CyberPower PR3000LCDSL Bedienungsanleitung


Lesen Sie kostenlos die đź“– deutsche Bedienungsanleitung fĂĽr CyberPower PR3000LCDSL (2 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war fĂĽr 8 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/2
PR2200LCDSL / PR3000LCDSL
User’s Manual
K01-0000287-01
(SAVE THESE INSTRUCTIONS)
This manual contains important instructions that must be followed during installation and maintenance of the UPS and batteries. Please read and
follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or
operate your UPS.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive
contaminants. (Please see specifications for acceptable temperature and humidity range).
CAUTION! To reduce the risk of electric shock, do not remove the cover except to service the battery. Turn off and unplug the unit before
servicing the batteries. There are no user serviceable parts inside except for the battery.
CAUTION! Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected.
CAUTION! The UPS must be connected to an AC power outlet with fuse or circuit breaker protection. Do not plug into an outlet that is not
grounded. If you need to de-energize this equipment, turn off and unplug the unit.
CAUTION! To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer
component.
CAUTION! Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment,
ANSI/NFPA 75.
CAUTION! To reduce the risk of fire, connect only to a circuit provided with 20 (PR2200LCDSL) or 30 (PR3000LCDSL) amperes maximum
branch circuit over current protection in accordance with the National Electric Code, ANSI/NFPA 70.
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not sell products for life support or medical
applications. use in any circumstance that would affect the operation and safety of life support equipment, medical applications, or DO NOT
patient care.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use with or near an aquarium. Condensation
from the aquarium can cause the unit to short out.
DO NOT USE THE UPS ON ANY TRANSPORTATION! To reduce the risk of fire or electric shock, do not use the unit on any transportation
such as airplanes or ships. The effect of shock or vibration caused during transit and the damp environment can cause the unit to short out.
INTRODUCTION
Thank you for selecting a CyberPower Systems UPS product. This UPS is designed to provide unsurpassed power protection, operation and
performance during the lifetime of the product.
UNPACKING
Inspect the UPS upon receipt. The box should contain the following:
(a) UPS unit (b) User’s manual (c) Function Setup Guide (d) Emergency Power Off cable (gray) (e) Serial cable (f) USB A+B type cable
*PowerPanel® Personal Edition software is available on our website.
Please visit www.cyberpower.com and go to the Software Section for free download.
OVERVIEW
The PR2200LCDSL/PR3000LCDSL provides complete power protection from utility power that is not
always consistent. The PR2200LCDSL/PR3000LCDSLfeatures surge protection against power surges
and maintenance free batteries for long lasting battery backup during power outages. In addition to
ensuring consistent power to your computer system and the PR2200LCDSL/PR3000LCDSL also
includes software that will automatically save your open files and shutdown your computer system during
a utility power loss.
AUTOMATIC VOLTAGE REGULATOR
The PR2200LCDSL/PR3000LCDSL stabilizes inconsistent utility power voltage to nominal levels that are
safe for equipment. Inconsistent utility power may be damaging to important data files and hardware, but
with Automatic Voltage Regulation (AVR), damaging voltage levels are corrected to safe levels. AVR automatically increases low utility power
and decreases high utility power to a consistent and safe 110/120 volts.
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
1. Ensure that the equipment plugged into the outlets does not exceed the UPS unit’s rated capacity (2070VA/1980W for PR2200LCDSL,
3000VA/2700W for PR3000LCDSL). If the rated capacities of the unit are exceeded, an overload condition may occur and cause the UPS
unit to shut down or the circuit breaker to trip.
2. There are many factors that can affect the amount of power that your computer system will require. It is suggested that the load placed on the
battery outlets not exceed 80% of the unit’s capacity.
HARDWARE INSTALLATION GUIDE
1. Your new UPS may be used immedi ately upon receipt. However, to ensure the battery’s maximum
charge capacity, it is recommended that you charge the battery for at least 8 hours. Your UPS is
equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will
automatically charge whether the UPS is turned on or off.
Note: This UPS is designed with a safety feature to keep the system from being turned on during
shipment.
The first time you turn the UPS on, you will need to have it connected to AC power or it will
not power up.
2. With the UPS unit turned off and unplugged, connect your computer, monitor, and any other peripherals requiring battery backup into the
battery power supplied outlets. DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or other large
electrical devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload and damage
the unit.
3. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is
protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air
conditioner, copier, etc…). The warranty prohibits the use of extension cords, outlet strips, and surge strips.
4. Press the power switch to turn the unit on. The Power On indicator light will illuminate and the unit will “beep”.
If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at
least one piece of equipment from the battery power supplied outlets. Make sure the circuit breaker is depressed and then turn the UPS on.
5. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
6. To store the UPS for an extended period, cover it and store with the battery fully charged. While in storage, recharge the battery every three
months to ensure battery life.
7. Ensure the wall outlet and UPS are located near the equipment being attached for proper accessibility.
DESCRIPTION
Front Panel
1 Power Switch
Used as the master on/off switch for equipment connected to the battery power
supplied outlets.
2 Power On Indicator
This LED is illuminated when the utility power is normal and the UPS outlets are
providing power, free of surges and spikes.
3 LCD Module Display
The intelligent LCD display shows all the UPS information using icons and messages.
For more information please review the “Definitions for Illuminated LCD Indicators”
section below.
4 Down/Display Button
The button can be used to select the LCD display contents including Input Voltage,
Output Voltage, and Estimated Run Time. Short press the button to scroll down the function menu. Pressing the button for 2 seconds will
keep the LCD display always on or turn the LCD display off while in AC/Utility power mode. For more information, please refer to the
Function Setup Guide.
5 Up/Mute Button
Short press the button to scroll up the function menu. Holding the button for more than 2 seconds will silence the alarm. For more
information, please refer to the Function Setup Guide.
6 Enter/Setup Button
Press the button for 2 seconds to enter the setup menu and then select the functions for configuration. For mor e information, please refer to
the Function Setup Guide.
Rear Panel
1 Battery and Surge Protected Outlets
The unit has seven battery powered/surge
suppression outlets for connected equipment to
ensure temporary uninterrupted operation of your
equipment during a power failure.
(DO NOT plug a laser printer, paper shredder,
copier, space heater, vacuum, sump pump or
other large electrical devices into the “Battery
and Surge Protected Outlets”. The power
demands of these devices may overload and
damage the unit.)
2 Serial/USB Ports to PC
The Serial and USB ports allow connection and
communication between the computer and the
UPS unit. Note: Only one port can be used at a
time.
3 EPO Port
Use the provided gray EPO cable to connect to a provided EPO contact
switch. Follow the appropriate circuit diagram to the right to wire the cable
to your EPO configuration. The EPO remote switch is a switch installed in
an outside area, connected to the unit via the Emergency Power Off cable.
In case of an emergency, it can be used to immediately cut-off power from
the UPS.
4 TVSS Ground
The TVSS GND only is used for dielectric voltage-withstand testing during
production.
5 SNMP/HTTP Network Slot
Remove the cover panel to install an optional RMCARD to remotely monitor and manage your UPS over a network.
6 Wiring Fault Indicator (red)
This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring. If this
is illuminated, disconnect all electrical equipment from the outlet and have an electrician verify the outlet is properly wired. The UPS will
operate normally and provide battery backup even if the indicator illuminates. However, the unit will not provide surge protection without
being plugged into a grounded and properly wired outlet.
7 AC Input Power Cord
Heavy-duty power cord.
8 Circuit Breaker
Located on the back of the UPS, the circuit breaker provides overload and fault protection.
REPLACING THE BATTERY
Replacement of batteries located in an OPERATOR ACCESS AREA.
When replacing batteries, replace with the same number of the following battery: CyberPower / RB1290X4K for the PR2200LCDSL and the
PR3000LCDSL. Contact CyberPower Systems about replacement batteries.
CAUTION! Risk of Energy Hazard, 12V, maximum 9 Ampere-hour batteries. Before replacing batteries, remove conductive jewelry such as
chains, wrist watches, and rings. High energy conducted through these materials could cause severe burns.
CAUTION! Do not dispose of batteries in a fire. The batteries may explode.
CAUTION! Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic.
CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING
TO LOCAL REGULATIONS.
BATTERY REPLACEMENT PROCEDURE:
1. Turn off and unplug all connected equipment.
2. Turn the UPS off and unplug it from the AC power source.
3. Remove the front panel of the UPS.
4. Remove screws from the battery compartment cover and slide the cover completely off of the unit.
5. Remove the batteries from the compartment.
6. Disconnect the battery wires from the batteries.
7. Install the replacement batteries by connecting the red wire (+) and black wire (-) to the same color connectors from the battery pack.
8. Put the batteries back into the compartment.
9. Re-install the battery compartment cover and tighten the retaining screws.
10. Put the front panel back on the UPS.
11. Connect to AC power and charge the new batteries for up to 16 hours to insure a full charge.
PR2200LCDSL / PR3000LCDSL
REMINDER: Batteries are considered and must be disposed of properly. Most retailers that sell lead-acid batteries HAZARDOUS WASTE
collect used batteries for recycling, as required by local regulations.
1. ONLINE: The UPS is supplying utility power to connected equipment.
2. BATTERY: During a severe brownout or blackout, this icon appears and an alarm sounds
(two short beeps followed by a pause) to indicate the UPS is operating from its internal
batteries. During a prolonged brownout or blackout, the alarm will beep rapidly every 1/2
second (and the BATT.CAPACITY meter shows one 20% capacity segment shaded. The
capacity depends on how much load added and the runtime left.) to indicate the UPS’s
batteries are nearly out of power. You should save files and turn off your equipment
immediately or allow the software to shut the system down.
3. Energy-Saving: The UPS in energy-saving bypass mode. When the utility power is
normal and the battery is fully charged, the UPS will go into energy-saving bypass mode
automatically. See “CyberPower GreenPower UPS
TM Technology” section for more
information.
4. LOAD capacity / Sensitivity setup: This meter displays the approximate output load level (in 20% increments) of the UPS battery outlets. It
can also be sensitivity setup meter if you are in Setup mode. It is to control the sensitivity of the UPS to switch to Battery Mode by selecting
UPS shutdown voltage range. When the sensitivity is increased, the UPS will switch to Battery Mode with less input power variation.
5. BATTERY capacity: This meter displays the approximate charge level (in 20% increments) of the UPS’s internal battery. During a blackout
or severe brownout, the UPS switches to battery power, the BATTERY icon appears, and the charge level decreases.
6. FAULT: This icon appears if there is a problem with the UPS. Press the POWER button to turn off the UPS.
F01: Battery Mode or AC/Utility Power Mode Overload fault (Turn on the UPS again.)
F02: Battery Output Short fault (Turn on the UPS again.)
F03: Charger Fault (Contact CyberPower Systems for support.)
F04: Internal Fault (Contact CyberPower Systems for support.)
F05: Fan Abnormal (Contact CyberPower Systems for support.)
7. OVER LOAD: This icon appears and an alarm sounds to indicate the battery-supplied outlets are overloaded. To clear the overload, unplug
BASIC OPERATION
INSTALLING YOUR UPS SYSTEM
IMPORTANT SAFETY INSTRUCTIONS
DEFINITIONS FOR ILLUMINATED LCD INDICATORS
PR2200LCDSL PR3000LCDSL
some of your equipment from the battery-supplied outlets until the icon turns off and the alarm stops.
8. SCHEDULE: Users can setup the schedule to turn on and shut down the computer and UPS through PowerPanel
® Personal Edition
software. The LCD display will show how much time is left before the UPS will turn back on or shut down.
9. ESTIMATED RUNTIME: This displays the run time estimate of the UPS with current battery capacity and load.
10. OUTPUT meter: This meter measure, in real time, the AC voltage that the UPS system is providing to the computer, such as normal line
mode, AVR mode, and battery backup mode. (Note: The OUTPUT meter shows the status of the battery backup outlets.)
11. INPUT meter: This meter measures the AC voltage that the UPS system is receiving from the utility wall outlet. The UPS is designed, through
the use of automatic voltage regulation, to continuously correct output voltage to connected equipment to a safe 110/120 voltage output
range. In the event of a complete power loss, severe brownout, or over-voltage, the UPS relies on its internal battery to supply consistent
110/120 output voltage. The INPUT voltage meter can be used as a diagnostic tool to identify poor-quality input power.
12. EVENT: This meter records the number of power outages.
13. SILENT: This icon appears whenever the UPS is in silent mode. The buzzer does not beep during silent mode until the battery reaches low
capacity.
14. AVR (Automatic Voltage Regulation): This icon appears whenever your UPS is automatically correcting low AC line voltage without using
battery power. This is a normal, automatic operation of your UPS, and no action is required on your part.
For more information about functions setup, please refer to the .Function Setup Guide
Problem Possible Cause Solution
Circuit breaker button is
projecting from the back of the
unit.
Circuit breaker has tripped due to an
overload.
Turn the UPS off and unplug at least one piece of
equipment. Wait 10 seconds, reset the circuit breaker by
pressing the button in, and then turn the UPS on.
The UPS does not perform
expected runtime.
Battery not fully charged. Recharge the battery by leaving the UPS plugged in.
Battery is worn out. Contact CyberPower Systems about replacement batteries
at tech@cpsww.com
The UPS will not turn on.
The on/off switch is designed to
prevent damage from rapidly turning
it off and on.
Turn the UPS off. Wait 10 seconds and then turn the UPS
on.
The unit is not connected to an AC
outlet. The unit must be connected to a 110/120V 60Hz outlet.
Battery is worn out. Contact CyberPower Systems about replacement batteries
at tech@cpsww.com
Mechanical problem. Contact CyberPower Systems at tech@cpsww.com
PowerPanel® Business Edition is
inactive (all icons are gray).
The USB / serial cable is not
connected.
Connect the USB / serial cable to the UPS unit and an open
USB / serial port on the back of the computer. You must
use the cable that came with the unit.
The USB / serial cable is connected
to the wrong port.
Check the back of the computer for an additional USB /
serial port. Move the cable to this port.
The unit is not providing battery
power.
Shutdown your computer and turn the UPS off. Wait 10
seconds and turn the UPS back on. This should reset the
unit.
The serial cable is not the cable that
came with the unit.
Please use the serial cable that came with the unit for the
software.
Additional troubleshooting information can be found under “Support” at https://www.cyberpower.com/
Model PR2200LCDSL PR3000LCDSL
Capacity 2070VA / 1980W 3000VA / 2700W
Nominal Input Voltage 120Vac
Input Frequency 60 Hz
Input Plug Type NEMA 5-20P NEMA L5-30P
Input Circuit Breaker 20A 30A
On-Battery Output Voltage 120Vac
On-Battery Output Wave Form Sine Wave
Operating Temperature + 32°F to 104° F / 0° C to 40° C
Operating Relative Humidity 0 to 90% non-condensing
Size (W x H x D)
6.7" x 8.7" x 17"
Net Weight 51.9lbs / 23.5kg 55.7lbs / 25.3kg
Typical Battery Recharge Time 5 hours to 90% capacity from total discharge
Typical Battery Life 3 to 6 years, depending on number of discharge/recharge cycles
Recommended Battery Sealed Maintenance Free Lead Acid Battery
Safety Approvals UL1778 4th, cUL CSA C22.2 No.107.3-05, FCC/DoC Class A
SYSTEM FUNCTIONAL BLOCK DIAGRAM
Advanced Energy-Saving Patented Bypass Technology
CyberPower’s patented GreenPower UPS™ with Bypass Technology reduces UPS energy costs by up to
75% compared to conventional UPS models. Even when utility power is normal, conventional UPS models
constantly pass power through a transformer. By contrast, under normal conditions the advanced circuitry of
a GreenPower UPS™ bypasses the transformer. As a result, the power efficiency is significantly increased
while decreasing waste heat, using less energy, and reducing energy costs.
When an abnormal power condition occurs, the GreenPower UPS™ automatically runs power through its transformer to regulate
voltage and provide “safe” power. Since utility power is normal over 88% of the time, the GreenPower UPS™ operates primarily in its
efficient bypass mode.
The GreenPower UPS™ is also manufactured in accordance with the Restriction on Hazardous Substances (RoHS) directive making
it one of the most environmentally-friendly on the market today.
Read the following terms and conditions carefully before using the CyberPower PR2200LCDSL/PR3000LCDSL (the “Product”). By
using the Product you consent to be bound by and become a party to the terms and conditions of this Limited Warranty and
Connected Equipment Guarantee (together referred to as this “Warranty”). If you do not agree to the terms and conditions of this
Warranty, you should return the Product for a full refund prior to using it.
Who is Providing this Warranty?
CyberPower Systems (USA), Inc. (“CyberPower”) provides this Limited Warranty.
What Does This Warranty Cover?
This warranty covers defects in materials and workmanship in the Product under normal use and conditions. It also covers
equipment that was connected to the Product and damaged because of the failure of the Product.
What is the Period of Coverage?
This warranty covers the Product for three years and connected equipment for as long as you own the Product.
Who Is Covered?
This warranty only covers the original purchaser. Coverage ends if you sell or otherwise transfer the Product.
How Do You Get Warranty Service?
1. Before contacting CyberPower, identify Your Product model number, the Purchase Date, and each item of Connected
Equipment (E.G. Computer tower, Computer Monitor, Ink Jet Printer, Cable Modem, etc).
2. Visit our web site at https://www.cyberpower.com/support/ or Call us at (877) 297-6937.
3. If your product requires warranty service you must provide a copy of your dated purchase receipt or invoice.
How Do You Open A Connected Equipment Claim?
1. Call us at (877) 297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave. E., STE 400, Shakopee, MN
55379, or send us an e-mail message at claims@cpsww.com for instructions, within 10 days of the occurrence.
2. When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment. Have
information on all applicable insurance or other resources of recovery/payment that are available to the Initial Customer and
Request a Claim Number.
3. You must provide a dated purchase receipt (or other proof of the original purchase) for the Cyber Power unit and connected
equipment. You also need to provide a description of the damage to your connected equipment.
4. Pack and ship the product to CyberPower and, if requested, the item(s) of Connected Equipment, a repair cost estimate for the
damage to the Connected Equipment, and all claim forms that CyberPower provides to you. Show the Claim Number on the
shipping label or include it with the product. You must prepay all shipping costs, you are responsible for packaging and
shipment, and you must pay the cost of the repair estimate.
How Long Do I Have To Make A Claim?
All claims must be made within ten days of the occurrence.
What Will We Do To Correct Problems?
CyberPower will inspect and examine the Product.
If the Product is defective in material or workmanship, CyberPower will repair or replace it at CyberPower's expense, or, if
CyberPower is unable to or decides not to repair or replace the Product (if defective) within a reasonable time, CyberPower will refund
to you the full purchase price you paid for the Product (purchase receipt showing price paid is required).
If it appears that our Product failed to protect any equipment plugged into it, p2-we will also send you forms for making your claim for the
connected equipment. We will repair or replace the equipment that was damaged because of the failure of our Product or pay you
the fair market value (NOT REPLACEMENT COST) of the equipment at of the time of the damage. We will use Orion Blue Book, or
another a third-party valuation guide, or eBay, craigslist, or other source to establish that amount. Our maximum liability is limited to
$375,000 for the PR2200LCDSL and PR3000LCDSL.
Who Pays For Shipping?
We pay when p2-we send items to you; you pay when you send items to us.
What isn’t covered by the warranty?
1. This Warranty does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any
data that is lost as a result of the failure or the restoration of data or records, or the reinstallation of software.
2. This Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the Product
or the equipment connected to it, nor for damage while in transit or in storage, nor if there has been improper operation or
maintenance, or use with items not designed or intended for use with the Product, such as laser printers, appliances, aquariums,
medical or life support devices, etc.
What are the Limitations?
The sole and exclusive remedies of the Initial Customer are those provided by this Warranty.
1. This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired
and grounded outlets (including compliance with electrical and safety codes of the most current electrical code), without the use
of any adapters or other connectors.
2. The Product must have been plugged directly into the power source and the equipment connected to the Product must be
directly connected to the Product and not “daisy-chained” together in serial fashion with any extension cords, another Product
or device similar to the Product, surge suppressor, or power tap. Any such installation voids the Limited Warranty.
3. The Product and equipment connected to it must have been used properly in a suitable and proper environment and in
conformance with any license, instruction manual, or warnings provided with the Product and the equipment connected to it.
4. The Product must have been used at all times within the limitations on the Product’s VA capacity.
The Product was designed to eliminate disrupting and damaging effects of momentary (less than 1ms) voltage spikes or impulses
from lightning or other power transients. If it can be shown that a voltage spike lasting longer than 1ms has occurred, the occurrence
will be deemed outside the rated capabilities of the Product and the Limited Warranty is void. CyberPower Does Not Cover or
Undertake Any Liability in Any Event for Any of the Following:
1. Loss of or damage to data, records, or software or the restoration of data or records, or the reinstallation of software.
2. Damage from causes other than AC Power Line Transients, spikes, or surges on properly installed, grounded and
code-compliant 120 volt power lines in the United States and Canada; transients, surges or spikes on standard telephone land
lines, PBX telephone equipment lines or Base 10T Ethernet lines, when properly installed and connected. (This exclusion
applies, for example, to fluctuations in data transmission or reception, by CATV or RF transmission or fluctuations, or by
transients in such transmission.)
3. Damage from any circumstance described as excluded above with respect to the Product.
4. Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse, misuse or alteration of either the
product or the Connected Equipment.
5. CyberPower excludes any liability for personal injury under the Limited Warranty and Connected Equipment Guarantee.
CyberPower excludes any liability for direct, indirect, special, incidental or consequential damages, whether for damage to or
loss of property [EXCEPT FOR (AND ONLY FOR) the specific limited agreement of CyberPower to provide certain warranty
benefits regarding "Connected Equipment" under this Warranty], loss of profits, business interruption, or loss of information or
data. NOTE: Some States or Provinces do not allow the exclusion or limitation of incidental or consequential damages, so the
above limitation may not apply to you.
6. The Product is not for use in high-risk activities or with aquariums. The Product is not designed or intended for use in hazardous
environments requiring fail-safe performance, or for use in any circumstance in which the failure of the Product could lead
directly to death, personal injury, or severe physical or property damage, or that would affect operation or safety of any medical
or life support device (collectively, "High Risk Activities"). CyberPower expressly disclaims any express or implied warranty of
fitness for High Risk Activities or with aquariums. CyberPower does not authorize use of any Product in any High Risk Activities
or with Aquariums. . ANY SUCH USE IS IMPROPER AND IS A MISUSE OF THE PRODUCT
Where Can I Get More Information?
The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded.
CyberPower is the warrantor under this Limited Warranty.
For further information please feel free to contact CyberPower at CyberPower Systems (USA), Inc. 4241 12th Ave E., STE 400,
Shakopee, MN 55379; call us at (877) 297-6937; or send us an e-mail message at claims@cpsww.com.
All rights reserved. Reproduction without permission is prohibited.
TECHNICAL SPECIFICATIONS
Limited Warranty and Connected Equipment Guarantee
CYBERPOWER GREENPOWER UPS TECHNOLOGY™
EMI
Filter
Surge
Suppressor
AVR
Charger
AC/DC
Battery
Inverter
Input Output
Normal Mode
Battery Mode
TROUBLESHOOTING


Produktspezifikationen

Marke: CyberPower
Kategorie: Nicht kategorisiert
Modell: PR3000LCDSL

Brauchst du Hilfe?

Wenn Sie Hilfe mit CyberPower PR3000LCDSL benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert CyberPower

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung fĂĽr -Kategorien-