UT1500/2200E/EI
User’s Manual
K01-C000111-01
IMPORTANT SAFETY INSTRUCTIONS
(SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the
unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive
contaminants. (See the specifications for the acceptable temperature and humidity range.)
CAUTION! To reduce the risk of overheating the UPS, do not cover the UPS' cooling vents and avoid exposing the unit to direct sunlight or
installing the unit near heat emitting appliances such as space heaters or furnaces.
CAUTION! Do not attach non-computer-related items, such as medical equipment, life-support equipment, microwave ovens, or vacuum
cleaners to UPS.
CAUTION! Do not plug the UPS input into its own output.
CAUTION! Do not allow liquids or any foreign object to enter the UPS. Do not place beverages or any other liquid-containing vessels on or
near the unit.
CAUTION! In the event of an emergency, press the OFF button and disconnect the power cord from the AC power supply to properly
disable the UPS.
CAUTION! Do not attach a power strip or surge suppressor to the UPS.
CAUTION! Unplug the UPS prior to cleaning and do not use liquid or spray detergent.
CAUTION! Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions.
Keep unauthorized personnel away from batteries.
CAUTION! The battery supply should be therefore disconnected in the plus and minus pole at the quick connectors of the battery when
maintenance or service work inside the UPS is necessary.
CAUTION! Internal battery voltage is 12Vdc. Sealed, lead-acid, 6-cell battery.
CAUTION! When replacing the batteries, use the same number and type of batteries.
CAUTION! Do not dispose of batteries in a fire. The battery may explode. Do not open or mutilate the battery or batteries. Released
electrolyte is harmful to the skin and eyes.
INSTALLING YOUR UPS SYSTEM
UNPACKING
The box should contain the following:
UT1500/2200E-IN: (1) UPS Unit x1; (2) USB Cable x 1; (3)
Warranty Card x 1; (4)User Manual x 1
UT1500/2200E-AS: (1) UPS Unit x1; (2) USB Cable x 1; (3)User Manual x 1
PowerPanel® Personal Edition software is available on our website. Please visit www.cyberpower.com and go to the Software Section for
free download.
OVERVIEW
The UT1500/2200E series provide automatic voltage regulation for inconsistent utility power, and provides battery backup during power
outages. The UT1500/2200E series ensure consistent power to your computer system.
HARDWARE INSTALLATION GUIDE
1. Your new UPS may be used immediately upon receipt. However, recharging the battery for at least 8 hours is recommended to ensure
that the battery's maximum charge capacity is achieved. Charge loss may occur during shipping and storage. To recharge the battery,
simply leave the unit plugged into an AC outlet. The unit will charge in both the on and off position.
2. With the UPS unit off and unplugged, connect the computer, monitor, and any externally powered data storage device (Zip drive, Jazz
drive, Tape drive, etc. into the battery power supplied outlets. DO NOT plug a laser printer, copier, space heater, vacuum, paper
shredder or other large electrical device into the battery power supplied outlets. The power demands of these devices will
overload and possibly damage the unit.
3. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit
breaker and does not service equipment with large electrical demands (e.g. air conditioner, refrigerator, copier, etc. Avoid using
extension cords.
4. Press the power switch to turn the unit on. The power on indicator light will illuminate and the unit will "beep".
5. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug
at least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make sure the circuit breaker / fuse is
normal and then turns the UPS on.
6. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
7. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months
to ensure battery life.
BASIC OPERATION
1. Power Switch
Press the switch for 2 seconds to turn the UPS
ON or OFF.
2. Led Indicators
This LED is illuminated when the UPS is working.
3. Battery Capability Led Indicators
Indicate the battery capability from bottom up
Front panel
Back panel
1. USB Port to PC
This port allows connection and puter to the UPS unit. The UPS communicates communication from the USB port on the com
its status to the PowerPanel
® Personal Edition software.
2. Communication Protection Ports
Communication protection ports will protect any standard modem, fax, telephone line, or network cable
3. Input Circuit Breaker
The circuit breaker provides optimal overload protection.
4. Input power cord
Connect to utility power.
5. Battery Backup & Surge Protected Outlets
Provide battery backup and surge protection. They ensure power is provided to connected equipment over a
period of time during a power failure.
TECHNICAL SPECIFICATIONS DEFINITIONS FOR ILLUMINATED LED INDICATORS
LED
Alarm
Condition
On Off Normal
Flash Beep Twice Utility Failure - The UPS is providing battery power to outlets.
Flash Rapid Beeping Utility Failure - The UPS is providing battery power. The rapid beeps indicate the battery will run out
of power shortly.
On/Flash Constant Tone Overload - Occurs when connected equipment exceeds the rating of the unit. Turn the UPS off and
unplug at least one piece of equipment from the UPS.
TROUBLESHOOTING
Problem Possible Cause Solution
The UPS does not perform
expected runtime.
Batteries are not fully charged. Recharge the battery by leaving the UPS plugged in.
Battery is slightly worn out. Contact CyberPower Systems Technical Support.
The UPS will not turn on.
The unit is not connected to an AC outlet. The unit must be connected to a 220-240V outlet.
The battery is worn out. Contact CyberPower Systems Technical Support.
Mechanical problem. Contact CyberPower Systems Technical Support.
Outlets do not provide power to
equipment
Fuse is blown or breaker is tripped due to
overload.
Turn the UPS off and unplug at least one piece
connected equipment. Unplug the power cord of the
UPS then replace the blown fuse with a spare one or
press the circuit breaker knob. Connect power cord
then turn the UPS on. Make sure that your spare fuse
meets the specification.
Batteries are discharged Allow the unit to recharge for at least 4 hours.
Unit has been damaged by a surge or spike. Contact CyberPower Systems Technical Support.
For more information, visit www.cyberpower.com
All rights reserved. Reproduction without permission is prohibited.
6F, No. 32, Sec. 1, Chenggong Rd., Nangang District, Taipei 115, Taiwan
Model UT1500E UT1500EI UT1500E UT2200E UT1500E UT2200E UT2200EI UT2200E
Capacity (VA) 1500 2200
Watt (W) 900 1320
Input
Voltage Range 165~290Vac
Nominal Frequency 50 Hz
Output
On Battery Output
Voltage Simulated Sine Wave at 230Vac +/-5%
On Battery Output
Frequency 50 Hz +/-1%
Overload Protection Breaker / Fuse
Physical
Total # of UPS
Receptacles
4
SCHOKO 6 IEC 4 ASEAN 4 INDIA
4
SCHOKO 6 IEC 4 ASEAN 4 INDIA
Dimensions (W x H x
D)(mm) 148 X 178 X 298
Weight (kg) 9.1 kg 10.8 kg
Battery
Sealed Maintenance
Free Lead Acid Battery RBP0089 p2-x2 RBP0090 p2-x2
Typical Recharge Time 8 Hours
Warning Diagnostics
Indicators Power On / Using Battery
Audible Alarms On Battery, Low Battery, Overload, Fault
Surge Protection
Network/ Phone/ Fax/
Modem Protection YES
Communication
PowerPanel® Personal
Edition Software
Windows 8/7/Vista/XP/2000,Server 2012/2008/2003, Linux
Environmental
Operating Temperature 0ï‚°C to 40ï‚°C
Operating Relative
Humidity 0 to 90%
Management
Auto-Charger Yes
Auto-Restart Yes


Produktspezifikationen

Marke: CyberPower
Kategorie: UPS
Modell: UT2200E