CyberPower SM120KMF Bedienungsanleitung

CyberPower UPS SM120KMF

Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für CyberPower SM120KMF (5 Seiten) in der Kategorie UPS. Dieser Bedienungsanleitung war für 13 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/5
Users Manual
SM20KPM
SM200KMF
SM120KMF
SM060KMF
CyberPower Systems, Inc.
www.cyberpower.com
Safety Precautions
Modular UPS SM series User Manual - 1 -
Safety Precautions
This manual contains information concerning the installation and operation of Modular UPS . Please carefully read this manual prior to installation.
The Modular UPS cannot be put into operation until it is commissioned by engineers approved by the manufacturer (or its agent) Not doing so .
could result in personnel safety risk, equipment malfunction and invalidation of warranty.
The UPS has been designed for commercial or industrial use only, and is not intended for use in any life support This is a CLASS application. C
Uninterruptible Power Supply (UPS) product. In a domestic environment, this product may cause radio interference, in which case, the user may be
required to take additional measures.
Conformity and standards
This product complies with CE73/23 & 93/68 (low voltage safety) and 89/336 (EMC), and the following UPS product standards:
*IEC62040-1-1-General and safety requirements for use in operator access area
*IEC/EN62040-2 EMC requirements CLASS C
*IEC62040-3 Performance requirements and test methods
For more details, refer to Chapter 9. Continued compliance requires installation in accordance with these instructions and the use of
manufacturer approved accessories only.
WARNING: high earth leakage current
Earth connection is critical before connecting the input supply (include both utility supply and battery).
"Earth leakage current introduced by the UPS, in any configuration from 10kW to 200kW, exceeds 3.5 mA and is less than 1000 mA and
complies with the requirements of IEC/EN 62040 1 / IEC/EN 60950 1" Transient and steady state earth leakage currents, which may occur when - - -
starting the equipment, should be taken into account when selecting instantaneous RCCB or RCD devices.
Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional pulses (class A) and insensitive to transient current
pulses.
Note also that the earth leakage currents of the load will be carried by this RCCB or RCD.
This equipment must be earthed in accordance with local electrical authority codes of practice.
WARNING: back-feeding protection
This system has a control signal available for use with an automatic device, externally located, to protect against feeding voltage through back-
the mains Static Bypass circuit. If this protection is not used with the switchgear that is used to isolate the bypass circuit, a label must be added
to the switchgear to advise service personnel that the circuit is connected to a UPS system.
The text has the following meaning or is equivalent to: Isolate the UPS before working on the circuit of this UPS.
Components that can be maintained by user
All the equipment maintenance and servicing procedures involving internal access need special tools and should be carried out only by trained
personnel. The components that can only be accessed by opening the protective cover with tools cannot be maintained by user.
This UPS full complies with “IEC62040 General and safety requirements for use in operator access area UPS”. Dangerous voltages are -1-1-
present within the battery box. However, the risk of contact with these high voltages is minimized for non service personnel. Since the component -
with dangerous voltage can only be touched by opening the protective cover with a tool, the possibility of touching high voltage component is
minimized. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating
procedures in this manual.
Safety Precautions
Modular UPS SM series User Manual - 2 -
Battery voltage higher than 400Vdc
All the battery maintenance and servicing procedures involving internal access need special tools or keys and should be carried out only by
trained personnel.
SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED WITH THIS EQUIPMENT.
WHEN CONNECTED TOGETHER, THE BATTERY TERMINAL VOLTAGE WILL EXCEED 400Vdc AND IS POTENTIALLY LEATHAL.
Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large bank of battery
cells. These precautions should be followed implicitly at all times. Particular attention should be paid to the recommendations concerning local
environmental conditions and the provision of protective clothing, first aid and - fire fighting facilities.


Produktspezifikationen

Marke: CyberPower
Kategorie: UPS
Modell: SM120KMF

Brauchst du Hilfe?

Wenn Sie Hilfe mit CyberPower SM120KMF benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung UPS CyberPower

Bedienungsanleitung UPS

Neueste Bedienungsanleitung für -Kategorien-