mode 2 0 3
Prohibited 0 4
Set this item when necessary.
12
Heating capacity
shift (*1)
Normal mode
1 2
0 0
Save energy mode 0 1
High power mode 1 0 2
High power mode 2 0 3
Set this item when necessary.
13 Prohibited (Factory default) 1 3 0 0
14 Prohibited (Factory default) 1 4 0 0
20
Switching be-
tween batch stop
or emergency
stop (*1)
Batch stop
2 0
0 0
Emergency stop 0 1
This mode selects the pattern of the stop function to be operated by the external
input terminal (CN134).
• Batch stop: The stop of all indoor units connected to same refrigerant system
due to input signal coming from CN134.
• Emergency stop: When emergency stop is actuated, the indoor unit does not
accept the operation command from the remote controller. On the other hand,
when the emergency stop is released (no input from CN134), the air conditioner
does not return to the original operation until the indoor unit is turned on by the
remote controller.
21
Operation mode
selecting method
(*1)
Priority given to the first com-
mand
2 1
0 0
Priority given to external
input of outdoor unit 0 1
Priority given to administra-
tive indoor unit 0 2
Select the priority setting of the operation mode.
•
Priority given to the first command: Priority is given to the operation mode which is set
first.
• Priority given to external input of outdoor unit: Priority is given to the operation
mode which is set by the external input terminal (CN132).
•
Priority given to administrative indoor unit: Priority is given to the operation mode
of the administrative indoor unit which is set by the wired remote controller.
22 Prohibited (Factory default) 2 2 0 0
23 Prohibited (Factory default) 2 3 0 0
24 High static pres-
sure mode
Standard
2 4
0 0
High static pressure 1
(equivalent to 072/090
model: 30 Pa, 108 model:
40 Pa, 126/144/162 model:
60 Pa)
0 1
25 Prohibited (Factory default) 2 5 0 0
26 Prohibited (Factory default) 2 6 0 0
27 Prohibited (Factory default) 2 7 0 0
28 Prohibited (Factory default) 2 8 0 0
29 Prohibited (Factory default) 2 9 0 0
7. FIELD SETTING
CAUTION
Discharge the static electricity from your body before setting up the DIP switches.
Never touch the terminals or the patterns on the parts that are mounted on the PC
board.
7.1. Field setting switches
Remove the service panel of the outdoor unit and the cover of the electrical component
box to access the PC board of the outdoor unit.
PC board switches for various settings and LED displays are shown in the figure.
7.2. DIP switch setting
7.2.1 List of Settings
SET 5 must be set for the DIP switch.
Configure the settings before turning
on the power. Settings for SET 1, SET
2, SET 3 and SET 4 DIP switches are
factory default ones. Do not change
them.
DIP Switch Function
SET 1 1-4 Prohibited
SET 2 1-4 Prohibited
SET 3 1-4 Prohibited
SET 4 1-4 Prohibited
SET 5 1-3 Prohibited
4 Terminal resistor setting
MODE
/NEXT SE LECT E NTE R SET1
SW101
SW102
REF AD
POW ER
MODE ERROR
× 1 0 × 1
SET2
LED 105
LED101
LED102
LED 104
SW111
7-Segment
displays
Push buttons
LED lamp
(green)
LED lamp
(red)
Rotary switches
Outdoor unit PC board
DIP switches
DIP switch (SET 5)
7.2.2 Terminating resistor setting
CAUTION
Be sure to set the terminal resistor according to specifications.
Set the terminal resistor for every network segment (NS).
If terminal resistor is set in multiple devices, the overall communication system may be
damaged.
If terminal resistor is not set in a device, abnormal communication may occur.
• Be sure to set 1 terminal resistor in a network segment. You can set the terminal resistor
at the outdoor unit or signal amplifier.
• When setting the terminal resistor of a signal amplifier, refer to the installation manual of
the signal amplifier.
• When setting multiple terminal resistors, take note of the following items.
(1) How many network segments are there in a VRF system?
(2) Where will you set the terminal resistors in a network segment? (Condition for 1 seg-
ment: Total number of outdoor and indoor units and signal amplifiers is less than 64,
or the total length of the transmission cable is less than 500 m)
(3) How many outdoor units are connected to 1 refrigerant system?
Configure the setting (DIP switch SET 5)
of the terminal resistor of the outdoor units
as shown below from conditions (1) to (3).
SET 5 Terminal
resistor Remarks
4
OFF Disable —
ON Enable (Factory setting)
Figure: Terminal resistor setting
NS2 (Network
segment 2)
NS3 (Network segment 3) NS4 (Network
segment 4)
NS1 (Network segment 1)
(Set terminal resistor at outdoor units)
Master unit
Master unit
Master unit
Refrigerant system 1
Refrigerant system 2
Refrigerant system 3
Terminal resistor: off
Terminal resistor: on
Terminal resistor: on
About the setting of
terminal resistor
Outdoor unit
Install
Do not
install
: On
: Off
Signal amplifier

En-13
30
Energy saving
level setting (*1)
Level 1 (stop)
3 0
0 0
Level 2
(operated at 40% capacity) 0 1
Level 3
(operated at 60% capacity) 0 2
Level 4
(operated at 80% capacity) 0 3
Level 5
(operated at 100% capacity) 0 4
The capacity limit can be selected by the external input terminal (CN133) when
operating with the “Energy Saving Peak Cut function”.
The lower the level, the more the effect of energy saving, but the cooling/heating
performance will also drop.
31 Prohibited (Factory default) 3 1 0 0
40
Capacity priority
setting (in low
noise mode) (*1)
Off (quiet priority)
4 0
0 0
On (capacity priority) 0 1
If the cooling/heating performance becomes insufficient when the low noise mode
is set, it is possible to set “capacity priority” that automatically cancels the low
noise mode (once performance is restored, the mode will automatically return to
the low noise mode).
41 Low noise mode
setting (*1)
Off (Normal) 4 1 0 0
On (Low noise mode) 0 1
42 Low noise mode
level setting
Level 1
4 2
0 0
Level 2 0 1
Prohibited 0 2
52 Prohibited (Factory default) (*4) 5 2 0 0
53 Prohibited (Factory default) 5 3 0 0
60 Prohibited (Factory default) 6 0 0 0
70
Electricity meter
No. setting 1 (*2)
Setting number (x00)
7 0
0 0
Setting number (x01) 0 1
······ ··· ···
Setting number (x98) 9 8
Setting number (x99) 9 9
Set the ones digit and tens digit of the No. of the electricity meter connected to
CN135.
71
Electricity meter
No. setting 2 (*2)
Setting number (0xx)
7 1
0 0
Setting number (1xx) 0 1
Setting number (2xx) 0 2
Set the hundreds digit of the No. of the electricity meter connected to CN135.
72
Electricity meter
pulse setting
1 (*3)
Setting number (xx00)
7 2
0 0
Setting number (xx01) 0 1
······ ··· ···
Setting number (xx98) 9 8
Setting number (xx99) 9 9
Set the ones digit and tens digit of the No. of the electricity meter pulse setting
connected to CN135.
73
Electricity meter
pulse setting
2 (*3)
Setting number (00xx)
7 3
0 0
Setting number (01xx) 0 1
······ ··· ···
Setting number (98xx) 9 8
Setting number (99xx) 9 9
Set the hundreds digit and thousands digit of the electricity meter pulse setting
connected to CN135.
90 Prohibited (Factory default) 9 0 0 0
*1: Do not set this for outdoor units with Slave setting.
*2: When electricity meter No. is set to “000” and “201 to 299”, the pulses input to
CN135 become ineffective. Available setting number is "001" to "200"
*3: When the electricity meter pulse setting is set to “0000”, the pulses input to CN135
become ineffective. Available setting number is "0001" to "9999"
*4: This item is not displayed for 072, 090, and 108 models.
(1) Turn on the power of the outdoor unit and enter standby mode.
• When system is normal
POWER/MODE lamp lights up. (ER-
ROR lamp is off.)
• When system is abnormal
Check the settings as there is an error in the
settings for outdoor unit address
(DIP switch SET 3-1, 2) or number of con-
nected slave units (DIP switch SET 3-3, 4).
MODE
/NEXT SELECT ENTER
POWER
MODE
ERROR
POWER/MODE
lamp: ON
ERROR
lamp: OFF
SELECT button
ENTER button
MODE/EXIT button
7-segment
display: off
MODE
/NEXT SELECT ENTER
POWER
MODE
ERROR
POWER/MODE
lamp: ON
7-segment display:
“-” display
ERROR lamp:
Blinking
(2) Setting method
Use the “MODE/EXIT”, “SELECT”,
and “ENTER” buttons to configure
settings according to the proce-
dures below.
(If no setting is made, the factory
default setting will be displayed.)
: Press the “MODE/EXIT” button
: Press the “SELECT” button
: Press the “ENTER” button.
: Press the “ENTER” button for
more than 3 seconds.
1: Function setting
7-segment LED display (LED 105, LED 104)
(Flashing)
First 2 digits Last 2 digits
(When [F3] to [F9] are displayed, continue to press
the “SELECT” button until [F2] is displayed.)
2: Setting the first
2 digits
3: Setting the last 2 digits
Continue to press the “SELECT” button until the
desired number appears at the last 2 digits.
Every press of the
“SELECT” button will
change the setting
number for the first 2
digits.
(Continue to press the “SE-
LECT” button until the desired
number appears at the last 2
digits.)
Setting is complete when the lamp lights up
Press “ENTER” button to return to “2: Setting the
first 2 digits” (If there is no operation for 5 seconds
after the setting, the display will return to “2: Setting
the first 2 digits”.)
Setting is complete when the lamp lights up
Press “ENTER” button to return to “2: Setting the
first 2 digits” (If there is no operation for 5 seconds
after the setting, the display will return to “2: Setting
the first 2 digits”.)
EXIT: Press the “MODE/EXIT” button to cancel the setting mode.
Produktspezifikationen
Marke: | Fujitsu |
Kategorie: | Klimaanlage |
Modell: | Airstage AJH144LELBH |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Fujitsu Airstage AJH144LELBH benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Klimaanlage Fujitsu

9 Oktober 2024

9 Oktober 2024

9 Oktober 2024

8 Oktober 2024

7 Oktober 2024

4 Oktober 2024

3 Oktober 2024

2 Oktober 2024

29 September 2024

26 September 2024
Bedienungsanleitung Klimaanlage
- Klimaanlage Samsung
- Klimaanlage Infiniton
- Klimaanlage Clatronic
- Klimaanlage Domo
- Klimaanlage Emerio
- Klimaanlage G3 Ferrari
- Klimaanlage Tristar
- Klimaanlage Sanyo
- Klimaanlage Manta
- Klimaanlage Medion
- Klimaanlage Nedis
- Klimaanlage Panasonic
- Klimaanlage Profile
- Klimaanlage LG
- Klimaanlage Adler
- Klimaanlage Bestron
- Klimaanlage Camry
- Klimaanlage Guzzanti
- Klimaanlage Princess
- Klimaanlage Trisa
- Klimaanlage Bosch
- Klimaanlage AEG
- Klimaanlage Ardes
- Klimaanlage Siemens
- Klimaanlage Bauknecht
- Klimaanlage Concept
- Klimaanlage Electrolux
- Klimaanlage Gorenje
- Klimaanlage Klarstein
- Klimaanlage Koenic
- Klimaanlage Teesa
- Klimaanlage Unold
- Klimaanlage Whirlpool
- Klimaanlage Alaska
- Klimaanlage Bomann
- Klimaanlage Essentiel B
- Klimaanlage H.Koenig
- Klimaanlage Korona
- Klimaanlage Listo
- Klimaanlage Melissa
- Klimaanlage Russell Hobbs
- Klimaanlage Taurus
- Klimaanlage Vox
- Klimaanlage TechniSat
- Klimaanlage Conrad
- Klimaanlage Day
- Klimaanlage ECG
- Klimaanlage Mesko
- Klimaanlage Telefunken
- Klimaanlage Thomson
- Klimaanlage Black And Decker
- Klimaanlage Trotec
- Klimaanlage Mestic
- Klimaanlage BEKO
- Klimaanlage Blaupunkt
- Klimaanlage Eldom
- Klimaanlage Grundig
- Klimaanlage Heinner
- Klimaanlage Home Electric
- Klimaanlage Hotpoint
- Klimaanlage Inventum
- Klimaanlage Koenig
- Klimaanlage Prime3
- Klimaanlage Primo
- Klimaanlage Sharp
- Klimaanlage Wilfa
- Klimaanlage Dometic
- Klimaanlage Ansonic
- Klimaanlage Ariston
- Klimaanlage Aspes
- Klimaanlage Brandt
- Klimaanlage Candy
- Klimaanlage Comfee
- Klimaanlage Corberó
- Klimaanlage Einhell
- Klimaanlage Daewoo
- Klimaanlage Everglades
- Klimaanlage Exquisit
- Klimaanlage Mitsubishi
- Klimaanlage Finlux
- Klimaanlage GE
- Klimaanlage Haier
- Klimaanlage Hisense
- Klimaanlage Hotpoint-Ariston
- Klimaanlage Bartscher
- Klimaanlage Kelvinator
- Klimaanlage Midea
- Klimaanlage NABO
- Klimaanlage Progress
- Klimaanlage Frigidaire
- Klimaanlage Svan
- Klimaanlage Vestel
- Klimaanlage Zanker
- Klimaanlage Zanussi
- Klimaanlage Philco
- Klimaanlage Eurom
- Klimaanlage Xiaomi
- Klimaanlage Avidsen
- Klimaanlage Akai
- Klimaanlage Arçelik
- Klimaanlage Hitachi
- Klimaanlage Hyundai
- Klimaanlage Orava
- Klimaanlage TCL
- Klimaanlage Toshiba
- Klimaanlage Livoo
- Klimaanlage DCG
- Klimaanlage Kärcher
- Klimaanlage Easy Home
- Klimaanlage Tectro
- Klimaanlage Sencys
- Klimaanlage Bimar
- Klimaanlage Klarbach
- Klimaanlage Lanaform
- Klimaanlage Rowenta
- Klimaanlage Sencor
- Klimaanlage DeLonghi
- Klimaanlage Element
- Klimaanlage Fakir
- Klimaanlage Kalorik
- Klimaanlage OneConcept
- Klimaanlage Rotel
- Klimaanlage Ufesa
- Klimaanlage Tripp Lite
- Klimaanlage Anslut
- Klimaanlage Calor
- Klimaanlage Cecotec
- Klimaanlage Vaillant
- Klimaanlage Termozeta
- Klimaanlage Centurion
- Klimaanlage Climadiff
- Klimaanlage Frilec
- Klimaanlage Inventor
- Klimaanlage Kibernetik
- Klimaanlage Qlima
- Klimaanlage Amcor
- Klimaanlage CHIGO
- Klimaanlage Duux
- Klimaanlage Honeywell
- Klimaanlage Klima1stKlaaS
- Klimaanlage Meaco
- Klimaanlage Remko
- Klimaanlage SHE
- Klimaanlage Sinclair
- Klimaanlage Suntec
- Klimaanlage Wood's
- Klimaanlage Zibro
- Klimaanlage Sigma
- Klimaanlage Globaltronics
- Klimaanlage Moa
- Klimaanlage Carson
- Klimaanlage Livington
- Klimaanlage Airlux
- Klimaanlage Broan
- Klimaanlage Elba
- Klimaanlage MPM
- Klimaanlage Thermex
- Klimaanlage White Knight
- Klimaanlage Logik
- Klimaanlage Team
- Klimaanlage Be Cool
- Klimaanlage Saunier Duval
- Klimaanlage Truma
- Klimaanlage Aermec
- Klimaanlage Orima
- Klimaanlage Proline
- Klimaanlage Dimplex
- Klimaanlage Sonnenkönig
- Klimaanlage Bavaria
- Klimaanlage Heylo
- Klimaanlage Toyotomi
- Klimaanlage Proklima
- Klimaanlage Westinghouse
- Klimaanlage Baxi
- Klimaanlage Amana
- Klimaanlage Carrefour Home
- Klimaanlage Galanz
- Klimaanlage Holland Electro
- Klimaanlage Vivax
- Klimaanlage Profilo
- Klimaanlage Sauber
- Klimaanlage Zelmer
- Klimaanlage Meireles
- Klimaanlage Kogan
- Klimaanlage Royal Sovereign
- Klimaanlage Innoliving
- Klimaanlage Argo
- Klimaanlage HQ
- Klimaanlage Jocca
- Klimaanlage Master
- Klimaanlage Sanus
- Klimaanlage Carrier
- Klimaanlage Edy
- Klimaanlage Frigor
- Klimaanlage Milectric
- Klimaanlage Be Quiet!
- Klimaanlage Insignia
- Klimaanlage Alpatec
- Klimaanlage Artrom
- Klimaanlage Coolix
- Klimaanlage D-Let
- Klimaanlage Gree
- Klimaanlage Gutfels
- Klimaanlage Heiko
- Klimaanlage Olimpia Splendid
- Klimaanlage TOSOT
- Klimaanlage SereneLife
- Klimaanlage Danby
- Klimaanlage APC
- Klimaanlage Ariston Thermo
- Klimaanlage Evolar
- Klimaanlage Ozito
- Klimaanlage Eden
- Klimaanlage Ferroli
- Klimaanlage Blumfeldt
- Klimaanlage RCA
- Klimaanlage Daikin
- Klimaanlage Starlyf
- Klimaanlage Soler & Palau
- Klimaanlage Esatto
- Klimaanlage Orbegozo
- Klimaanlage Dantherm
- Klimaanlage Furrion
- Klimaanlage Oregon Scientific
- Klimaanlage General Electric
- Klimaanlage Ridgid
- Klimaanlage Daitsu
- Klimaanlage Defy
- Klimaanlage Domair
- Klimaanlage Edgestar
- Klimaanlage Emerson
- Klimaanlage Emmeti
- Klimaanlage Fairland
- Klimaanlage Firstline
- Klimaanlage Fral
- Klimaanlage Fronius
- Klimaanlage Fuave
- Klimaanlage Fuji Electric
- Klimaanlage Innova
- Klimaanlage Itho
- Klimaanlage Jocel
- Klimaanlage Just Fire
- Klimaanlage Kenmore
- Klimaanlage Lavorwash
- Klimaanlage Maiko
- Klimaanlage Maxicool
- Klimaanlage MDV
- Klimaanlage Mistral
- Klimaanlage Mizushi
- Klimaanlage Mobile Airco
- Klimaanlage MundoClima
- Klimaanlage Prem-i-air
- Klimaanlage Protector
- Klimaanlage Qlima - Zibro
- Klimaanlage Retro
- Klimaanlage Salton
- Klimaanlage Seally
- Klimaanlage Shinco
- Klimaanlage SMC
- Klimaanlage SMD
- Klimaanlage SPT
- Klimaanlage Stirling
- Klimaanlage Tarrington House
- Klimaanlage Teco
- Klimaanlage Telair
- Klimaanlage Thermo Comfort
- Klimaanlage Trilec
- Klimaanlage Tronix
- Klimaanlage Whynter
- Klimaanlage Zymbo
- Klimaanlage Argoclima
- Klimaanlage Elgin
- Klimaanlage Kunft
- Klimaanlage Becken
- Klimaanlage Rinnai
- Klimaanlage Ravanson
- Klimaanlage Godrej
- Klimaanlage Friedrich
- Klimaanlage NewAir
- Klimaanlage Klimaire
- Klimaanlage EcoFlow
- Klimaanlage Andrews
- Klimaanlage Convair
- Klimaanlage Brivis
- Klimaanlage Malmbergs
- Klimaanlage Challenge
- Klimaanlage Arctic King
- Klimaanlage ElectriQ
- Klimaanlage Luma Comfort
- Klimaanlage Aircooler
- Klimaanlage Acson
- Klimaanlage Volteno
- Klimaanlage Geist
- Klimaanlage Monzana
- Klimaanlage Simplicity
- Klimaanlage Kaden
- Klimaanlage Equation
- Klimaanlage Daizuki
- Klimaanlage Cool Breeze
- Klimaanlage Braemar
- Klimaanlage Equator
- Klimaanlage Khind
- Klimaanlage Krone
- Klimaanlage GoldAir
- Klimaanlage American Comfort
- Klimaanlage Riffel
- Klimaanlage Airwell
- Klimaanlage Bonaire
- Klimaanlage MRCOOL
- Klimaanlage Arcoaire
- Klimaanlage Companion
- Klimaanlage SEEGER
- Klimaanlage Heat Controller
- Klimaanlage LERAN
- Klimaanlage IFB
- Klimaanlage ActronAir
- Klimaanlage Consul
- Klimaanlage HTW
- Klimaanlage B-Air
- Klimaanlage Schabus
- Klimaanlage Mabe
- Klimaanlage House & Luft
- Klimaanlage DEXP
- Klimaanlage Evapcool
- Klimaanlage Aerian
- Klimaanlage Ocean Breeze
- Klimaanlage Commercial Cool
- Klimaanlage Kaco
- Klimaanlage InAlto
- Klimaanlage Climachill
- Klimaanlage Create
- Klimaanlage Bodin
- Klimaanlage ARCTIC WIND
- Klimaanlage JHS
- Klimaanlage Keystone
- Klimaanlage FREONIC
- Klimaanlage Big Ass Fans
- Klimaanlage Electroline
- Klimaanlage Omega Altise
- Klimaanlage Avalon Bay
- Klimaanlage TURBRO
- Klimaanlage Norpole
- Klimaanlage Cool-Space
- Klimaanlage KuulAire
- Klimaanlage BLUEPALM
- Klimaanlage Akira
- Klimaanlage Airview
- Klimaanlage Aertesi
- Klimaanlage Alberello
- Klimaanlage Kubo
- Klimaanlage Aircool
- Klimaanlage KDK
- Klimaanlage Hokkaido
- Klimaanlage Bryant
- Klimaanlage Evapolar
- Klimaanlage Liebert
- Klimaanlage Polocool
- Klimaanlage Céliera
- Klimaanlage AFINTEK
- Klimaanlage Avallon
- Klimaanlage Columbia Vac
- Klimaanlage Vostok
- Klimaanlage Quirky
- Klimaanlage KwiKool
- Klimaanlage Senville
- Klimaanlage Goodwe
- Klimaanlage Swegon
- Klimaanlage BOSFOR
- Klimaanlage Aconatic
- Klimaanlage AireMax
- Klimaanlage VänEE
- Klimaanlage Mayer
- Klimaanlage Perfect Aire
- Klimaanlage Koldfront
Neueste Bedienungsanleitung für -Kategorien-

4 Dezember 2024

4 Dezember 2024

3 Dezember 2024

3 Dezember 2024

3 Dezember 2024

3 Dezember 2024

1 Dezember 2024

1 Dezember 2024

1 Dezember 2024

1 Dezember 2024