FSP/Fortron Proline TW 30 kVA Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für FSP/Fortron Proline TW 30 kVA (2 Seiten) in der Kategorie Unterbrechungsfreies Stromversorgungssystem. Dieser Bedienungsanleitung war für 5 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/2
Professional On-Line & Line-Interactive UPS Solutions
True Double Conversion 1.0kVA - 20kVA & 30kVA - 800kVA
Output Power Factor 0.9 - Rack/Tower 2 in 1 Design - LCD Display - Perfect Battery Pack
Proline Series Online UPS Systems
10/20/30 kVA with battery bank solution 3-Phase Input / 3-Phase Output
Designed in small footprints, Proline TW 3P/3P online series integrates true double conversion design, DSP technology, and
active input power factor correction design to ensure better output voltage conditions, power quality and power performance at
all times. Besides, easy-configurable program via LCD panel enhances the flexibility to meet ever-increasing power demand of IT
and networked environment.
Features & Advantages
True double-conversion
DSP technology guarantees high performance
Output power factor 0.8
Wide input voltage range (110-300 VAC)
Active power factor correction in all phases
50Hz/60Hz frequency converter mode
ECO mode operation for energy saving
Accepts dual-mains inputs
Emergency power off function (EPO)
Generator compatible
SNMP+USB+RS-232 multiple communications
3-stage extendable charging design for optimized battery performance
Adjustable battery numbers
Maintenance bypass available
Optional N+X parallel redundancy
Optional isolation transformer offers full isolation and complete common mode noise rejection
Proline TW 10/20 kVA
Proline TW 30 kVA
Proline TW 10/20 kVA rear view Proline TW 30 kVA rear view
Battery Bank for Proline Series 10/20/30 kVA UPS
Battery bank Battery Type Batteries Bank Capacity Dimension
BB-240/9RT 12V/9Ah 20 pcs 240V / 9Ah 580 x 438 x 133 mm
Backup Time: Please see the following Backup Time Table
Battery Bank for Proline Series 10/20/30 kVA UPS
Battery bank Battery Type Batteries Bank Capacity Dimension
BB-240/18T 12V/9Ah 40 pcs 240V / 18Ah 596 x 250 x 576 mm
BB-240/27T 12V/9Ah 60 pcs 240V / 27Ah 830 x 250 x 576 mm
Backup Time: Please see the following Backup Time Table
Backup Time Table for Proline TW Series 10/20/30 kVA UPS
Backup Time (min)
UPS Battery Bank 100% 75% 50%
Proline TW
PR-3310TL
Tower
10.0 kVA
without Internal Battery 0 0 0
+ 1 BB-240/9RT - 240V / 9 Ah 2,5 5,5 12,5
+ 1 BB-240/18T - 240V / 18 Ah 12,5 28 44
+ 1 BB-240/27T - 240V / 27 Ah 33,5 44 54,5
+ 2 BB-240/18T - 240V / 36 Ah 51 60 159
Proline TW
PR-3320TL
Tower
20.0 kVA
without Internal Battery 0 0 0
+ 1 BB-240/18T - 240V / 18 Ah 2,6 5,6 13,5
+ 1 BB-240/27T - 240V / 27 Ah 7,1 12,7 33,7
+ 2 BB-240/18T - 240V / 36 Ah 12,7 28 44
Proline TW
PR-3330TL
Tower
30.0 kVA
without Internal Battery 0 0 0
+ 1 BB-240/27T - 240V / 27 Ah 3,2 6,5 13,8
+ 2 BB-240/27T - 240V / 54 Ah 13 28,8 45
+ 4 BB-240/27T - 240V / 108 Ah 35 45 55
P Model kVA Form Datasheet Brochure Manual SNMP Card Software Price
1 PR-3310TL 10.0 kVA Tow er
PDF PDF PDF Go to SNMP Go to Software Pricelist2 PR-3320TL 20.0 kVA Tow er
3 PR-3330TL 30.0 kVA Tow er
Specification
Model PR-3310TL PR-3320TL PR-3330TL
Phase 3 phase in / 3 phase out
Capacity 10.0 kVA / 8kW 20.0 kVA / 16kW 30.0 kVA / 24kW
Input
Voltage Range 305-478 VAC (3-phase) @ 100% Load
190-520 VAC (3-phase) @ 50% Load
Frequency Range 46Hz ~ 54Hz or 56Hz ~ 64Hz
Power Factor 0.99 @ 100% Load
Output
Output Voltage 3x400 VAC (3Ph + N)
Voltage Regulation ± 1%
Frequency range
(Synchronized Range) 46Hz ~ 54Hz or 56Hz ~ 64Hz
Frequency Range
(Batt. Mode) 50Hz ± 0.1Hz or 60Hz ± 0.1Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion 2% THD (Linear Load) ; 5% THD (Non-linear Load)
Transfer
Time
Bypass to Inverter Zero
Inverter to Bypass Zero
Waveform (Batt. Mode) Pure Sinewave
Efficiency
AC Line Mode 89% 89% 89%
Battery Mode 86% 88% 87%
Battery
Long-Run
Model
Battery Type Depending on the capacity of external batteries
Numbers Depending on the capacity of external batteries
Charging Current
(max.) 4A 4A 4A
Charging Voltage 273 VDC ± 1% (based on 20 pcs batteries)
Indicators
LCD Display UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault condition
Alarm
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continously sounding
AC Input & Output Connectors
AC Input Connector Terminal
AC Output Connector Terminal
Standards
IEC 62040-1 (safety) Yes
IEC-62040-2 (EMC) Yes
CE Yes
Physical dimensions
Long-Run
Model
Dimension (mm) 592 (D) x 250 (W) x 826 (H) 592 (D) x 250 (W) x 826 (H) 815 (D) x 250 (W) x 826 (H)
Net Weight (kgs) 38 40 62
Environment
Humidity 0-90% RH @ 0-40°C (non-condensing)
Noise Level Less tahn 58dBa @ 1 Meter Less tahn 60dBa @ 1 Meter
Management
Smart RS-232 / USB Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser
*When using internal batteries from 18-19, the unit will de-rate according to the below formula: P = PRating x N/20.


Produktspezifikationen

Marke: FSP/Fortron
Kategorie: Unterbrechungsfreies Stromversorgungssystem
Modell: Proline TW 30 kVA
Display-Typ: LCD
Akustische Signale: Ja
Breite: 250 mm
Tiefe: 815 mm
Gewicht: 62000 g
Produktfarbe: Schwarz
Höhe: 826 mm
Stecker: Terminal
Betriebstemperatur: 0 - 40 °C
Relative Luftfeuchtigkeit in Betrieb: 0 - 90 %
Zertifizierung: IEC-62040-2\r\nCE
LED-Anzeigen: Ja
Geräuschpegel: 58 dB
Akku-/Batteriespannung: 12 V
Ausgangsspannung Gesamtverzerrungsfaktor THD: 2 %
Batteriekapazität: 9 Ah
Formfaktor: Tower
Kompatible Betriebssysteme: Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, MAC
Ausgangsleistung: 24000 W
Eingangsfrequenz: 46/64 Hz
Sicherheit: IEC 62040-1
Kühlung: Aktiv
Effizienz: 89 %
Anzahl der AC-Ausgänge: - AC-Ausgänge
Eingangs-Betriebsspannung (min): 190 V
Eingangs-Betriebsspannung (max): 520 V
Ausgangskapazität: 30 kVA
Ausgangs-Betriebsspannung (min): - V
Ausgangs-Betriebsspannung (max): - V
AC-Steckertypen: Terminal
Typische Backup-Zeit bei halber Belastung: - min
Typische Backup-Zeit bei voller Belastung: - min
Wellenform: Sine
Regulierung der Ausgangsspannung: 2 %
Nominale Ausgang Spannung: 400 V
Management-Plattform: SNMP, USB, RS-232
Anzahl der Eingangs-Phasen: 3
Crest-Faktor: 3:1
Ausgangs-Leistungsfaktor: 0.8
Notstrom Aus (EPO): Ja
Anzahl der Ausgangs-Phasen: 3